Crydom HS501DR + A2450G, Panel or Din Rail Mount Solid State Relay 90-280VAC Control Input, LED Status, 24-280VAC Output, 10 Amps
Features
Ratings from 25A to 125 Amp @24-280 VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Part Number
HS501DR + A2450G
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
90-280VAC
Load Current
10 Amp (rms) @ 40 Deg C
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Din Rail or Panel Mount
Load Voltage Range
24-280VAC
Max Non Repetitive Peak Voltage
600 Vp
Termination Style
Screw Terminals
Dimensions
L:79.9mm x W:45mm x D:40.3mm
Unit Weight
296g
Factory Pack Qty
20
Datasheet
HS501DR
A2450-G
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Shinko JCL33AS/M-DR Series Digital Indicating Controllers
• Program control, converter function are standard features
• 5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
• Drip-proof / Dust-proof IP66 (front panel only)
• 9-step pattern (for SV and time) is a standard feature
• UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
• Each unit needs just 24 x 48mm panel space
• EC Compliant (Details)
Specification
Shinko Part Number
JCL33AS/M-DR
Control Output
SSR Drive 12VDC +/-15% @ 40mA
Input
Multirange (refer to datasheet)
Alarm
1 x Open Collector(100mA)(EV2)
Option
Relay Cooling Output (EV1)
Mounting Style
24 x 48mm Panel Mount
Supply Voltage
100 - 240VAC
Termination Style
Screw
Weight
120g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
Download Datasheet
Download Manual
Delivery in 2-3 weeks if not in stock.
Shinko BCD2S1000 Series Digital Indicating Controllers
• Program control, converter function are standard features
• 5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
• Drip-proof / Dust-proof IP66 (front panel only)
• 9-step pattern (for SV and time) is a standard feature
• UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
• Each unit needs just 60 mm depth panel space
• EC Compliant (Details)
Specification
Shinko Part Number
BCD2S1000
Control Output
SSR 12VDC +/-15%, 40mA (short circuit protected)
Input
Multirange (refer to datasheet)
Option 1
2nd Alarm, 4-20mA Cooling Output
Option 2
None
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
24VAC/DC
Termination Style
Screw
Weight
170g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
BC Series Brochure
BC Series User Manual
BC Series RS485 Comms Manual
Shinko Product Guide
Fine Tuning Adjustments
Premium Quality TC Cable 500M Teflon - Type R Thermocouple Cable 500 Meter Twisted and Screened 7/0.2mm, ANSI Standard
Features
CE, ANSI, ROHS Approved
Colour Codes
Datasheet
Thermocouple Cable Brochure
Varsi-Raycap V420E40, 420VAC, 560VDC, E40 Package, 930W Metal Oxide Varistor (MOV), Equivalent to Epcos SIOV-B40K420 Features
Features
High Energy Absorption Rating
Industry Standard Package
Wide Operating Range 35 - 1100VAC
High Peak Current Capability (70kA)
UL/CSA/ROHS/ISO9001:2015 Approved
Panel Mount
Screw Terminals
APPLICATION AREAS:
1. Railways and trams: For the protection of electrical equipment, power electronics (IGBT, thyristors...) in systems with alternating, direct or combined AC + DC power supply, especially in power supply of AC/DC, DC/AC, DC/DC converters. They may be used in systems with main and auxiliary power supply for example: automatic control and regulation systems, cooling systems, warming systems, ventilation systems, and combination systems (electromechanical, electropneumatic and other systems).
2. Wind powerplants For protection of automatic control and regulation in power electronics (IGTB, tyristors...), as well as the protection of sensitive electronic systems (e. g. AC/DC, DC/AC, DC/DC converters, drive systems) from direct or indirect lightning strikes.
3. Photovoltaic systems For protection of photopanels, automatic control electronics with sensitive electronic components, and DC/AC converters (inverters) from direct or indirect lightning strikes. Depending on the application, both serial and parallel connections are possible. With serial connection the required voltage is achieved. With parallel connection higher current absorption is achieved in the modules.
Specification
Varsi-Raycap Part Number
V420E40
Operating Voltage AC (50-60Hz)
420V
Operating Voltage DC
505V
Average Power Dissipation
1.4W
Permissable Peak Current
40kA
Energy Absorption(2ms)
930W(max)
Tolerance(Vn)
+/- 10%
Termination Style
Screw
Weight
65g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CSA
Yes
Datasheet
Product Datasheet
Application Notes
Technical Blog MOV Article
GDT/MOV/TVS Tester
SPD Tester
Gigavac P115CDA, MiniTactor Contactor, 1000VDC, 50A @ 25°C, 25A @ 85°C, SPST-NO, 24VDC Coil Contactor
Features
Hermetically Sealed (Patented) rated to 175 Deg C
High Efficiency Dual DC Coils - 12,24,48VDC options
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Small and lightweight
Flexible package for installation
Specification
Gigavac Part Number
P115CDA
Main Contact Type
SPST-NO
Auxiliary Contact Type
N/A
Coil Voltage
24VDC
Load Current
50A @ 25°C, 25A @ 85°C
Mechanical Life @ 0 Amp
100,000 Operations
Impulse Withstand
6kV rms
Control Input Terminals
M3 Screw
Special Feature
N/A
Mounting Style
Panel Mount (M4)
Load Voltage Range
1500VDC
Standards
UL508, NEC 690.11 and 690.12 DC
Termination Style
M4 Screw
Unit Weight
135g
Factory Pack Qty
1
Datasheet
Product Datasheet
Infineon TT250N12KOF-K Dual Thyristor Module
Features
Thyristor for line frequency
Pressure Contact Technology
Electrically insulated base plate
Industrial standard package
Long-term stability
3600V Isolation
50mm Base Width
Applications
Power Converter
Line rectifying 50/60 Hz
Deep Cycle Applications
Controlled Rectifiers
Softstart AC motor control
AC power control
Lighting and temperature control
Specification
Infineon Part Number
TT250N16KOF-K
Vrrm
1600V
Diode Configuration
Common Cathode Dual Thyristor Module
IF(av) @ 85 Deg C
250 Amp
Package Size
W:50mm L:115mm D:52mm
Itsm
9.1 kA
VF(to)
0.8V
Tj(max)
125°C
rF
0.7mΩ
I(gt) @ 25 Deg C
200mA
Terminals
M8 Screw
Hole Centres
80mm x 38mm(M6)
Gate Terminals
Spade (A 2.8 - 0.8 DIN 46244)
R th(j-c)
0.065°C/W
R th(c-h)
0.04°C/W
Weight
800g
Mounting Torque
5 Nm (12 Nm Terminals)
Factory Pack Qty
8
Certification
UL Listed, ROHS
Infineon Headquarters
Germany
Datasheet
Product Datasheet
Alternatives
Contact Us for Possible Replacement for alternative suggestion
Iskra Doo MT540-HSHFNAAAA, Multifunction Power Transducer, Class 0.5S, 4 Wire, 600V L-N, 5A AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, USB, Ethernet, RS485 Comms
Class 0.5S Active, Class 0.2 Reactive (EN 60688) , Class 0.2 on Comms
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
MT540-HSHFNAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
4 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.5s(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
EU Style Clamp Terminals
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
H37 (Semikron P35) Heatsink Profile 40mm x 250mm, Various Lengths cut to order, Milled or Raw Finish
Note: for Milled finish. we can mill 150mm each pass leaving a line in the centre.
Note: for any lengths not showing in stock, and we have longer lengths in stock, the profile is available in 2-3 days to cut and mill.
Datasheet
Product Datasheet
Fastron Electronics AM5H-A-DV7-A, 96x48mm Digital Voltmeter 0-600VDC with 1 x Relay Alarm, 110/240VAC Aux supply, 5 Digit
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 5 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 96 x 48mm Panel Space
90mm Depth
Specification
Fastron Electronics Part Number
AM5H-A-DV7-A
Alarm Output
1 x Relay, 3 Amp 250VAC
Input
0 - 600VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
110/240VAC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Display Type
5 Digit RED LED
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
User Manual
Application Notes
Panel Meters Blog Articles
Advanced Energy Thyro-A-3A-400-100-H-RLP3, Three Phase SCR Controller 100 Amp 400VAC +10/-57%, Phase(VAR), Burst(TAKT) Fire, SWITCH Operating Modes, Voltage Control, Current Feedback, Power Limit Options
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustments
Synchronisation Function for Multiple TAKT Sync
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (VAR Mode Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-3A-400-100-H-RLP3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Three Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide