Magnelab DCT-0010-005, AC CT, Self Powered, 5 Amp Average RMS 0-5V output
Features
Split Core
0-5V Average RMS Output
Cable Mounting
Self Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ⌀ 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Motor Control
Actuators
Lamp Failure
Specification
Magnelab Part Number
DCT-0010-005
Technology
AC Current Transformer
Supply Voltage
Self Powered
Load Current (RMS)
5 Amp
Maximum Measurement Current (RMS)
7.5 Amp
Output
0-5V (Average RMS) 5% Ripple
Response Time
300ms
Isolation
2.5kV (AC, 50Hz, 1 min)
Voltage Rating
Cat III 600VAC
Bandwidth
50/60Hz
Mounting Style
Cable Mount
Operating Temperature Range
-20°C / 50°C
Accuracy
2%
Aperture
⌀ 10mm
Termination Style
Screw
Approvals
CE,UL,ROHS2
Unit Weight
70g
Factory Pack Qty
6
Datasheet
Product Datasheet
Magnelab DCT-0010-050, AC CT, Self Powered, 50 Amp Average RMS 0-5V output
Features
Split Core
0-5V Average RMS Output
Cable Mounting
Self Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ⌀ 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Motor Control
Actuators
Lamp Failure
Specification
Magnelab Part Number
DCT-0010-050
Technology
AC Current Transformer
Supply Voltage
Self Powered
Load Current (RMS)
50 Amp
Maximum Measurement Current (RMS)
75 Amp
Output
0-5V (Average RMS) 5% Ripple
Response Time
300ms
Isolation
2.5kV (AC, 50Hz, 1 min)
Voltage Rating
Cat III 600VAC
Bandwidth
50/60Hz
Mounting Style
Cable Mount
Operating Temperature Range
-20°C / 50°C
Accuracy
2%
Aperture
⌀ 10mm
Termination Style
Screw
Approvals
CE,UL,ROHS2
Unit Weight
70g
Factory Pack Qty
6
Datasheet
Product Datasheet
Fastron Electronics GBMA-4-DA6-ANAN, 140x420mm Digital Ammeter, Panel Mount, 4-20mA Input, 100-240VAC/VDC supply, 4-20mA Transmission Output, with IR Remote Control
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-DA6-ANAN
Conditioner Output
4-20mA
Input
4-20mA
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics GBMT-4-K-ANNNN, 140x420mm Digital Voltmeter, Panel Mount, Type K Thermocouple Input, 100-240VAC/VDC supply, with IR Remote Control
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
BMT-4-K-ANNNN
Conditioner Output
N/A
Input
Tyep K Thermocouple -200°C to 1360°C
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics GBMT-4-K-ANNNY, 140x420mm Digital Panel Meter, Type K Thermocouple Input, 100-240VAC/VDC supply, with IR Remote Control, RS485 Modbus RTU
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Modbus RTU RS485
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMT-4-K-ANNNY
Conditioner Output
N/A
Input
Type K Thermocouple -200°C to 1360°C
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Comms
RS485 Modbus RTU
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics GBMA-4-DVO(0-150VDC)-ANNY, 140x420mm Digital Voltmeter, Panel Mount, 0-150V DC Input, 100-240VAC/DC supply, with IR Remote Control, RS485 Modbus RTU
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
RS485 Modbus RTU
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-DVO(0-150VDC)-ANNY
Conditioner Output
N/A
Input
0-150VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Comms
RS485 Modbus RTU
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics GBMA-4-DA6-ANNY, 140x420mm Digital Ammeter, Panel Mount, 4-20mA Input, 100-240VAC/VDC supply, with IR Remote Control, RS485 Modbus RTU
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-DA6-ANNY
Conditioner Output
N/A
Input
4-20mA
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Comms
RS485 Modbus RTU
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics GBMA-4-DA6-ANAY, 140x420mm Digital Ammeter, Panel Mount, 4-20mA Input, 100-240VAC/VDC supply, 4-20mA Transmission Output, with IR Remote Control, RS485 Modbus RTU
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
RS485 Modbus RTU
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-DA6-ANAY
Conditioner Output
4-20mA
Input
4-20mA
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Comms
RS485 Modbus RTU
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Westcode-IXYS-Littlefuse MCC95-18io1B, Dual Thyristor (SCR) Module, 95 Amp, 1800V
Features
Package with DCB ceramic
Electrically insulated base plate
Improved temperature and power cycling
Planar passivated chips
Very low forward voltage drop
Very low leakage current
3600V Isolation
Industrial standard package
20mm Base Width
Applications
Power Supplies
Rectifier for drives applications
Uncontrolled Rectifiers
Rectifiers for UPS
Battery Chargers
For single and three phase bridge configurations
Field supply for DC motors
Input rectifiers for PWM inverter
Specification
Westcode-IXYS-Littlefuse Part Number
MCC95-18io1B
Vrrm
1800V
Diode Configuration
Dual Thyristor Module
IF(av) @ 85 Deg C
116 Amp
Package Size
TO-240AA W:20mm L:93mm D:30mm
Itsm
2.25 kA
VF(to)
0.8V
Tj(max)
125°C
rF
2.4mΩ
Terminals
M5 Screw
Hole Centres
80mm (M6)
Gate Trigger Current
N/A
R th(j-c)
0.22°C/W
R th(c-h)
0.42°C/W
Weight
85g
Mounting Torque
3.25 Nm (3.25 Nm Terminals)
Factory Pack Qty
10
Certification
UL Listed, ROHS
IXYS Headquarters
United States
Datasheet
Product Datasheet
Alternatives
See DD100N16S for IXYS replacement. See DD104N14KOF for Infineon Pressure Contact Alternative
Crouzet 84873024, 3 Phase Voltage Monitoring Relay With 17.5mm SPDT Contacts, 3 x 208 - 480 V AC MWA, Sequence, Failure, Imbalance (asymmetry), Under/Over
MWA relays control, on 3-phase networks :
Overvoltage between phases,
Undervoltage between phases
Asymmetry (Imbalance)
Sequence Detection
Controls its own supply voltage
True RMS measurement
LED status indication
3-phase voltage controllers which monitor :
Undervoltage, adjustable from -20 to -2 % of Un
Overvoltage, adjustable from 2 to 20 % of Un
Asymmetry, adjustable from 5 to 15% of Selected Un
Presence of the neutral (H3USN only) Measurements are taken between Phases for the H3US
M3US and between Phases and Neutral for the H3USN Faults are signalled via LEDs, distinguishing the origin of the fault (one LED for the upper threshold, one LED for the lower threshold). Set the selector switch to the 3-phase network voltage Un.
The position of this selector switch is only taken into account when the unit is powered up. If the switch position changes while the unit is operating, all the LEDs flash but the product continues to work normally with the voltage selected on energisation prior to the change of position. The LEDs return to their normal state if the switch is reset to its initial position defined before the last energisation.
Specification
Crouzet Part Number
84873224 (3 Phase Voltage Monitoring Relay With SPDT Contacts)
Function
Undervoltage/Overvoltage between phases
Nominal Voltage
3 x 208 → 3 x 480 V ∿
Digital Outputs
1 x C/O Relays, 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/5VDC
Timing Range
0.3 → 30s (0, +10%)
Delay on Pickup
500ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Fixed Hysteresis
2% of Un
Maximum Measurement Cycle Time
150ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement 3 x 208 → 3 x 480 V ∿
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Application Notes
Legend
1
Overvoltage
2
Hysteresis
3
Undervoltage
4
Phases L1, L2, L3
5
Relay R1
6
Relay R2
7
Overvoltage threshold delay
8
Undervoltage threshold delay
The relay monitors its own supply voltage. It controls :
Undervoltage, adjustable from - 2 to - 20 % of Un (-2 to -12 % over the 3 x 220 V ∿ range due to the minimum voltage 194 V ∿)
Overvoltage, adjustable from + 2 to +20 % (+2 to +10 % over the 3 x 480 V ∿ range due to the maximum voltage 528 V ∿). Each threshold has its own time delay with independent setting between 0.3 and 30 s. In the event of a voltage fault, the corresponding relay (one undervoltage output/one overvoltage output) opens at the end of the time delay set by the user. In the event of phase failure, both relays open instantaneously, without waiting for the end of the time delay. The two relay LEDs go out. The relay monitors its own supply voltage. It controls :
Presence of the neutral, - Undervoltage, adjustable from -2 to -20 % of Un, - Overvoltage, adjustable from +2 to +20 %. Each threshold has its own time delay with independent setting between 0.3 and 30 s. In the event of a voltage fault, the corresponding relay (one undervoltage output/one overvoltage output) opens at the end of the time delay set by the user. If neutral is lost, both relays open instantaneously and the corresponding LED is extinguished, without waiting for the end of the time delay. The two relay LEDs are extinguished.
Fastron Electronics SCT-F16-25, 25/0.333V Measurement Split Core Current Transformer
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F16-25
Technology
Split Core AC Current Transformer
Ratio
25/0.333V
Aperture Size
ø 15 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
25Amp x 1.2
Termination Style
0.5M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Timer Chronos2 88827103 Timer Chronos2 MUR3 20-30VDC & 20- 264 VAC, Can be replaced by BM1R05MV1 (5 Amp)
MUR3 Timers Syrline 17.5 mm - 1 C/O Relay 8A :
Multi-range (0.1s - 100hrs)
Multi-voltage 12 →240 V AC/DC
LED status indicator
Possibility of external load connection in parallel to the control input
3-wire PNP sensor compatible
Multifunction Timers Includes The Following :
Function A Delay on energisation 1 relay
Function Ac Timing after closing and opening of control contact 1 relay
Function At Timing on energisation with memory 1 relay
Function B Timing on impulse one shot 1 relay
Function Bw Timing pulse output (adjustable)
Function C Timing after impulse 1 relay
Function D Flip-flop Pause start 1 relay
Function Di Flip-flop Pulse start 1 relay
Function H Timing on energisation 1 relay
Function Ht Delay on energisation with memory 1 relay
Specification
Crouzet Part Number
88827103 (Syr-Line Timer SinglePole Double Throw 1 x 8A Multifunction, 12 - 240VAC/DC, 17.5 mm)
Function
Multifunction Timer A - Ac - At - B - Bw - C - D - Di - H - Ht
Nominal Voltage
12 → 240 V AC/DC
Digital Output
1 x C/O (DPDT) (Changeover -Single Pole Double Throw-), 250VAC/DC @ 8 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Selectable 0.1s - 1s - 10s - 1 min - 10min - 1h, 10h, 100h
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Isolation
4kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
Screw
Weight
80g
Certification
CE, cULus,CCC, ROHS, Reach, WEEE
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Cross Reference
Can Be Replaced by BM1R05MV1 (5 Amp) or BM1R16MV1
Can Be Replaced by BM1R05MV1 (5 Amp) or BM1R16MV1
Replaces MRU1