RCS-1800-1500-30M Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, 30Meters of Coil Cable, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-1500
Specification
Magnelab Part Number
RCS-1800-1500-30M
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
1500 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1500 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
30M Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Trent NBR Series NBR-FR22GR69V25T + RT18-125L, 25 Amp 690V Semiconductor I²t Fuse & DIN Rail Fuse Holder Cartridge Style
Features
Cylindrical Standard Fuses Sizes
Wide Range of I²t
Ratings up to 125 Amp
Quick Release with RT18-125L fuse holder
DIN Rail Mount with RT18-125L fuse holder
Compatible with all 58 x 21mm fuse holders
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Solid State Relay Switchboards
Bridge rectifier Fusing
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-FR22GR69V25T + RT18-125L
Fuse Type
I²t gR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating (Pre-Arcing)
410 A²/s
Nominal Current (RMS + DC)
25 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
123 x 76 x 37.5mm
Fuse Holder
RT18-125L
Mounting Style
Din Rail Mount
Operating Temperature Range
-40°C / 125°C
Watt Loss
13.8W
DC Breaking Capacity
50kA
Unit Weight
60g
Factory Pack Qty
10
Datasheet
RT18-125L
Datasheet
Iskra Doo RI61J C 6-10kA, 1 Pole DC Miniature Circuit Breaker Disconnect Switch C Curve 6 Amp, 220VDC, 4.5kA
Miniature Circuit Breakers are used for over-current (overload and short-circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
< 50mS Trip Delay Time
1 Pole Disconnect
4.5kA Short Circuit Rating
Suitable for Isolation
Customised versions available
Type B, C, D Curve available
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
Specification
Iskra Doo Part Number
RI61J C6
Functions
1 Pole MCB - C Curve
Nominal Voltage
220VDC
Nominal Current Range
6 Amp RMS
Trip Delay Time
< 50ms
Rated Frequency
50/60 Hz
Operating Temperature
-25 to 55 Deg C
Rated Operations
10,000 Ops
Surge Current
220V
Short Circuit Current
4.5kA
Approvals
VDE, GOST-R
Standards
IEC/EN 60898,60947-1/2, IP20 (IP40 Installed) IEC 61008 ;
Weight
130g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Iskra Doo RI62J C 40-10kA, 2 Pole DC Miniature Circuit Breaker Disconnect Switch C Curve 40 Amp, 440VDC, 10kA
Miniature Circuit Breakers are used for over-current (overload and short-circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
< 50mS Trip Delay Time
1 Pole Disconnect
10kA Short Circuit Rating
Suitable for Isolation
Customised versions available
Type B, C, D Curve available
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
Specification
Iskra Doo Part Number
RI62J C40
Functions
2 Pole MCB - C Curve
Nominal Voltage
440VDC
Nominal Current Range
40 Amp RMS
Trip Delay Time
< 50ms
Rated Frequency
50/60 Hz
Operating Temperature
-25 to 55 Deg C
Rated Operations
10,000 Ops
Surge Current
500V
Short Circuit Current
10kA
Approvals
VDE, GOST-R
Standards
IEC/EN 60898,60947-1/2, IP20 (IP40 Installed) IEC 61008 ;
Weight
200g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Trent NBR-FR22GR69V125T + RT18-125L Series 125 Amp 690V Semiconductor I²t gR Fuse & DIn Rail Fuse Holder Cartridge Style
Features
Cylindrical Standard Fuses Sizes
Wide Range of I²t
Ratings up to 125 Amp
Quick Release with RT18-125L fuse holder
DIN Rail Mount with RT18-125L fuse holder
Compatible with all 58 x 21mm fuse holders
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Solid State Relay Switchboards
Bridge rectifier Fusing
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-FR22GR69V125T + RT18-125L
Fuse Type
I²t gR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating (Pre-Arcing)
8100 A²/s
Nominal Current (RMS + DC)
125 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
123 x 76 x 37.5mm
Fuse Holder
RT18-125L
Mounting Style
Din Rail Mount
Operating Temperature Range
-40°C / 125°C
Watt Loss
22.8W
DC Breaking Capacity
50kA
Unit Weight
60g
Factory Pack Qty
10
Datasheet
RT18-125L
Datasheet
RCS-4800-XXXX Three-Phase Flexible Current Sensor System (Rogowski Coils):
Contact Us for Possible Replacement for specific Ratings
The RCS-4800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-4800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-4800-XXXX
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
500-5000 Amp RMS (please specify with order)
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 5000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
12 Inch
Coil Circumference
36 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
LEM DVC 1000-P, C/L Voltage Transducer, 1000V AC/DC, 5VDC Supply, 2.5Vref Output, PCB Mount
Features
Bandwidth DC to 47kHz
8 Pins
5V Unipolar Supply
Closed loop transducer using Hall Effect
Compact and versatile
PCB Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
AC variable speed drives and servo motor drives
Single and Three Phase Inverters
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVC 1000-P
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
5VDC
Primary Nominal Voltage
+/-1000V AC/DC
Measurement Range
+/-1500V AC/DC
Output
2.5V Vref 1.17V -> 3.83V (0.5 to 4.5V over range) Instantaneous
Isolation
4.2 kV
Bandwidth
DC-47 kHz
Mounting Style
PCB Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Through Hole PCB
Unit Weight
22g
Factory Pack Quantity
25
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
RCS-1805-VAR, 5 Amp Output, Class 1 Three Phase 500/1000/2500/5000\10000\25000\50000 Amp AC Measurement 6 Inch Diameter Rogowski Coils with Integrator Flexible Current Sensor System:
The RCS-1805 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 5 Amp.
A 24VDC Power Supply is included to operate these coils. The RCS-1805 comes with 5 Amp integrator..
Included is an 18 inch circumference rope CT with Integrator, and power supply.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-1805-VAR
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
500/1000/2500/5000\10000\25000\50000 Amp RMS Selectable
Measurement Range
10% - 130% if Ipn
Output Range
0-5Amp
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
24VDC
Accuracy
1% from 25 to 5000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
2200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS-VAR Series Installation Guide