Fastron Electronics FESCT-075-1000-1-IP65, 1000Amp Measurement, 1 Amp Output Split Core CT's, Class 1, 7.5VA, 7.5VA, w/10M Flying leads, ø 55mm Aperture
Features
Quick Release Split Core System
10m Flying Leads
ø 75mm
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurement, 1 Amp Outputs
Specification
Fastron Electronics Part Number
FESCT-075-1000-1-IP65
Technology
Split Core AC Current Transformer
Ratio
1000/5A
Aperture Size
ø 75mm
VA Rating
7.5VA
Accuracy Class
Class 1
Output
1 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Dimensions
180x138x52mm
Mounting Style
Panel Mount
Operating Temperature Range
-35°C / 55°C
Continuous Current (max)
1000Amp x 1.2
Termination Style
10M Twisted Pair 0.34mm^2
Unit Weight
2000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Trent FGM6S-3P-400H 315A, 3 Pole Moulded Case Circuit Breaker (MCCB) Thermal, Adjustable Type 75kA 315 Amp, 400/690VAC
Miniature Circuit Breakers are used for over-current (overload and short-circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
Disconnect
75kA Short Circuit Rating @400VAC
Suitable for Main Incoming Breaker
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
AS/NZ 61009-1
Specification
Trent Part Number
FGM6S-3P-400H 315A
Functions
MCCB
Nominal Voltage
400/690VAC @ 50/60Hz
Nominal Current Range
315 Amps RMS
Trip Delay Time
< 50ms
Rated Impulse Voltage
8kV
Operating Temperature
-25 to 50 Deg C
Mechanical Operations
20,000 Ops
Insulation Voltage
800V
Short Circuit Current
75kA
Approvals
KEMA EUR, CE
Standards
IEC/EN 60898-1,IEC/EN 60947-3, IP20 (IP40 Installed) IEC 61008 ; AS/NZ 61009-1
Weight
5.1g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Trent FGM6DC-3PL-630 630A, 3 Pole DC Moulded Case Circuit Breaker (MCCB) Fixed Type Ics = 25kA, 630 Amp, 1500VDC
Miniature Circuit Breakers are used for over-current (overload and short-circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
3 Pole Disconnect
25kA Short Circuit Rating @1500VDC
Suitable for DC Power Systems Including Solar and Battery
Standards :
IEC/EN 60947-3
IP20 (IP40 Installed) IEC 61008
Specification
Trent Part Number
FGM6DC-3PLC-630 630A
Functions
3 Pole DC MCCB
Nominal Voltage
1500VDC
Nominal Current Range
630 Amps
Trip Delay Time
< 50ms
Rated Impulse Voltage
12kV
Operating Temperature
-35 to 70 Deg C
Electrical Operations
5,000 Ops
Insulation Voltage
1500V
Short Circuit Current Ics=Icu (Ics/Icu)
25kA
Approvals
CE
Standards
GB/T14048.2, IEC/EN 60947-3, IP20 (IP40 Installed)
Weight
8.5kg
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
CE Declaration
Fastron FTPS-3-400-80-010, SCR Phase/Burst Controller for HVAC, 3 Phase, 0-10/0-5/2-10/1-5V Input, with In built Fuses, 64 Amps per Phase @ 50 Deg C
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
Made in China, Low cost
3 Phase, Phase Angle/Burst Controller
4-20mA Input Proportional Control (0-10V/1-5V/5K POT input on request)
Fully enclosed IP20
Phase Angle or Burst switching
Aluminium Frame
Removable Cover
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Specification
Fastron Part Number
FTPS-3-400-80-010
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA default (0-10V/0-5V/5K POT on request)
Load Current
64 Amps Per Phase @ 50 Deg C
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
1 x NO Relay Contact (not available with RS485 Option)
Comms
Optional RS485 Modbus RTU
Special Feature
Internal Fuse
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
230VAC +/-10%
Delay on Start
Programmable from 0 to 10 seconds
Soft Start
Programmable from 0 to 10 seconds
Termination Style
Screw
Unit Weight
4kg (6kg Packed)
Factory Pack Qty
1
Technical Docs
User Manual
Modbus Register Map
Calibration Procedure
Wiring Detail
RCS-3600-5000 0.333V, 3 Phase 5000Amp AC Measurement 12 Inch Rogowski Coils with Integrator, Class 1
The RCS-3600 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-3600 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-3600-5000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
5000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
12 Inch
Coil Circumference
36 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
LEM DVL 750 Digital Voltage Transducer, Vpn = 750V, 50mA output, +/-15...24VDC powered, 8.5kV Isolation
Features
Bandwidth DC to 14kHz
Digital Transducer (ASIC based)
Closed loop transducer using Hall effect
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVL 750
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-15..24 VDC Bipolar, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 750V
Measurement Range
+/- 1125V
Output
50 mA @Vpn
Isolation
8.5 kV
Bandwidth
DC-14 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
270g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
FPT-135 1200/5A 5P20 15VA Protection Class CT, 1200/5A, Class 5P20 15VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 1200/5A 5P20 15VA
Technology
Protection Class Current Transformer
Ratio
1200/5
Aperture Size
81 x 135mm
VA Rating
15VA
Accuracy Class
Class 5P20
Output
5 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
1200Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
3kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
FPT-135 2000/1A 5P20 15VA Protection Class CT, 2000/1A, Class 5P20 15VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
Specification
Fastron Electronics Part Number
FPT-135 2000/1A 5P20 15VA
Technology
Protection Class Current Transformer
Ratio
2000/5
Aperture Size
81 x 135mm
VA Rating
15VA
Accuracy Class
Class 5P20
Output
1 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
2000Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
FPT-135 1000/1A 5P35 5VA Protection Class CT, 1000/1A, Class 5P35 5VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 1000/1A 5P35 5VA
Technology
Protection Class Current Transformer
Ratio
1000/5
Aperture Size
81 x 135mm
VA Rating
5VA
Accuracy Class
Class 5P35
Output
1 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
1000Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
F922 Series AC Average RMS or DC Current Transducer, 9-36VDC Supply, 0-8 Amp, 4 Output types available
Features
Isolated measurement of AC or DC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC or DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F922-X-XX-XX
Functions
Single Phase AC or DC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Iskra Doo MT440-SSUDAAMNA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V L-N, 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, 1 relay output, RS485 & USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAAMNA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
1 x Relay Output
Tariff Input
N/A
Output(s)
2 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer