Fastron Electronics GBMA-4-DA6-ANNY, 140x420mm Digital Ammeter, Panel Mount, 4-20mA Input, 100-240VAC/VDC supply, with IR Remote Control, RS485 Modbus RTU
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-DA6-ANNY
Conditioner Output
N/A
Input
4-20mA
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Comms
RS485 Modbus RTU
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics GBMA-4-DA6-ANAY, 140x420mm Digital Ammeter, Panel Mount, 4-20mA Input, 100-240VAC/VDC supply, 4-20mA Transmission Output, with IR Remote Control, RS485 Modbus RTU
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
RS485 Modbus RTU
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-DA6-ANAY
Conditioner Output
4-20mA
Input
4-20mA
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Comms
RS485 Modbus RTU
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
DCBT-300-24-420, Hall Effect DC Current Transducer, +/-300 Amp DC, 4-20mA bipolar output, 24VDC supply, 20mm Aperture
Compact and versatile Split Core DC current sensor, +/-300 Amp DC, 4-20 mA Bipolar Output
Features
⌀20mm Aperture
DC Bipolar Measurement
4-20mA analogue output
Busbar, or panel mounting
Isolated plastic case recognised according to UL94-V0
Advantages
High isolation between primary and secondary circuits
Easy installation
DIN Rail Kit available
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
Fastron Part Number
DCBT-300-24-420
Technology
DC Hall Effect Current Transducer with Instant Output
Yes
Supply Voltage
24VDC
Nominal Current (RMS + DC)
+/-300 Amp
Response Time
< 1uS
Output
Bipolar 4-20mA Analogue
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
DC
Aperture
20mm
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Molex 4 Pin
Unit Weight
120g
Factory Pack Qty
6
Datasheet
Product Datasheet
Fastron Electronics SCT-F16-25, 25/0.333V Measurement Split Core Current Transformer
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F16-25
Technology
Split Core AC Current Transformer
Ratio
25/0.333V
Aperture Size
ø 15 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
25Amp x 1.2
Termination Style
0.5M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F16-150-1A, 150/1 Amp Measurement Split Core Current Transformer, 16mm Aperture
Features
Quick Release Split Core System
Cable Mount
1 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F16-150-1A
Technology
Split Core AC Current Transformer
Ratio
150/1 Amp
Aperture Size
ø 15 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
1 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
150Amp x 1.2
Termination Style
0.5M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F16-150-5A, 150/5 Amp Measurement Split Core Current Transformer, 16mm Aperture
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F16-150-5A
Technology
Split Core AC Current Transformer
Ratio
150/5 Amp
Aperture Size
ø 15 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
150Amp x 1.2
Termination Style
0.5M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F16-175-5A, 175/5 Amp Measurement Split Core Current Transformer, 16mm Aperture
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F16-175-5A
Technology
Split Core AC Current Transformer
Ratio
175/5 Amp
Aperture Size
ø 15 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
175Amp x 1.2
Termination Style
0.5M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
LEM ART-B22-D175-SP3, AC Measurement Rogowski Coil (coil only). 17.5cm Diameter, Class 0.5, 3M Shielded Cable Connection
Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary circuit (measurement). The patented Perfect Loop Technology dramatically reduces both the error due to the position of the measured conductor within the aperture, and the error due to the proximity of external conductors.
The ART series single phase flexible rope CT from LEM. In conjunction with AI-PMUL combined integrator & signal conditioner LEM offer True RMS 0-5V, 0-10V, 0-20mA, 4-20mA outputs, or direct linear outputs 0.333V or 0.166V
Included is a 17.5cm diameter rope CT, and 1.5M of twisted pair (1000V) output leads for connection to an integrator, or meter/logger with integration function.
LEM coils come with 5 year warranty
Features
Rated insulation voltage 1000 V Cat III PD2
Accuracy Class 0.5 (IEC 61869-2)
Protection degree IP67
? 70, ? 125, ? 175, ? 300 mm sensing aperture
3 m output cable (other lengths available see page 8)
Ambient temperature ?40 °C … +80 °C
Very flexible and thin coil: 6.1 mm
Slot for attaching the loop on the primary with a cable tie
? 2 mm hole to pass a security seal tampering
An innovative patented clasp drastically reduces the positioning error near the closing
Internal shield for enhanced measurement accuracy at low primary currents.
Advantages
Thin, flexible, and light weight solution
Very low positioning error
Quick, non-intrusive and easy setup
A single sensor for a large current range without overload
Less influenced by external fields
Adaptable for a large range of cable diameters
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010; IEC 61010-2-32 ed.3: 2012
1) IEC 61869-1 ed1.0: 2007; IEC 61869-2: ed1.0: 2012
1) IEC 61869-6: draft 2016; IEC 61869-10: draft 2016
UL
Specification
LEM Part Number
ART-B22-D175-SP3
Function
AC Current Measurement
Measuring Range
0 - 5,000 Amp RMS (Contact Us for Possible Replacement for wider range)
Secondary Voltage (Sensitivity)
22.5mV
Frequency Measuring Range
50-300kHz
Operating Voltage
Self Powered
Accuracy
0.5% from 25 to 5000 Amp
Phase Angle
< 0.004
Coil Diameter (?)
17.5cm
Coil Circumference
55cm
Integrator to Coil Cable
3M Twisted Pair
Maximum Voltage
1000V Reinforced insulation according to EN 61010-1
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
7.4kV
Overload
350,000 Amp
Termination Style
2 Stripped Wires
Weight
138g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
Product Datasheet
Application Notes
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modeling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ? 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ? 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
LEM ART-B22-D300-SP4, AC Measurement Rogowski Coil (coil only). 30cm Diameter, Class 0.5, 4.5M Shielded Cable Connection
Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary circuit (measurement). The patented Perfect Loop Technology dramatically reduces both the error due to the position of the measured conductor within the aperture, and the error due to the proximity of external conductors.
The ART series single phase flexible rope CT from LEM. In conjunction with AI-PMUL combined integrator & signal conditioner LEM offer True RMS 0-5V, 0-10V, 0-20mA, 4-20mA outputs, or direct linear outputs 0.333V or 0.166V
Included is a 30cm diameter rope CT, and 1.5M of twisted pair (1000V) output leads for connection to an integrator, or meter/logger with integration function.
LEM coils come with 5 year warranty
Features
Rated insulation voltage 1000 V Cat III PD2
Accuracy Class 0.5 (IEC 61869-2)
Protection degree IP67
⌀ 70, ⌀ 125, ⌀ 175, ⌀ 300 mm sensing aperture
3 m output cable (other lengths available see page 8)
Ambient temperature −40 °C … +80 °C
Very flexible and thin coil: 6.1 mm
Slot for attaching the loop on the primary with a cable tie
⌀ 2 mm hole to pass a security seal tampering
An innovative patented clasp drastically reduces the positioning error near the closing
Internal shield for enhanced measurement accuracy at low primary currents.
Advantages
Thin, flexible, and light weight solution
Very low positioning error
Quick, non-intrusive and easy setup
A single sensor for a large current range without overload
Less influenced by external fields
Adaptable for a large range of cable diameters
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010; IEC 61010-2-32 ed.3: 2012
1) IEC 61869-1 ed1.0: 2007; IEC 61869-2: ed1.0: 2012
1) IEC 61869-6: draft 2016; IEC 61869-10: draft 2016
UL
Specification
LEM Part Number
ART-B22-D300-SP4
Function
AC Current Measurement
Measuring Range
0 - 5,000 Amp RMS (Contact Us for Possible Replacement for wider range)
Secondary Voltage (Sensitivity)
22.5mV
Frequency Measuring Range
50-300kHz
Operating Voltage
Self Powered
Accuracy
0.5% from 25 to 5000 Amp
Phase Angle
< 0.004
Coil Diameter (⌀)
30cm
Coil Circumference
95cm
Integrator to Coil Cable
4.5M Twisted Pair / Coax
Maximum Voltage
1000V Reinforced insulation according to EN 61010-1
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
7.4kV
Overload
300,000 Amp
Termination Style
2 Stripped Wires
Weight
155g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
Product Datasheet
Application Notes
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modeling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Eastron SDM630MCT-MODBUS-MID-CL0.5 V2, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 0.5S, 1/5Amp Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms, MID Approved
1/5 Amp CT Input
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 0.5S
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-MODBUS-MID-CL0.5 V2
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
1/5Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 0.5 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
Eastron SDM630MCT-MV, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 1, 0.333V CT Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms, SAA Approved
0.333V CT Input
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-MV
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
0.333V
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III, CE, SAA220473
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility