Shinko WCL13A-AA/MM Series Dual Loop Digital Indicating Controllers
Differential control, Tank level control, converter function are standard features
5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
9-step pattern (for SV and time) is a standard feature
UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant (Details)
Note the WCL13A Series Requires Open Ring Lug ask-002-1 or Touch Proof ask-001-1 Terminal base to function.
Specification
Shinko Part Number
WCL13A-AA/MM
Control Output 1
4 - 20mA
Control Output 2
4 - 20mA
Input
Multirange (refer to datasheet)
Option
None
Mounting Style
Din Rail Mount
Supply Voltage
100 - 240VAC
Termination Style
Screw
Weight
180g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
WCL Series Brochure
WCL 2014 Additions Brochure
WCL Series User Manual
Delivery 2-3 weeks delivery if not in stock
Fastron FRV 8-04/265, 127 to 265VAC L-N Voltage Monitoring Relay, 3 Phase 4 Wire Over/Under Voltage Detection, 1 x CO SPDT 8 Amp Contact, Adjustable Timer Delay, Adjustable Upper and Lower Voltage Limits
FRV 8 Series serves to monitor voltage, phase failure and sequence in switchboards, protection of devices in 3-phase 4 wire mains
Features
Upper and lower level of monitoring voltage
Adjustable time delay eliminates short voltage peaks and failures in the main
Supply is done from monitored voltage
Faulty state is indicated by red LED and by opening of output relay contact
Output contact 1 x Changeover / SPDT 10 A /250 V AC1
In case supply voltage falls below 60 %Un (U lower level) relay off immediately opens without delay
FRV8-04/460 - supply from all phases which means that relay is functional also in case when one phase is faulty
Variant FRV 8-04/265 - supply L1-N, means that relay monitors also failure of neutral wire
1-MODULE, DIN rail mounting
Specification
Technical Data
FRV 8
Supply and measuring
L1, L2, L3 (127,132,138,220,230,240,254,265VAC)
Supply terminals
L1, L2, L3
Supply/measured voltage
3 x 127-265 V (L-N) / 50 Hz
Level Umax
105 - 125 % Un
Level Umin
75 - 95 % Un
Burden
max. 2 VA
Hysteresis
2 %
Max. permanent overload
AC 3 x 265 V
Peak overload <1ms
AC 3 x 265 V
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
Number of contacts
1 x changeover/ SPDT (AgNi / Silver Alloy)
Rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE, CE
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
Application Notes
Relay in 3-phase main monitors size of phase voltage. It is possible to set two independent voltage levels and thus it is possible to set two independent voltage levels and monitor e.g. undervoltage and overvoltage independently. In normal state when voltage is within set levels, output relay is closed and red LED shines.
In case voltage exceeds or falls below the set levels, output relay opens and red LED shines ( LED indicates faulty state – flashes when timing). In case supply voltage falls below 60 % Un (UOFF lower level)relay immediately opens without delay and faulty state is indicated by red LED.In case timing is in progress and faulty state is indicated, timing is immediately stopped.
Fastron FCP-L-V-1-G-2, PID Pattern Controller, 96x96mm, 100-240VAC, 4-20mA output, 1 Alarm, 8 steps (segments), 4 patterns (programs), Interlinkable
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
4 x 8-step patterns is a standard feature
CE Approved
Each unit needs just 60 mm depth panel space
EC Compliant (Details)
Specification
Fastron Part Number
FCP-L-V-1-G-2
Control Output
12VDC SSR , 4 Program 8 steps, Interlinkable.
Input
Multirange (refer to datasheet)
Option 1
1 Alarm
Option 2
N/A
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
100-240VAC
Termination Style
Screw
Weight
250g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
FC-P Datasheet
Shinko JCL33AS/M-DR Series Digital Indicating Controllers
• Program control, converter function are standard features
• 5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
• Drip-proof / Dust-proof IP66 (front panel only)
• 9-step pattern (for SV and time) is a standard feature
• UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
• Each unit needs just 24 x 48mm panel space
• EC Compliant (Details)
Specification
Shinko Part Number
JCL33AS/M-DR
Control Output
SSR Drive 12VDC +/-15% @ 40mA
Input
Multirange (refer to datasheet)
Alarm
1 x Open Collector(100mA)(EV2)
Option
Relay Cooling Output (EV1)
Mounting Style
24 x 48mm Panel Mount
Supply Voltage
100 - 240VAC
Termination Style
Screw
Weight
120g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
Download Datasheet
Download Manual
Delivery in 2-3 weeks if not in stock.
Fastron FRV 8-02/AD240, 50 to 270VAC Voltage Monitoring Relay, Single Phase Over/Under Voltage Detection, 1 x CO SPDT 10 Amp Contact, Adjustable Timer Delay, Adjustable Upper and Lower Voltage Limits
FRV 8 Series serves to monitor under/over voltage in switchboards, protection of devices in single phase 2 wire mains
Features
Upper and lower level of monitoring voltage
Adjustable time delay eliminates short voltage peaks and failures in the main
Supply is done from monitored voltage
Faulty state is indicated by red LED and by opening of output relay contact
Output contact 1 x Changeover / SPDT 10 A /250 V AC1
In case supply voltage falls below 60 %Un (U lower level) relay off immediately opens without delay
1-MODULE, DIN rail mounting
Specification
Technical Data
FRV 8-02
Supply and measuring
50-270VAC
Measured voltage
65-260VAC / 50 Hz
Level Umax
112.5 % Un
Level Umin
83 % Un
Burden
max. 2 VA
Hysteresis
2 %
Max. permanent overload
270 VAC/DC
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
Number of contacts
1 x changeover/ SPDT (AgNi / Silver Alloy)
Rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE, CE
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
Application Notes
Relay in 3-phase main monitors size of phase voltage. It is possible to set two independent voltage levels and thus it is possible to set two independent voltage levels and monitor e.g. undervoltage and overvoltage independently. In normal state when voltage is within set levels, output relay is closed and red LED shines.
In case voltage exceeds or falls below the set levels, output relay opens and red LED shines ( LED indicates faulty state – flashes when timing). In case supply voltage falls below 60 % Un (UOFF lower level)relay immediately opens without delay and faulty state is indicated by red LED.In case timing is in progress and faulty state is indicated, timing is immediately stopped.
TCR-L-1-K HEATING Temperature Controller, Analogue Dial, 96x96mm, 230VAC, C/O Relay output, Type K Input, 0-400 Deg C
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional COOLING or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCR-L-1-K
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Type K Thermocouple (0-400 Deg C)
Control Mode
Heating ON/OFF Control
Mounting Style
96x96mm Panel Mount
Control Range
0-400 Deg C
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCR Datasheet and User Manual
Fastron FCP-L-R-1-G-2, PID Pattern Controller, 96x96mm, 100-240VAC, Relay output 1 Alarm, 8 steps (segments), 4 patterns (programs), Interlinkable
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
4 x 8-step patterns is a standard feature
CE Approved
Each unit needs just 60 mm depth panel space
EC Compliant (Details)
Specification
Fastron Part Number
FCP-L-R-1-G-2
Control Output
Relay, 4 Program 8 steps, Interlinkable.
Input
Multirange (refer to datasheet)
Option 1
1 Alarm
Option 2
N/A
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
100-240VAC
Termination Style
Screw
Weight
250g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
FC-P Datasheet
RCT-1200 Single Phase Flexible Current Sensor System:
The RCS-1200 Single Phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCT-1200-3000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
3000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Advanced Energy Thyro-A-1A-500-60-H-RL3, Thyro-A-1A-Series Single Phase SCR Controller 60Amp 500VAC Phase(VAR), Burst(TAKT), Quick TAKT(QTM), VT(on Request), SWITCH Operating Modes
Features
Optional Profinet,Profibus,Ethernet,Modbus Comms
500VAC +10/-57% Voltage, Current or Power Control
Built in Fuse
Smallest footprint on the market
Single Phase Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
Quick TAKT Mode (QTM), VT Mode (on request)
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
Potentiometer Adjustment
USB Configuration/Bias Setting
Synchronisation Function (dASM Module Recommended)
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
AC Soft Starter (Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-1A-500-60-H-RL3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Single Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
500VAC +10/-15% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 30kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
RCT-1200 Single Phase Flexible Current Sensor System:
The RCS-1200 Single Phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCT-1200-1000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
1000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Iskra Doo MT440-SSUDAAMAA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 3 Programmable Analogue Outputs, 1 relay output, RS485 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUSAAMAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
1 x Relay Output
Tariff Input
N/A
Output
3 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS485 2400-115200 b/s (RS232 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Protec T1-1100PV-3+0-R, 1100VDC Surge Protection Device for Photovoltaic Systems, Type 1, Type 2/Open Type 1 SPD Listed, with Remote Contact
Specifications
Raycap part number
Protec T1-1100PV-3+0-R
Nominal Voltage
1100VDC
No of Poles
3
Category IEC / EN / VDE
Type 1, Type 2/Open Type 1 SPD Listed
Location of use
String Box, Inverter
Protection modes
(+)-PE,(-)-PE,(+)-(-) PE
Additional Remote Contacts
YES
Protective element
MOV + GDT
No Fault/Fault Indication
Green Flag / Not Green Flag
Surge discharge rating
Per pole 12.5kA (10/350uS), 60kA(8/20uS)
Internal protection and safety
Thermal disconnector in each MOV
Standards
IEC/EN 61643-11
Datasheet
Product Datasheet
GDT/MOV/TVS Tester
SPD Tester