Iskra Doo MCR 32 UNI, Current Monitoring Relay AC 2-20 Amp, Adjustable Range, Universal 24-240VAC 24VDC Aux Supply, 1 x 8 AMP SPST CO Relay
MCR 32 Series serves to monitor AC currents up to 20 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s. Can replace Crouzet 84871122
Features :
Current transformer is a part of the product. Inside this transformer there is a wire which senses the volume of fl owing current
Non Invasive measurement
Galvanically separates monitored circuit
Universal supply AC 24 - 240 V and DC 24 V Supply is galvanically separated from measuring current
Current withstand up to 100 A
Output contact: 1x changeover/SPST 8 A Clamp terminals 1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Iskra Doo Part Number
MCR 32 UNI
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
-15 %; +10 %
Current Range
1 - 20 A (AC 50 Hz)
Current Trip Adjustment
2,4,6,8,10,12,14,16,18,20 Amp Setpoints
Settign Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/°C
Peak Overload (10s)
100 Amp
Time delay T1
max. 500 ms
Time delay T2
N/A
Output
SPDT Relay 8 Amp
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Rating
8 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1
Datasheet
Product Datasheet
Application Notes
Monitoring relay MCR-32 serves to monitor current level in single phase AC circuits. Due to its fl uent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.
Iskra Doo MS-25-6.3, 3 Phase Motor Protection Switch
Motor Protection Circuit Breakers are a special type of circuit breaker designed for protection of a wide range of single and 3 phase AC motors against overload and Short circuit. Used in industry, small machines agricultural machines, compressors etc.
Features :
Magnetic and Thermal releases
< 50mS Trip Delay Time
3 Pole Disconnect
Short Circuit Breaking Capacity up to 4kA
Voltage resettable version available
Customised versions available
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
AS/NZ 61009-1
Specification
Iskra Doo Part Number
MS-25-6.3
Functions
3 Phase Motor Protection Switch
Nominal Voltage
230/400VAC @ 50/60Hz
Nominal Current Range
4 - 6.3 Amp RMS
Trip Delay Time
< 50ms
Rated Frequency
50/60 Hz
Operating Temperature
-25 to 60 Deg C
Rated Operations
100,000 Ops
Insulation Voltage
690V
Overload Protection
Thermal and Magnetic Release
Breaking Capacity
230V(6kA) 415V(4kA) 500V(2.5kA) 690V(2kA)
Approvals
CSA, EAC
Standards
IEC/EN 60947-2/4-1/5-1, IP20 (IP40 Installed) IEC 61008 ; AS/NZ 61009-1
Weight
230g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Alternatives
Trent FGV2 Series
MS Power MSD151R16U1B, Rectifier Diode 150 Amp, 1600V, 3/8"24UNF, Anode Stud
Features
Full blocking capability over wide temperature range
Hermetic metal case with glass insulator
Threaded stud
Applications
Power Supplies
Uncontrolled Rectifiers
Oil Cooled Circuits
Battery Chargers
Specification
MS Power Part Number
MSD151R16U1B
Vrrm
1600V
Diode Configuration
Anode Stud
IF(av) @ 100 Deg C
165 Amp
IF(av) @ 125 Deg C
130 Amp
Itsm
2.5 kA
VF(to)
0.85V
Tj(max)
180°C
rF
1.3mΩ
Termination Style (Tail)
10mm Round Lug
Termination Style (Stud)
3/8" -24UNF2A
Tail Length to Stud
185mm
R th(j-c)
0.28°C/W
R th(c-h)
0.05°C/W
Weight
110g
Mounting Torque
10 - 13 Nm
Factory Pack Qty
10
Country Of Origin
China
MS Power Headquarters
Germany
Datasheet
Product Datasheet
MS Power MSD Series Stud Mount Rectifier Diode
Features
Full blocking capability over wide temperature range
Hermetic metal case with glass insulator
Threaded stud
Applications
Power Supplies
Uncontrolled Rectifiers
Oil Cooled Circuits
Battery Chargers
Specification
MS Power Part Number
MSD16R16UB
Vrrm
1600V
Diode Configuration
Anode Stud
IF(av) @ 100 Deg C
N/A
IF(av) @ 125 Deg C
16 Amp
Itsm
350 Amp
VF(to)
0.85V
Tj(max)
180°C
rF
11mΩ
Termination Style (No Tail)
2.2mm Solder Tab
Termination Style (Stud)
10 - 32 UNF
Tail Length to Stud
N/A
R th(j-c)
2.7°C/W
R th(c-h)
1.0°C/W
Weight
5.5g
Mounting Torque
2 Nm
Factory Pack Qty
50
Country Of Origin
China
MS Power Headquarters
Germany
Datasheet
Product Datasheet
Gigavac P125CDA, Contactor SPST-NO, 30 AMP, 1200VDC, 24VDC Coil Contactor
Features
Hermetically Sealed (Patented) rated to 175 Deg C
High Efficiency Dual DC Coils - 12,24,48VDC options
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Small and lightweight
Flexible package for installation
ROHS2 Compliant
Bidirectional Switching capability
Specification
Gigavac Part Number
P125CDA
Main Contact Type
SPST-NO
Auxiliary Contact Type
N/A
Coil Voltage
24VDC
Load Current
30 Amp
Mechanical Life @ 0 Amp
100,000 Operations
Impulse Withstand
6kV rms
Control Input Terminals
M3 Screw
Special Feature
N/A
Mounting Style
Panel Mount (M4)
Load Voltage Range
1200VDC
Standards
UL508, NEC 690.11 and 690.12 DC, ROHS2
Termination Style
M4 Screw
Unit Weight
90g
Factory Pack Qty
1
Datasheet
Product Datasheet
Gigavac P195BDA, Contactor SPST-NO, 80 AMP, 1200VDC, 12VDC Coil Contactor
Features
Perfect for Photovoltaic/Battery Systems
Hermetically Sealed (Patented) rated to 175 Deg C
High Efficiency Dual DC Coils - 12,24,48VDC options
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Small and lightweight
Flexible package for installation
Chassi level power terminals
Specification
Gigavac Part Number
P195BDA
Main Contact Type
SPST-NO
Auxiliary Contact Type
N/A
Coil Voltage
12VDC
Load Current
80 Amp
Mechanical Life @ 0 Amp
100,000 Operations
Dielectric at Sea Level
4.3kV rms
Control Input Terminals
M3 Screw
Special Feature
N/A
Mounting Style
Panel Mount (M4)
Load Voltage Range
1200VDC
Standards
UL508, NEC 690.11 and 690.12 DC
Termination Style
M4 Screw
Unit Weight
135g
Factory Pack Qty
1
Datasheet
Product Datasheet
FP075080P, 750/5 Amp Split Core CT, Class 1, 2.5VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FP075080P
Technology
Split Core AC Clip On Current Transformer
Ratio
750/5
Aperture Size
50 x 80mm
VA Rating
2.5VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
750Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Datasheet
Product Datasheet
Installation Guide
Iskra Doo TSD 1 UNI, Twilight Switch, Universal 12-240VAC/DC Power Supply, 16 Amp SPST CO Relay
TSD 1 Series serves to monitor luminance from 1 to 50,000lx, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Used to control lights on the basis of ambient light intensity
External sensor IP44 suitable for mounting on the wall (cover and holder of a sensor are a part of the package)
Red LED output indication
1-MODULE, DIN rail mounting Level of ambient intensity is monitored by an external sensor and output is switched according to set level on the device
Control input for additional control, e.g. time switch, preswitch etc.
Level of illumination adjustable in two ranges: 1 - 100 lx and 100 - 50000 lx Adjustable time delay to eliminate short term fluctuation in illumination
Supply voltage AC 230 V or AC/DC 12 - 240 V
Output contact: 1x changeover/ S
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Iskra Doo Part Number
TSD 1 UNI
Voltage Range
AC 12 - 240 VAC/DC
Operating Range
-15 %; +10 %
Current Range
0.05 - 5 A (AC 50 Hz)
Trip Adjustment
Potentiometer
Setting Accuracy
30 %
Burden
max. 12 VA
Repeatability
1 %
Temperature Drift
0.1%/°C
Peak Overload (10s)
100 Amp
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Luminance range
2 Ranges 1-100lx, 100-50,000lx
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Rating
16 A / AC1
Breaking capacity
4000 VA / AC1, 384 W / DC
Inrush current (3s)
30 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
109 g
Standards
EN 60255-6, EN 61010-1
Datasheet
Product Datasheet
Perspex Cover for F Series Power Controllers up to 100 Amp
See the following brochures for dimensions of each controller
F330 Brochure
F431 Brochure
F430 Brochure