Crydom D2450-10, Solid State Relay, Single Phase 3-32VDC Control, 50A, 24-280VAC Load, Random Crossing
Features
• Ratings from 25A to 125 Amp @ 24-280 VAC
• SCR output for heavy industrial loads
• Zero voltage or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• AC & DC control types
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
Spec
Crydom Part Number
D2450-10
Switching Type
Random Crossing
ROHS
Yes (Details)
Control Voltage
3-32VDC
Load Current
50 Amp (rms)
Surge Capability
597 Amp (peak)
Special Feature
None
Mounting Style
Panel Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Crydom DRA-CN024D05, Slimline Relay & Socket, 3-12VDC Coil, 3.5 Amp 24VDC Load
Features
Output 3.5 Amp @ 24VDC
3-12VDC Control input
DIN Rail Mount
Ultra slim package
CE Compliant to IEC 60664
IP67
Specification
Crydom Part Number
DRA-CN024D05
Switching Type
250VAC 2 Amp Load SSR
Approvals
UL, CE
ROHS
Yes (Details)
Control Voltage
3-12VDC
Load Current
3.5 Amp (rms)
Special Feature
LED Status Indicator
Mounting Style
Socket Mount (F41F-1Z-C2-5 12-14VAC/DC)
Load Voltage Range
24VDC Load
EMC Compliant
Level 3
Termination Style
PCB or Socket Mount
Unit Weight
6g
Factory Pack Qty
20
Datasheet
Relay Datasheet
Fastron FC5-S-R-1-G-4-C PID Controller, 24VDC with 1 Alarm, RS485, K,E,J,N,T,S,R,B Thermocouple, Pt100 or Cu20, Optional Linear Current/Voltage, 48x48mm,Relay Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
FC5-S-R-2-T/R-2
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Multirange Type,K,E,J,N,T,S,R,B, Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
1 Alarm, RS485 standard (Excludes 48x48mm with SSR/Relay output)
Mounting Style
48 x 48mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Datasheet
Datasheet
User Manual
Modbus Protocol
FC5 Communication Protocol
Fastron Electronics GBMC-5-N2-R2NN, 140x420mm, Pulse Input Counter/Totaliser NPN 12V input 4 Digit, Large Panel Meter, 100-240VAC/DC Supply
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMC-5-N2-R2NN
Conditioner Output
None (optional)
Relay Outputs
2
Input
0-3kHz NPN 12VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
N/A
Zero Adjustment Range
N/A
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics SCT-Y24-50A/100mV, 50A/100mV Measurement, Class 1 Split Core CT's, Easy Click HY2.0 Connector for CRJ-31 RJ45 Splitter
Features
Quick Release Split Core System
Cable Mount
100mV Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads with HY-2.0 Connector
Applications
Eastron Modular Metering Equipment
Energy Monitoring
Load Balancing
Power Quality Measurements
Specification
Fastron Part Number
SCT-Y24-50A/100mV
Technology
Split Core AC Current Transformer
Ratio
50/100mV
Aperture Size
ø 24 mm
VA Rating
1VA
Accuracy Class
Class 1
Output
100mV (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (mVx)
50Amp x 1.2
Termination Style
0.9M Flying leads with HY-2.0 Connector
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
CRJ-31 Connector User Guide
Northern Design Multicube Modular Master Single and 3 Phase Power Meter with RS485
Up to 20 Meters in 1 with additional modules
Minimum 2 x 3 Phase Circuits with measurement module
Master Unit of Modular Multicube System
Optional 12 way pulse/alarm digital output modules
Nominal current up to 0.383V (For 0.333V CT Input) and nominal voltage up to 240V L-N 415V L-L
Graphic Display
Optional RS485 or Ethernet communication up to 19,200 bit/s
True RMS measurement of currents and voltages
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, reactive power, power factor, harmonics, etc.) from the measured signals.
Features :
20 Meters in same space as 4 traditional meters
Expandable to 20 x 3 Phase or 60 x Single Phase Circuits
Accuracy class 1
In Built Logger
Simple Menu
Optional MODBUS RTU RS485 communication up to 19,200 bit/s or Ethernet communication
5 Year Warranty
240V AC power supply
Specification
Northern Design Part Number
Multicube Modular Master with Logger
Functions
kWh Meter, Energy Meter, Power Quality, Network Recorder
Supply Voltage
240VAC < 15VA
Nominal Measurement Range
415V L-L 240V L-N, 0.333V
Maximum Measurement Range
480V L-L 280V L-N, 0.383V
Display
Graphic LCD
Pulse Output
12 (Optional)
Accuracy
Class 1 (kW,kWh) Class 1(Active), Class 2 Reactive
Ethernet
Optional
Logger
Optional
Isolation
2.11kV
RS232/RS485
Modbus RTU RS485 2400-19200 b/s
Weight
900g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
ABS with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
164 x 96mm x 100mm
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product brochure
User manual
Wiring Diagram
Suitable 0.333V CT's
Split Core CT's
Crydom MCBC2425DL, Solid State Relay burst fire Controller, 240VAC, 4-20mA, 20 Cycles
Features
Selectable Proportional Burst Control Input
Ratings from 25A to 90 Amp @ 180-530 VAC
SCR output for heavy industrial loads
Zero voltage turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
MCBC4850DL
Switching Type
Burst Fire (20 Cycles)
ROHS/CE/UL
Yes
Control Voltage
4 - 20mA Proportional Input
Load Current
50 Amp (rms)
Surge Capability
250Amp (peak)
Special Feature
Proportional Controller + SSR
Mounting Style
Panel Mount
Load Voltage Range
180-280VAC
Overvoltage Vpk
600V
Termination Style
Terminal Plug & Screws
Unit Weight
87g
Factory Pack Qty
10
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
Crydom PMP2425W or Contact Us for Possible Replacement
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Eastron SDM630MCT-4L, Quad 3 Phase DIN Rail Mount kWh Meter with Easyclick, 4 x 3 Phase or 12 x Single Phase, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 4 x 3 Phase Connect
100mA RJ12 12 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 2 x three phase or 6 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-4L
Functions
Quad Three Phase Energy Meter/ 12 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
System Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
700g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Fastron FC5-H-W-1-G-4-C, 24VDC PID Controller with 1 Alarm, RS485, E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 48x96mm,Relay + 12VDC Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
FC5-H-W-1-G-4-C
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)/12VDC @ 20mA
Input
Multirange Type,K,E,J, Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
1 Alarm, RS485 standard (Excludes 48x96mm with SSR/Relay output)
Mounting Style
48x96mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Approvals
CE
Datasheet & User Manual
Datasheet
User Manual
FC5 Communication Protocol
Fastron FC5-L-1A-1-G-4-C PID Controller, 24VDC with 1 Alarm, RS485, E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x96mm,4-20mA Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Fastron Part Number
FC5-L-1A-1-G-4-C
Control Output
4-20mA
Input
Multirange Type,K,E,J, Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
1 Alarm, RS485 standard (Excludes 96x96mm with SSR/Relay output)
Mounting Style
96x96mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Datasheet & User Manual
Datasheet
User Manual
FC5 Communication Protocol
Risbabh EM94-Z-V3-M-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-M-D
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.