VX4-UCMA-A2D2, Temp Controller, 48x48mm, 100-240VAC, Multirange Input, 4-20mA Output, Relay Cooling Output, 2 x SV Input, 2 Alarms
Multirange Input (Programmable)
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
UL/CE Approved
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant
Specification
Hanyoung Nux Part Number
VX4-UCMA-A2D2
Control Output 1 (Heat)
4-20mA
Control Output 2 (Cool)
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Multirange Type K/J/E/T/R/B/S/L/N/U/W/PLII/PT100/JPT100/4-20mA/0-20mA/1-5V/0-5V/0-10V/0-50mV/0-100mV. Note for Direct Current Input please use 250 Ohm Resistor in Parallel to the input terminals.
Alarm
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 1
2nd Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 2
2 x SV Inputs (Setpoint)
Mounting Style
48 x 48mm Panel Mount
Supply Voltage
85Â - 265VAC
Termination Style
Screw
Weight
350g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Â
Datasheet
VX Series Brochure
VX Series Instruction Manual
Free Software
Hanyoung Nux TCS Software
Hanyoung Nux TCS Software User Manual
VX Series SB Driver (Windows 7) Not required for Windows 10 or 11
Â
Fastron FDV-50-420-24, DC Voltage Transducer, Din Rail Mount, 0-50VDC, 4-20mA output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-50-420-24
Analogue Output
4-20mA
Input
0 - 50VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Â
VX2-USND-A2CH1, Temp Controller, 48x96mm, 24VDC, Multirange Input, SSR Output, 2 Alarms
Multirange Input (Programmable)
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP65 (front panel only)
UL/CE Approved
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant
Specification
Hanyoung Nux Part Number
VX2-USND-A2CH1
Control Output 1 (Heat)
SSR 12-15VDC @30mA
Control Output 2 (Cool)
N/A
Input
Multirange Type K/J/E/T/R/B/S/L/N/U/W/PLII/PT100/JPT100/4-20mA/0-20mA/1-5V/0-5V/0-10V/0-50mV/0-100mV. Note for Direct Current Input please use 250 Ohm Resistor in Parallel to the input terminals.
Alarm
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 1
2nd Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 2
RS485 Modbus RTU, Current Feedback Input
Mounting Style
48 x 96mm Panel Mount
Supply Voltage
24VDC
Termination Style
Screw
Weight
350g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Â
Datasheet
VX Series Brochure
VX Series Instruction Manual
Free Software
Hanyoung Nux TCS Software
Hanyoung Nux TCS Software User Manual
VX Series SB Driver (Windows 7) Not required for Windows 10 or 11
Â
Fastron Electronics SCT-F24-200-5A, 200/5 Amp Class 1 Series Current Transformer
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F24-200-5A
Technology
Split Core AC Current Transformer
Ratio
200/5 Amp
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
200Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
IMR122, Insulation Monitoring Relay For 0-520VAC 13.5-440Hz System with 2 Outputs (1 C/O + 1NO), Aux Supply Voltage 24-240VAC/DC. L/PE Moitoring, For Earth Resitance Monitoring
Â
Features
Monitors insulation resistance of unearthed IT Systems in compliancewith IEC 61557-8, EN 50155, IEC 61373 and EN 45545 HL-2/3
Measuring input L-PE with line voltages upto 520V AC
Wide auxiliary supply voltage range 24V – 240V AC/DC
Adjustable trip resistance value from 1K to 100Kohm
2 Relay outputs (1C/O + 1NO) for fail safe and non fail safe operation
Test / Reset function with Manual and remote facility
Configurable Auto / Manual Reset
LED indication for insulation fault , Power and Relay output
DIN Rail / Base Mounting
EC Compliant
Can Replace:
-CM-IWS.2S(ABB)
-CM-IWS.1S(ABB)
-3UG4581-1AW31(Siemens)
-IL5880 (DOLD)
-RI-22 (Contrel)
-IR140Y-4 (Bender)
-IR470LY-40 (Bender)
Â
Specification
GIC Controls Part Number
IMA122
Control Output
2 Relay outputs (1C/O + 1NO) for fail safe and non fail safe operation . (NO 5 Amp, NC 3 Amp)
Adjustable Trip Range
1K to 100Kohm
Input
External PT100 Sensor (not supplied)
Mounting Style
17.5 x 75mm Din Rail Mount
Supply Voltage
24 - 240VAC/DC
Termination Style
Screw
Weight
230g
Factory Pack Qty
1
ROHS
Yes
Standards
IEC 61000, EN50121, EN50155, EN55011, IEC60255-27, EN 45545-2,HL-2/3, IEC 60255-27, IEC 60068, UL508 See datasheet for full revision details
CE
Yes
Â
Datasheet
Datasheet
Fastron Electronics SCT-F24-300-5A, 300/5 Amp Class 1 Series Current Transformer
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F24-300-5A
Technology
Split Core AC Current Transformer
Ratio
300/5 Amp
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
300Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Rishabh Rish Con P 4WUB 100-500V 1/5A 60-300U 10 D, Active Power/Reactive Power/Apparrent Power/Phase Angle/Power Factor Transducer 4 wire, 100-500V, 5Amp measurement,60-300VAC/DC Supply, 1 x 0-20mA/4-20mA/0-10V output, with display
Measures Active Power/Phase Angle/Power Factor
Measures Apparent/Reactive/Active Power
Digital output setting 0-20mA/4-20mA/0-10V
Dual output version available
300mS response time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 43.75 x 100.9 mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish P 4WUB 100-500V 1/5A 60-300U 10 D
Functions
Power/Phase Angle/Power Factor Transducer 4 wire
Measurement Output
4-20mA/0-20mA/0-10V User Selectable
Input
57 - 500VAC 50/60Hz
Overload (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-40 - 70°C
Supply Voltage
60 - 300VAC, or 24-60VAC/DC
Accuracy
0.2%
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Technical Support
Rish Con P setup procedure blog
Â
Â
Crydom HD4875G, Solid State Relay, Single Phase 3-32VDC Control, 75A, 48-530VAC Load, w/status LED
Features
Ratings from 25A to 125 Amp @ 48-480VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
HD4875G
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
4-32VDC
Load Current
75 Amp (rms)
Surge Capability
954 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Panel Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Â
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
See HD4875 for stocked equivalent (no LED).
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Tocos RV24YN20S-B103 + GSBKA03-60, Single Turn Potentiometer (Standard) Linear 10K Ohm Panel Mount, Includes Platic Knob and Panel Position Indicator
Features
Panel Mount
Brush Type
Single Turn 270°
10Kohm
Linear
Datasheet
Product Datasheet
Iskra Doo MT440 SSUDHHHHA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 4 Programmable FAST Analogue Outputs, RS485 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output
4 x Analogue (FAST)
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS485 2400-115200 b/s (RS232 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer