FPT-135 4000/1A 5P20 15VA Protection Class CT, 4000/1A, Class 5P20 15VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 4000/1A 5P20 15VA
Technology
Protection Class Current Transformer
Ratio
4000/5
Aperture Size
81 x 135mm
VA Rating
15VA
Accuracy Class
Class 5P20
Output
1 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
4000Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
Crydom D2490-10, Solid State Relay, Single Phase 3-32VDC Control, 90A, 24-280VAC Load, Random Cross
Features
• Ratings from 25A to 125 Amp @ 24-280 VAC
• SCR output for heavy industrial loads
• Zero voltage or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• AC & DC control types
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
Spec
Crydom Part Number
D2490-10
Switching Type
Random Crossing
ROHS
Yes (Details)
Control Voltage
3-32VDC
Load Current
90 Amp (rms)
Surge Capability
1145 Amp (peak)
Special Feature
None
Mounting Style
Panel Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Please note Changes from Gen 3 to Gen 4 (current) package design here
Alternatives
See D2450-10 or D2475-10 which are stocked items
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics SCT-Y24-5A/100mA, 5A/100mA Measurement, Class 1 Split Core CT's, Easy Click HY2.0 Connector for CRJ-31 RJ45 Splitter
Features
Quick Release Split Core System
Cable Mount
100mA Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads with HY-2.0 Connector
Applications
Eastron Modular Metering Equipment
Energy Monitoring
Load Balancing
Power Quality Measurements
Specification
Fastron Part Number
SCT-Y24-5A/100mA
Technology
Split Core AC Current Transformer
Ratio
5/100mA
Aperture Size
ø 24 mm
VA Rating
1VA
Accuracy Class
Class 1
Output
100mA (+20%)
Isolation
3kV (AC, 10Hz, 1 min)
Bandwidth
10-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
5Amp x 1.2
Termination Style
0.9M Flying leads with HY-2.0 Connector
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
CRJ-31 Connector User Guide
Fastron TC5-W-W-2-T/R-2 PID Controller, 100-240VAC with 2 3 Amp Relay Alarms, K,E,J Thermocouple, Pt100 or Cu20, Optional Linear Current/Voltage, 96x48mm,Relay + 12VDC Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Now available will full Multirange input (K,E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x48mm,4-20mA Output)
Specification
Fastron Part Number
TC5-W-W-2-T/R-2
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)/12VDC @ 20mA
Input
Multirange Type,K,E,J,Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
2 3 Amp Relay Alarms standard (Excludes 96x48mm with SSR/Relay output)
Mounting Style
96x48mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Safety
CE
Factory Pack Qty
10
Datasheet
TC5 Datasheet and User Manual
Gigavac GXL14C1AB, Latching Contactor SPST-NO, 350+ AMP, 12-800VDC, 24VDC Coil, 38cm Flying leads, SPST-NO Auxiliary Contact, IP67, IP69K, High Side Drive Version
Features
Hermetically Sealed (Patented) rated to 175 Deg C
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 & IP69K
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
PWM option provides additional drive control flexibility
Built in Coils suppression for all DC Coils
Flexible package for installation
Chassi level power terminals
Salt Fog MIL-STD-810
Specification
Gigavac Part Number
GXL14C1AB
Main Contact Type
SPST-NO
Auxiliary Contact Type
SPST-NO
Coil Voltage
24VDC (Low Side Drive, refer datasheet)
Load Current
350+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.2kV rms
Control Input Terminals
38cm Flying Leads
Aux Contact Terminals
38cm Flying Leads
Special Feature
Hermetically Seal rated to 175 Deg C, High Side Drive Version
Mounting Style
Panel Mount (M5)
Load Voltage Range
12-800VDC
Standards
UL1604, IP67, IP69K, SAE J1171, ISO8846
Termination Style
M8
Unit Weight
440g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics SCT-F36-400, 0.333V, 400Amp measurement Split Core CT's Class 1, 35mm Aperture
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F36-400
Technology
Split Core AC Current Transformer
Ratio
400/0.333V
Aperture Size
ø 35 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
400Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
400g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
SDM230-Modbus-MID-V2, DIN Rail Mount kWh Meter, Single Phase, 240VAC aux, Class 1, 100Amp Direct Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms, MID Approved, SAA212516
100 amp Direct Connect
LoRaWaN AS923 communication
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
SAA Approved
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy Class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM230-Modbus-MID-V2
Functions
Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
230V L-N 230V L-N, 100 Amp
Maximum Measurement Range
276 L-N 230V L-N,100 Amp
Nominal Current Input
Direct connect 100 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
36mm x 100mm x 66mm (2 modules wide)
Isolation
4kV
LoRaWaN
LoRaWAN AS923
Weight
250g
Certification
EN 61010-1 Installation Category III, SAA212516
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Modbus Utility
EEM Meter Setting Software Utility
Fastron Electronics SCT-F50-500, 0.333V, 500Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-500
Technology
Split Core AC Current Transformer
Ratio
500/0.333V
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
500Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
500g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
Fastron Electronics SCT-F50-150, 0.333V, 150Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-150
Technology
Split Core AC Current Transformer
Ratio
150/0.333V
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
150Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
150g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
Northern Design Multicube Modular Master Single and 3 Phase Power Meter with RS485
Up to 20 Meters in 1 with additional modules
Minimum 2 x 3 Phase Circuits with measurement module
Master Unit of Modular Multicube System
Optional 12 way pulse/alarm digital output modules
Nominal current up to 0.383V (For 0.333V CT Input) and nominal voltage up to 240V L-N 415V L-L
Graphic Display
Optional RS485 or Ethernet communication up to 19,200 bit/s
True RMS measurement of currents and voltages
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, reactive power, power factor, harmonics, etc.) from the measured signals.
Features :
20 Meters in same space as 4 traditional meters
Expandable to 20 x 3 Phase or 60 x Single Phase Circuits
Accuracy class 1
In Built Logger
Simple Menu
Optional MODBUS RTU RS485 communication up to 19,200 bit/s or Ethernet communication
5 Year Warranty
240V AC power supply
Specification
Northern Design Part Number
Multicube Modular Master with Logger
Functions
kWh Meter, Energy Meter, Power Quality, Network Recorder
Supply Voltage
240VAC < 15VA
Nominal Measurement Range
415V L-L 240V L-N, 0.333V
Maximum Measurement Range
480V L-L 280V L-N, 0.383V
Display
Graphic LCD
Pulse Output
12 (Optional)
Accuracy
Class 1 (kW,kWh) Class 1(Active), Class 2 Reactive
Ethernet
Optional
Logger
Optional
Isolation
2.11kV
RS232/RS485
Modbus RTU RS485 2400-19200 b/s
Weight
900g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
ABS with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
164 x 96mm x 100mm
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product brochure
User manual
Wiring Diagram
Suitable 0.333V CT's
Split Core CT's
Fastron Electronics AMB-DVO(+/-75mV)A-N, 96x48mm DC Ammeter DC Voltmeter +/-75mV Input, 110-240VAC supply, Large 4.1 Digit
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 4.1 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 48mm Panel Space
90mm Depth
CE Approved
Specification
Fastron Electronics Part Number
AMB-DVO(+/-75mV)A-N
Conditioner Output
N/A
Input
+/-75mVDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100 - 240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Display Type
4.1 Digit RED LED
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics AMB-DV4-A-N, 96x48mm DC Voltmeter 0-10V Input, 100-240VAC/DC supply, Large 4.1 Digit
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 4.1 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 48mm Panel Space
90mm Depth
CE Approved
Specification
Fastron Electronics Part Number
AMB-DV4-A-N
Conditioner Output
N/A
Input
0 - 10VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100 - 240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Display Type
4.1 Digit RED LED
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles