VX9-UMNA-A4D2, Temp Controller, 96x96mm, 100-240VAC, Multirange Input, Relay Output, 3 Alarms, 2 x SV Inputs
Multirange Input (Programmable)
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP65 (front panel only)
UL/CE Approved
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant
Specification
Hanyoung Nux Part Number
VX9-UMNA-A4D2
Control Output 1 (Heat)
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Control Output 2 (Cool)
N/A
Input
Multirange Type K/J/E/T/R/B/S/L/N/U/W/PLII/PT100/JPT100/4-20mA/0-20mA/1-5V/0-5V/0-10V/0-50mV/0-100mV. Note for Direct Current Input please use 250 Ohm Resistor in Parallel to the input terminals.
Alarm
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 1
2nd Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 2
3rd & $th Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Mounting Style
96x96mm Panel Mount
Supply Voltage
85 - 265VAC
Termination Style
Screw
Weight
450g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
VX Series Brochure
VX Series Instruction Manual
Free Software
Hanyoung Nux TCS Software
Hanyoung Nux TCS Software User Manual
VX Series SB Driver (Windows 7) Not required for Windows 10 or 11
LEM DVL 750 UI, Digital Voltage Transducer 750V Input, 4-20mA output, +/- 15V…24VDC, 8.5kV Isolation
Features
Bandwidth DC to 14kHz
Multi Range through pin selection
Closed loop transducer using Hall effect
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVL 750 UI
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-15..24 VDC Bipolar, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 750V
Measurement Range
+/- 1125V
Output
4 - 20mA
Isolation
8.5 kV
Bandwidth
DC-14 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
270g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
SDM630MCT-LORAWAN-MID-AS923, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 1, 1/5 Amp CT Connect, w/ 2 x pulse outputs and LoRaWaN AS923 Wireless Comms
1/5 Amp CT Input
LoRaWaN AS923
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
The meter is intended for measuring, and monitoring single-phase or three phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-LORAWAN-MID-AS923
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
1/5 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
Comms
LoRaWaN AS923
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Modbus Utility
EEM Meter Setting Software Utility
TCD-L-3-PT HEATING Temp Controller, 96x96mm 230VAC, C/O Relay output, PT100 RTD Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-L-3-PT
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Pt100 RTD
Control Mode
Time Proportional Control
Control Range
0- 999 Deg C
Mounting Style
96x96mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
Fastron FDV-50-V05-24, DC Voltage Transducer, Din Rail Mount, 0-150VDC, 0-5V output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-50-V05-24
Analogue Output
0-5V
Input
0 - 50VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
VFD38AMS43ANSAA, 3 Phase, Variable Frequency Drive, 18.5kW, 29 Amp (Normal Duty)/31.6 Amp (Heavy Duty), 460VAC L-L, 300x175x192mm
Features
3 Phase VFD/VSD
4-20mA, 0-5V, 0-10V Proportional Input Control
7 x Digital Input
2 x STO Inputs
Fully enclosed IP20 (Optional IP40)
Small frame Size
Applications
Fan Motor Control
Production Lines
Transportation
Controlled Power Applications
Suitable for extreme environments such as mining
Specification
Delta Part Number
VFD38AMS43ANSAA
Rated Operation Temperature
50°C (With Derating)
Configuration
3 Phase AC Drive
Control Voltage
4-20mA, 0-20mA, 0-10V
Digital Inputs
7 x Mix / 2 x STO
Load Current
24.4 Amp(Normal Duty) / 27.4 Amp(Heavy Duty) Per Phase
Control Range
0.1-599 Hz
Dimensions
250x130x185mm
Mounting Style
Panel Mount
Supply Voltage Range
323-528VAC
Soft Start
0-6000s
Termination Style
Screw
Unit Weight
6.5kg
Factory Pack Qty
1
Datasheet
MS300 Brochure
User Manual
Fastron TC5-S-1A-2-T/R-2 PID Controller, 100-240VAC with 2 3 Amp Relay Alarms, K,E,J Thermocouple, Pt100 or Cu20, Optional Linear Current/Voltage, 48x48mm,4-20mA Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Now available will full Multirange input (K,E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x48mm,4-20mA Output)
Specification
Fastron Part Number
TC5-S-1A-2-T/R-2
Control Output
4-20mA
Input
Multirange Type,K,E,J, Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
2 3 Amp Relay Alarms standard (Excludes 48x48mm with SSR/Relay output)
Mounting Style
48 x 48mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Datasheet
TC5 Datasheet and User Manual
Crydom HS211 + MCBC4825CF, Single Phase Proportional Burst Controller with Heatsink, 10 Cycles, 0-10VDC Input, 90-530VAC, 24 Amps
Features
Proportional Phase Control Input
Ratings from 25A to 90 Amp @ 380-530 VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Panel Mount
Din Rail Mount
Spec
Part Number
HS211 + MCBC4825CF
Switching Type
Burst Fire (Zero Crossing)
ROHS/CE/UL
Yes
Control Voltage
0-10V Proportional Input
Load Current
24 Amp (rms) @ 40 Deg C
Surge Capability
239 Amp (peak)
Special Feature
Proportional Controller + SSR
Mounting Style
Din Rail or Panel Mount
Load Voltage Range
380-530VAC
Max Non Repetitive Peak Voltage
600 Vp
Termination Style
Screw Terminals
Dimensions
L:81mm x W:45mm x D:73.4mm
Unit Weight
296g
Factory Pack Qty
20
Datasheet
HS211
MCBC Series
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron GPH10048ZD3, Solid State Contactor SSR, Single Phase 5-24VDC Control, 100Amp 70-480VAC Load, Din Rail Mount
Ratings from 10A to 100 Amp @ 70-480 VAC
Contactor Style for retrofit
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
CE Compliant to EN60950-1
IP20
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Spec
Fastron Part Number
GPH10048ZD3
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
5-24VDC
Load Current (single unit)
92 Amp (rms) @ 20 Deg C Ambient, 68 Amp (rms) @ 40 Deg C Ambient
Surge Capability
1600 Amp (peak)
Special Feature
Contactor Style IP20 Terminals
Mounting Style
DIN Rail Mount
Load Voltage Range
70 - 480VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
500g
Factory Pack Qty
20
Datasheet
Product Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics SCT-F36-250, 0.333V, 250Amp measurement Split Core CT's Class 1, 36mm Aperture
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F36-250
Technology
Split Core AC Current Transformer
Ratio
250/0.333V
Aperture Size
ø 35 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
250Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
400g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
LEM DVL 150 Digital Voltage Transducer, Vpn = 150V, 50mA output, +/-15...24VDC powered, 8.5kV Isolation
Features
Bandwidth DC to 14kHz
Digital Transducer (ASIC based)
Closed loop transducer using Hall effect
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVL 150
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-15..24 VDC Bipolar, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 150V
Measurement Range
+/- 225V
Output
50 mA @Vpn
Isolation
8.5 kV
Bandwidth
DC-14 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
270g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Fastron FRI 8-03/0.5, Under/Over Current Monitoring Relay AC 0.05 - 0.5 A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choise of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 8 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI 8-03/0.5
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
-15 %; ? %
Current Range
0.05 - 0.5 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.