LEM ART-B22-D300-SP4 + AI-PMUL, Single Phase Rogowski Coil Set, Class 1, User Selectable 0.333v, 0.166v, True RMS 4-20mA, 0-20mA, 0-10V, 0-5V Outputs, Sensitivity, and Measurement Range, 30cm Diameter
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D300-SP4 + AI-PMUL
Function
Single Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 30cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
4.5M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
Â
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Â
RCS-1200-0500 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1200 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-1200-0500
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
500 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 500 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Fastron Electronics SCT-F50-200, 0.333V, 200Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-200
Technology
Split Core AC Current Transformer
Ratio
200/0.333V
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
200Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
200g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
Crouzet 87622162, Totalizer/Counter with orange Backlit Display CTR24 10-264VAC/DC, Lithium Battery Powered 8 year battery Life
Hour Meter with two PNP Inputs
IP65
4-30VDC PNP Inputs
6 Digit Display (8mm)
10-264VAC/DC Aux Supply
48 x 24mm Cutout
Rest On Panel or External Inhibit
Datasheet
Product Datasheet
Fastron Electronics SCT-F50-100, 0.333V, 100Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-100
Technology
Split Core AC Current Transformer
Ratio
100/0.333V
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
Fastron Electronics FESCTHY-51-800-100mA, 800Amp measurement Split Core Current Transformer, w/1M Flying leads, 51x51mm Aperture
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Electronics Part Number
FESCTHY-51-800-100mA
Technology
Split Core AC Current Transformer
Ratio
800/100mA
Aperture Size
51 x 51mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mAAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
800Amp x 1.2
Termination Style
1M Twisted Pair 0.34mm^2
Unit Weight
950g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
RCS-1200 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1200 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-1200-3000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
3000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Fastron Electronics FESCT-19-100-100mV, 100Amp measurement Split Core CT's, Class 1, w/1M Flying Leads, HY2.0 Connection, 19x19mm Aperture Current Transformer
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
FESSCT-19-100-100mV
Technology
Split Core AC Current Transformer
Ratio
100/100mV
Aperture Size
19 x 19mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mVAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
100Amp x 1.2
Termination Style
1M Twisted Pair 0.34mm^2
Unit Weight
350g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics FESCT-19-250-100mA, 250Amp/100mA measurement Split Core CT's, w/1M Flying Leads, HY2.0 Connection, 19x19mm Aperture, 100mV Class 1 Series Current Transformer
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
FESSCT-19-250-100mA
Technology
Split Core AC Current Transformer
Ratio
250/100mA
Aperture Size
19 x 19mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mA (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
250Amp x 1.2
Termination Style
1M Twisted Pair 0.34mm^2
Unit Weight
350g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Iskra Doo WM1-6 Series Single Phase Power Meter
65 Amp direct connect, no CT's required
Ultra slim 2 DIN
RS 232/RS 485 communication up to 19,200 bit/s
True RMS values of currents and voltages
Measurements of active, reactive power
The meter is intended for measuring, and monitoring single-phase electrical power networks. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Optional Modbus RS232/RS485 communication up to 19,200 bit/s communication
Optional Pulse Output
Graphic LCD with illumination
Multilingual support
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
WM1-6 230WWNA
Functions
Energy Meter
Supply Voltage
230V L-N, 5 Amp +/-20% < 5VA
Nominal Measurement Range
230V L-N, 5 Amp +/-20%
Maximum Measurement Range
230V L-N, 5 Amp +/-20%
Nominal Current Input
65 Amp AC Direct Connect
Infra Red Output
19200
Tariff Input
N/A (Optional)
Accuracy
Class 1 (I,U,F,PF,) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Dimensions
36 x 90 x 64mm (2 DIN)
Pulse Output
N/A
Isolation
4kV
RS232/RS485
1200-19200 b/s (Optional)
Weight
270g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
RCS-2400-1000 Three-Phase Flexible Current Sensor System(Rogowski Coils):
The RCS-2400 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-2400 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-2400-1000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
1000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
8 Inch
Coil Circumference
24 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Fastron Electronics SCT-F36-100-5A, 5 Amp, 150Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F36-100-5A
Technology
Split Core AC Current Transformer
Ratio
100/5 Amp
Aperture Size
ø 35 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
400g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's