Eastron Smart X96-5-MID, Panel Mount Multifuction Meter, Class 1, 173-480VAC, 1A/5A CT input, 30 Parameter, 2 x Digital Pulse/Alarm Outputs, Modbus RTU RS485 Comms, Self Powered, MID Approved
Metering and Numerical Display
Adjustable tariff clock (Optional 4 Tarriffs), display of electric energy consumption in optional currency
Modbus RTU as standard
True RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 30 quantities (U, I, P, THD, IHD, S, PF, PA, f, f, MD, etc.).
Accuracy class 1
Optional 2 or 4 tariff inputs,
Digital Output and Input
Ethernet communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD with Dual Metering and PF Displays
Specification
Eastron Part Number
Smart X96-5-MID
Functions
Power Quality Meter, Energy Meter
Aux Supply
Through Measurement Inputs
Nominal Measurement Range
173-480V L-N, 1/5 Amp
Maximum Measurement Range
280V L-N, 1/5 Amp
Pulse Outputs
2 x Digital Outputs (shared with Alarm function)
Alarm
2 x Digital Outputs (shared with Pulse function)
Tariff Input
1 (Optional 4 x )
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
2.5kV (1 Min)
RS485
2400-38400 b/s
Weight
500g
Certification
MID, UL
Factory Pack Qty
1
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Operating Temperature
-25 →+55 °C
Datasheet
Product Datasheet
User Manual
Modbus Registers
Trent NBR-CH14/UQ/16A/690V, gR Semiconductor Fuse, 16 Amp, 51x14mm 690V Semiconductor I²t Fuse Cartridge Style 51 x 14mm
Features
Cylindrical Standard Fuses Sizes
Wide Range of I²t
Ratings up to 125 Amp
Quick Release with RT18-63L fuse holder
DIN Rail Mount with RT18-63L fuse holder
Compatible with all 58 x 21mm fuse holders
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Solid State Relay Switchboards
Bridge rectifier Fusing
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-CH14/UQ/40A/690V
Fuse Type
I²t gR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating (Pre-Arcing)
75 A²/s
Nominal Current (RMS + DC)
16 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
51 x 14mm
Fuse Holder
RT18-63L
Mounting Style
Requires fuse holder
Operating Temperature Range
-40°C / 125°C
Watt Loss
8W
DC Breaking Capacity
50kA
Unit Weight
60g
Factory Pack Qty
10
Datasheet
Product Datasheet
Compatible Fuse Holder
RT18-63L
Crydom DC500D60, Solid State Relay, DC 3-32VDC control, 60A, 500VDC Load
Features
Rating of 60 Amp @ 1-500VDC
Mosfet output for reliable DC switching
Multiple modules can be wired in parallel for higher currents
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
DC500D60
Switching Type
DC Load
ROHS
Yes (Details)
Control Voltage
3.5-32VDC
Load Current
60 Amp DC
Surge Capability (10ms)
95 Amp DC
Special Feature
IP20 Cover
Mounting Style
Panel Mount
Load Voltage Range
1 - 500VDC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
See alternative D1D40K with raised terminals for alternative or D1D80 for higher current alternative
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
GIC Controls 45D331AR, Temp Control Relay with NTC Probe, For Traction Lift Monitoring Monitoring, 24VDC, Relay Output
3-digit display (0.5s response)
CE/ROHS Approved
Each unit needs just 17.5mm width Din Rail space
EC Compliant
Specification
GIC Controls Part Number
45D331AR
Control Output
Relay NO 5 Amp/NC 3 Amp (Resistive)
Input
External NTC Sensor (Included)
Mounting Style
17.5 x 75mm Din Rail Mount
Trip Window
5 to 40 Deg C
Supply Voltage
24VDC
Termination Style
Screw
Weight
300g
Factory Pack Qty
1
ROHS
Yes
CE
Yes
Datasheet
Datasheet
Fastron FES521-FD-420T, Solid Core AC Current Transducer, Multirange 0-10A,20A, 50A, Self Powered, Average RMS 4-20mA Output. 1% Accuracy (FCS521-SD-420E)
Compact and versatile current switches for detection of AC Currents, Multirange 0-10Amp, 0-20Amp, 0-50Amp via jumper, 4-20mA True RMS output
Features
True RMS 4-20mA output
Multirange selector
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Highly accurate low current measurement down to 1Amp
High isolation between primary and secondary circuits
Easy installation
Applications
Fault Detection
Motor or Fan Protection
Application Domain
Energy and Automation
Specification
Fastron Part Number
FES521-FD-420T
Technology
Solid Core Solid Core AC Current Transducer
Range
0-10Amp, 0-20Amp, 0-50Amp via jumper
Supply Voltage
Self Powered
Load Current (RMS)
1Amp to 50 Amp
Output
4-20mA True RMS
Isolation
2kV (AC, 50Hz, 1 min)
Bandwidth
50/60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
1%
Termination Style
Screw Terminals
Unit Weight
200g
Certifications
UL E320368, CE, Rohs compliant
Datasheet
Product Datasheet
Installation Guide
F710, Series +/-15VDC Bipolar Power Supply 85-265VAC
Open frame solution
Din Rail Mount
RMS Output with Galvanic Isolation
Opitons Include 85-265VAC
Output Current 800mA RMS x 2
Operating Temperature Range: 0 to 50 Deg C
Datasheet
Fastron FES2151-FP-V10, Split Core AC Current Transducer, Multirange 0-100A,150A, 200A, Self Powered, Average RMS 0-10V Output. 1% Accuracy FCS2151-SP-V10
Compact and versatile current switches for detection of AC Currents, Multirange 0-10Amp, 0-20Amp, 0-50Amp via jumper, 0-10V True RMS output
Features
Average RMS 0-10V output
Multirange selector
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Highly accurate low current measurement down to 1Amp
High isolation between primary and secondary circuits
Easy installation
Applications
Fault Detection
Motor or Fan Protection
Application Domain
Energy and Automation
Specification
Fastron Part Number
FES2151-FD-V10
Technology
Solid Core Split Core AC Current Transducer
Range
0-100Amp, 0-150Amp, 0-200Amp via jumper
Supply Voltage
Self Powered
Load Current (RMS)
1Amp to 200 Amp
Output
0-10V Average RMS
Isolation
2kV (AC, 50Hz, 1 min)
Bandwidth
50/60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
1%
Termination Style
Screw Terminals
Unit Weight
200g
Certifications
UL E320368, CE, Rohs compliant
Datasheet
Product Datasheet
Installation Guide
Iskra IK40-30-24VAC/DC, 3 Pole 3 x SPST NO, Modular Contactor 440VAC 40 Amp, 24VAC/DC 40-500Hz Control Voltage, Hum Free
Features
40 Amp (rms) @ 440VAC
DIN Rail Mount
Changeover Contact
Slim package
CE Compliant to IEC 60664
IP20
Specification
Fastron Part Number
IK40-30-24VAC/DC
Switching Type
3 x SPST NO
Approvals
CE
Coil Voltage
24VAC/DC
Load Current (RMS/DC)
40 Amp (rms) @ 440VAC
Special Feature
Hum Free
Mounting Style
DIN Rail Mount
Load Voltage Range
440VAC 40-500Hz
Isolation
4kV
Termination Style
Screw
Unit Weight
295g
Factory Pack Qty
20
Datasheet
Contactor Datasheet
Iskra IK63-30-24VAC/DC, 3 Pole 3 x SPST NO, Modular Contactor 440VAC 63 Amp, 24VAC/DC 40-500Hz Control Voltage, Hum Free
Features
63 Amp (rms) @ 440VAC
DIN Rail Mount
Changeover Contact
Slim package
CE Compliant to IEC 60664
IP20
Specification
Fastron Part Number
IK63-30-24VAC/DC
Switching Type
3 x SPST NO
Approvals
CE
Coil Voltage
24VAC/DC, 40-500Hz
Load Current (RMS/DC)
63 Amp (rms) @ 440VAC
Special Feature
Hum Free
Mounting Style
DIN Rail Mount
Load Voltage Range
440VAC, 40-500Hz
Isolation
4kV
Termination Style
Screw
Unit Weight
295g
Factory Pack Qty
20
Datasheet
Contactor Datasheet
Magnelab HCT-0010-010, Split Core DC Hall Effect Current Sensor, 10 Amp, +/-4V Output, Split Core 10mm Aperture, X = 1%
Features
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Applications
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
Magnelab Part Number
HCT-0010-010
Technology
Split Core Open Loop Hall Effect
Aperture
ø10mm
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
10 Amp
Measurement Range
+/-15 Amp
Output
+/-4 V
Isolation
4 kV
Bandwidth
DC
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 75°C
Accuracy
1%
Termination Style
Flying Lead
Unit Weight
80g
Factory Pack Quantity
10
Datasheet
Product Datasheet