GMTA-DV6-D-RN, DC Voltage Transducer with Alarm, 0-300VDC Input, 22-60VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DV6-D-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-300VDC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron FDV-500-V05-24, DC Voltage Transducer, Din Rail Mount, 0-500VDC, 5V output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-500-V05-24
Analogue Output
5V
Input
0 - 500VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Accuracy
1%
Response Time
150mS
Voltage Isolation (1 min)
2.5kV
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron FDV-300-V05-24, DC Voltage Transducer, Din Rail Mount, 0-300VDC, 0-5V output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-300-V05-24
Analogue Output
0-5V
Input
0 - 300VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron TTH-32-DB-3, Relative Humidity Sensor and Transmitter, 190 x 18-19mm w/3M Cable, Can replace GEFRAN TRANSMICOR T211
1 x 4-20mA Output 2 Wire
Humidity Measurement for RH 0 to 100 %
Long Term Stability <2% RH per year
190 x 18mm with 3M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Thin Film Capacitor Sensing Elements
Specification
Fastron Part Number
TTH-32-DB-3
Sensor Type
Thin Film Capacitor (Humidity)
No of Wires
2
Shaft Length
190mm
Shaft Thickness
18-19mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet
Installation Guide
Wiring Diagram
Fastron FDV-15-420-24, Battery DC Voltage Transducer, Din Rail Mount, 0-15VDC, 4-20mA output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-15-420-24
Analogue Output
4-20mA
Input
0-15VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron FDV-100-V05-12, DC Voltage Transducer, Din Rail Mount, 0-100VDC, 0-5V output, 12VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-100-V05-12
Analogue Output
0-5V
Input
0 - 50VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
12VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
F923 Series DC Current Transducer with Process Outputs & High and Low C/O Alarm
Features
Isolated measurement of DC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F923-X-XX-DC-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Fastron FDV-300-V05-12, DC Voltage Transducer, Din Rail Mount, 0-300VDC, 0-5V output, 12VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-300-V05-12
Analogue Output
0-5V
Input
0 - 300VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
12VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron FDV-300-420-24, DC Voltage Transducer, Din Rail Mount, 0-300VDC, 4-20mA output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-300-420-24
Analogue Output
4-20mA
Input
0 - 300VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics GT-D-C-SP02, 0-150VDC Voltage Transducer, 22-60VAC/DC aux, 4-20mA output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-D-C-SP02
Control Output
4-20mA
Input
0 - 150VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22 - 60VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
GMTA-DV7-A-RN, DC Voltage Transducer with Alarm, 0-600VDC Input, 100-240VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DV7-A-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-600VDC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
F921 DC Series Current Transducer 100mA to 400 Amp Range with Adjustable High and Low C/O Relay Alarm
Features
Isolated measurement of DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F921-X-XX-DC-XX-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-400 Amp (Sensor dependant)
Maximum Measurement Range
2500 Amp with External Sensor
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet