Fastron Electronics FESCT-32-600-0.333V, 600Amp measurement Split Core CT's, w/1M Flying leads, 32x32mm Aperture, 0.333v Class 1 Series Current Transformer
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/2kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FESCT-32-600-0.333V
Technology
Split Core AC Current Transformer
Ratio
600/0.333V
Aperture Size
32 x 32mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333VAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
600Amp x 1.2
Termination Style
1M Twisted Pair 0.34mm^2
Unit Weight
350g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Northern Design Power Rail PR350-M2-C-0.333V, kWh Meter, 3 Phase, DIN Rail, 240VAC aux, Class 1, 0.333V input, w/ pulse output and RS485 Comms, Power quality measurements
0.333V CT Input
Optional RS 485 communication up to 19,200 bit/s
True RMS values of currents and voltages
Power Quality Measurements
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, Hours Run, Peak Demand etc to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Optional MODBUS RS 485 communication up to 19,200 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Northern Design Part Number
Power Rail PR350-M2-C-0.333V
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N, 5 Amp +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 5 Amp +/-15%
Nominal Current Input
0.333 Volt AC
Pulse Output
3 x NO Voltage Free Contacts 100mA @ 100VAC/DC
Tariff Input
N/A (Optional)
Accuracy
Class 1 (I,U,F,PF,) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
106mm x 90mm x 58mm (6 modules wide)
Isolation
3.5kV
RS485
1200-19200 b/s
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 6 Modules
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Product Manual
Product Comms Manual
Option Links
Application Notes
CT Cable Losses
Meter Accuracy at Low Current
Current Input Isolation
Fastron Electronics FRL8-02, Liquid Level Control Relay, 240VAC or 24VAC/DC Aux Supply 16 Amp changeover/SPDT, 1 or 2 Level Control
Level Switch, 110/240VAC or 24VAC/DC Aux Supply 1 x 16 Amp changeover/SPDT (AgNi / Silver Alloy) Relay
Features :
1. one-level switch of conductive liquids ( by connecting H and D)
2. two-level switch of conductive liquids ! One-state device monitors one level, two-state device monitors two levels (switches on one level and switches off on another level)
Choice of function PUMP UP, PUMP DOWN
Adjustable time delay on the output (0.5 - 10 s)
Sensitivity adjustable by a potentiometer (5-100 kÙ)
Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes
Galvanically separated supply voltage UNI 24.. 240 VAC/DC
Output contact 1xchangeover/SPDT 8A/250V AC1
1-module type, mounting onto a DIN rail
Specification
Fastron Part Number
FRL8-02
Voltage Range
110/240VAC or 24VAC/DC
Sensitivity (Input resistance)
5kOhm to 100kOhm
Electrode Voltage
3.5 max
Trip Adjustment
Potentiometer
Settign Accuracy
5 %
Burden
max. 12 VA
Repeatability
1 %
Temperature Drift
0.1%/°C
Peak Overload (10s)
100 Amp
Time delay T1
max. 400 ms
Time delay T2
adjustable 0.1-10 s
Control Type
1 or 2 level
Number of contacts
1 x changeover/ SPDT (AgNi / Silver Alloy)
Rating
1 x 16 A / AC1
Breaking capacity
2500 VA / AC1, 250 W / DC
Inrush current (3s)
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Control Type
1 or 2 Level Control
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage category
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
109 g
Standards
EN 60255-6, EN 61010-1
Datasheet
Product Datasheet
Sensors for use with
PLT Series Tank Level Sensors
Fastron FRT8-D/W240, Delay Off Timer without Supply Voltage 12-240 V AC/DC, 0.1s - 10 Min, 1 x SPDT 16 Amp
Features :
Multi-range (0.1s - 10min)
Multi-voltage 12 →240 V AC/DC
LED status indicator
Possibility of external load connection in parallel to the control input
Dely Off Energisation
No trigger voltage required
Specification
Fastron Part Number
FRT8-D/W240
Function
Delay TImer Without Supply Voltage
Nominal Voltage
12 → 240 V AC/DC
Digital Output
2 x C/O (SPDT) (Changeover -Single Pole), 250VAC/DC @ 16 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Selectable 1s - 10 Days
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Isolation
4kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
Screw
Weight
80g
Factory Pack Qty
1
Certification
CE, RoHS
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
MS Power MSD83N16MB Series Stud Mount Rectifier Diode
Features
Full blocking capability over wide temperature range
Hermetic metal case with glass insulator
Threaded stud
Applications
Power Supplies
Uncontrolled Rectifiers
Oil Cooled Circuits
Battery Chargers
Specification
MS Power Part Number
MSD83N16MB
Vrrm
1600V
Diode Configuration
Cathode Stud
IF(av) @ 140 Deg C
85 Amp
Itsm
1.15 kA
VF(to)
0.85V
Tj(max)
180°C
rF
3mΩ
Termination Style (Tail)
8.2mm Round Lug
Termination Style (Stud)
M8 x 1
Tail Length to Stud
158mm
R th(j-c)
0.55°C/W
R th(c-h)
0.20°C/W
Weight
40g
Mounting Torque
4 Nm
Factory Pack Qty
10
Country Of Origin
China
MS Power Headquarters
Germany
Datasheet
Product Datasheet
MS Power MSD83R16MB Series Stud Mount Rectifier Diode
Features
Full blocking capability over wide temperature range
Hermetic metal case with glass insulator
Threaded stud
Applications
Power Supplies
Uncontrolled Rectifiers
Oil Cooled Circuits
Battery Chargers
Specification
MS Power Part Number
MSD83R16MB
Vrrm
1600V
Diode Configuration
Anode Stud
IF(av) @ 140 Deg C
85 Amp
Itsm
1.15 kA
VF(to)
0.85V
Tj(max)
180°C
rF
3mΩ
Termination Style (Tail)
8.2mm Round Lug
Termination Style (Stud)
M8 x 1
Tail Length to Stud
158mm
R th(j-c)
0.55°C/W
R th(c-h)
0.20°C/W
Weight
40g
Mounting Torque
4 Nm
Factory Pack Qty
10
Country Of Origin
China
MS Power Headquarters
Germany
Datasheet
Product Datasheet
Gigavac Contactor HX21CAB, Contactor SPST-NO 350 AMP, 1500VDC, 24VDC Coil, 38cm Flying leads, with SPST-NO Auxiliary Contact Continuous Duty, IP67, IP69
Features
Hermetically Sealed (Patented)
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 IP69
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
PWM option provides additional drive control flexibility
Built in Coils suppression for all DC Coils
Flexible package for installation
Integrated safety cover
Specification
Gigavac Part Number
HX21CAB
Main Contact Type
SPST-NO
Auxiliary Contact Type
SPST-NO
Coil Voltage
24VDC
Load Current
350+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
4.3kV rms
Control Input Terminals
38cm Flying Leads
Aux Contact Terminals
38cm Flying Leads
Special Feature
N/A
Mounting Style
Panel Mount (M5)
Load Voltage Range
1500VDC
Standards
UL1604, IP67, IP69
Termination Style
M8
Unit Weight
440g
Factory Pack Qty
1
Datasheet
Product Datasheet
Crydom CWA2450E, Solid State Relay, Single Phase 18-36VAC Control, 50A, 24-280VAC Load
Features
Ratings from 25A to 125 Amp @ 24-280VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
CWA2450E,
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
18-36VAC
Load Current
50 Amp (rms)
Surge Capability
850 Amp (peak)
Special Feature
LED Status Indicator, High Surge, Internal Over Voltage Protection
Mounting Style
Panel Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
See CWU4850 for stocked equivalent (no overvoltage protection).
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies