Fastron FDV-25-V05-24, DC Voltage Transducer, Din Rail Mount, 0-25VDC, 0-5V output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-25-V5-24
Analogue Output
0-5V
Input
0 - 25VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Current Transducer, AT-MVO(0-25)-D-3, AC Voltage Transducer, True RMS, 0-25VAC, 22-60VAC/DC Aux, 0-5V output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type)
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
AT-MVO(0-25)-D-3
Control Output
0-5VDC True RMS
Input
0-25V Rms
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
22 - 60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics GT-LL2-D-4, Signal Transmitter/Conditioner, Load Cell, 2mV/V EX.5V input, 0-10V output, 22-60VAC/DC supply
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GT-LL2-D-4
Control Output
0-10V
Input
2mV/V EX.5V
Over Range
N/A
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
LEM AI-PMUL Universal Integrator for Rogowski Coils, Multi Range Input (100 to 5000 Amp) and Output (0.333V,0.225), and True RMS outputs (4-20mA,0-20mA,0-5V,0-10V), Adjustable Sensitivity(22.5,70,80,85,100,120mV/kA), Din Rail Mount
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both True RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation. optional
Input signal
Accuracy Class 0.5 (IEC 61869-2) [1].
Linearity error ? 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature ?25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 0.5 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross power plugin connector: side contacts to stack up to 3 Integrator modules and use only one power supply.
24VDC Power Supply Meanwell HDR-15-24
Specification
LEM Part Number
AI-PMUL
Function
Integrator and True RMS Conditioner for Rogowski Coils
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
0.5% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm
Mounting
Din Rail Mount
Integrator to Meter cable
User Supplied Shielded cable 6mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
Product Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ? 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ? 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
FastronFKPC-200-400 Rev 2, Single Phase Voltage Control SCR Trigger Module, 4-20mA,0-10V,0-5V,5K POT Input, 200-450VAC, 240VAC Aux Supply, Can Replace Semikron Semi-PCM 2 SKPC200-240, CE Approved, Previously FKPC-240-CE Rev 2
Rev 2: Supports Inputs: 4-20mA,0-10V, 0-5V or 10K POT Proportional Phase Control Input
Suitable for SCR Blocks up to 3000 Amp
Instantaneous turn-on output
CE Approval (Pending)
Can Replace Semikron Semi-PCM 2 SKPC200 for most applications. Please take care to connect 240VAC Aux Supply Seperately and connect the gate leads to cathode rather than anode
Specification
Fastron part Number
FKPC200-400 Rev 2 (Previously FKPC-240-CE Rev 2) (Possible Replacement to SKPC200-240)
Switching Type
Phase Angle (Random Crossing)
Control Voltage
4-20mA,0-10V,0-5V,10K POT Proportional Input (Note the zero value is 0.20.3V to avoid noise to cause gate firing
Load Current
Based on SCR Stack
Special Feature
Single Phase Proportional Controller/Trigger
Mounting Style
Panel Mount
Load Voltage Range
200-450VAC +10%
Auxiliary Power Supply
200-450VAC +10%
Termination Style
Barrier Strip Screw
Dimensions
105 x 90 x 40mm
Certifications EMC
EN 61000-6-3:2007+A1:2011, EN IEC 61000-3-2:2019+A1:2021, EN 61000-3-3:2013+A1:2019, EN IEC 61000-6-1:2019
Certifications LVD
Low Voltage Directive 2014/35/EU, EN IEC 60947-1:2021
Unit Weight
400g
Factory Pack Qty
20
Datasheet and User Manual
User Manual
FKPC wiring Half Controlled M505012F Crydom Bridge for up to 240VAC - 400VAC Load
FKPC wiring Half Controlled SKCH28/16 Bridge for up to 240VAC - 400VAC Load
FKPC AC Switch Wiring
Northern Design XD-V5-3, AC Current Transducer, Average RMS, Ipn = Selectable 50,100,150,200,300 Amp, 0-5V output, Self Powered
Features
Ipn = Selectable 50,100,150,200,300 Amp
Average RMS Output
0-5V Output
Din Rail Mounting
Self Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ⌀ 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Earth Leakage Measurement
Motor Control
Actuators
Lamp Failure
Specification
Northern Design Part Number
XD-V5-2
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
Self Powered
Load Current (RMS)
Selectable 15,30,45,60,75,100 Amp
Output
0-5V Average RMS
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
55 - 65Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
Class 1
Termination Style
Screw
Unit Weight
180g
Factory Pack Qty
6
Datasheet
Product Brochure
Product Manual
Fastron F312 Series Proportional Phase Control Solid State Relay Controller
Proportional Phase Controller for SSR switching
Ratings from 25A to 90 Amp @ 90-600 VAC
Use any DC Control Solid State Relay
Use any Solid State Contactor
Instantaneous turn-on outputs
Specification
Fastron Part Number
F312 Series
Switching Type
Phase Angle or Burst (Selectable)
ROHS/CE/UL
Yes
Control Voltage
0 - 10V/0 - 5V/4 - 20mA/POT Input (at time of order)
Load Current
N/A based on SSR
Surge Capability
N/A based on SSR
Special Feature
Proportional Controller for SSR
Mounting Style
DIN Rail Mount
Load Voltage Range
90-415VAC
Dielectric Strength
4kV
Termination Style
Screw Terminal
Unit Weight
360g
Factory Pack Qty
20
Datasheet
Product Datasheet
F312 User Manual
Product Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent Parts
Contact Us for Possible Replacement
LEM ART-B22-D300-SP4 + AI-PMUL, Single Phase Rogowski Coil Set, Class 1, User Selectable 0.333v, 0.166v, True RMS 4-20mA, 0-20mA, 0-10V, 0-5V Outputs, Sensitivity, and Measurement Range, 30cm Diameter
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D300-SP4 + AI-PMUL
Function
Single Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 30cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
4.5M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
LEM ART-B22-D70-SP3 + AI-PMUL Single Phase Rogowski Coil Set, Class 1, User Selectable 0.333v, 0.166v, True RMS 4-20mA, 0-20mA, 0-10V, 0-5V Outputs, Sensitivity, and Measurement Range, 7cm Diameter
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Included Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D70-SP3 + AI-PMUL
Function
Single Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 7cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Applicaton Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Crydom PMP2490WP, Phase/Burst control, 240VAC, 90 Amp, Selectable 0-5V,0-10V,4-20mA input, w/Overvoltage Protection
Features
Selectable Proportional Phase or Burst Control Input
Ratings from 25A to 90 Amp @ 170-600 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
PMP2490WP
Switching Type
Phase Angle or Burst (Selectable)
ROHS/CE/UL
Yes
Control Voltage
0 - 10V/0 - 5V/4 - 20mA Proportional Input (Selectable)
Note Requires DC Power Supply for 0-5V/0-10V input modes
Load Current
90 Amp (rms)
Surge Capability
1290Amp (peak)
Special Feature
Proportional Controller + SSR
Mounting Style
Panel Mount
Load Voltage Range
170-280VAC
Dielectric Strength
4kV
Termination Style
Terminal Plug
Unit Weight
160g
Factory Pack Qty
20
Datasheet
Product Datasheet
PMP24 Installation/Wiring Guide
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
FTY220D80P
Contact Us for Possible Replacement
PMP24 Installation/Wiring Guide
Heatsink
SSR and Heatsink Assemblies
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Fastron FDV-15-420-24, Battery DC Voltage Transducer, Din Rail Mount, 0-15VDC, 4-20mA output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-15-420-24
Analogue Output
4-20mA
Input
0-15VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
LEM ART-B22-D300-SP4 + AI-PMUL - 3 Pcs, 3 Phase Rogowski Coils & Universal Multi Range Integrator with Signal Conditioner
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D300-SP4 + AI-PMUL - 3 Pcs
Function
3 Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 30cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
4.5M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.