TPR-3SL055H-F, SCR Phase/Burst Controller Fan Cooled, 400VAC 3 Wire (400V L-L, 230V L-N), 3 Phase, 1-5V/4-20/0-20mA/POT Input, with In built Fuses, 44 Amps per Phase @ 50 Deg C
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
3 Phase, or Single Phase, Angle/Burst Controller
4-20mA/1-5V/10K POT Input Proportional Control
Fully enclosed IP20
Phase Angle or Burst switching
Aluminium/Plastic Frame
Removable Cover
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Specification
Fastron Part Number
TPR-3SL055H-F
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA (Default), 1-5V, 10K POT)
Load Current
44 Amps Per Phase @ 50 Deg C
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
2 x NO Relay Contact
Comms
Optional RS485 Modbus RTU
Special Feature
Internal Fuse
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
100-240VAC +/-10%
Delay on Start
NA
Soft Start
Programmable from 0 to 60 seconds
Termination Style
Screw
Unit Weight
4kg (6kg Packed)
Factory Pack Qty
1
Technical Docs
User Manual
Advanced Energy Thyro-A-3A-400-100-H-RLP3, Three Phase SCR Controller 100 Amp 400VAC +10/-57%, Phase(VAR), Burst(TAKT) Fire, SWITCH Operating Modes, Voltage Control, Current Feedback, Power Limit Options
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustments
Synchronisation Function for Multiple TAKT Sync
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (VAR Mode Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-3A-400-100-H-RLP3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Three Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
Crouzet Millenium 3 Series Programmable Logic Controllers
Highly visible blue LCD with 4 lines of 18 characters and configurable backlighting
More cost effective solution
Allow the use of the entire library of specific functions blocs of the software workshop
Extended temperature range (-20 °C →+70 °C)
Analogue inputs 0-10 VDC, Potentiometer, NTC, LDR (0-20 mA/Pt100 with converters)
Open to XN network communication extensions, digital I/O, analogue, Pt100 extensions
HMI Screens Available
Specification
Crouzet Part Number
88974164 (XD26-16I/10O R)
Analogue Inputs
0-10VDC (x6)
Digital Inputs
12/24VDC (4.4mA @ 12VDC) (x16)
Digital Outputs
Relay, 5-30VDC,24-250VAC @ 10mA minimum (x10)
PWM SSR Output
12-24VDC @ 500mA (x4)
Expandable
Yes
LCD Display
Yes
Mounting Style
DIN Rail Mount (124.6mm)
Supply Voltage Range
24VAC (21.6 - 28.8VAC)
Termination Style
Screw
Weight
350g
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Selection Chart
Software
Crouzet Touch Soft V6.00.02.173
Software M3-soft-AC9-V3.1.2.0_ML
Remote Control Software CVD_PC_V2_3_01_02
Crouzet Soft EVO EM4 1.12.01.14
Fastron FTPS-3-400-50-420, SCR SCR Phase/Burst Controller, 400VAC 3 Wire (400V L-L, 230V L-N), 4-20/0-20mA/5K POT Input, 3 Phase, with In built Fuses, 40 Amps per Phase @ 50 Deg C
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
Made in China, Low cost
3 Phase, Phase Angle/Burst Controller
4-20mA Input Proportional Control (0-10V/1-5V/5K POT input on request)
Fully enclosed IP20
Phase Angle or Burst switching
Aluminium Frame
Removable Cover
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Specification
Fastron Part Number
FTPS-3-400-50-420
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA default (0-10V/0-5V/5K POT on request)
Load Current
40 Amps Per Phase @ 50 Deg C
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
1 x NO Relay Contact (not available with RS485 Option)
Comms
Optional RS485 Modbus RTU
Special Feature
Internal Fuse
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
230VAC +/-10%
Delay on Start
Programmable from 0 to 10 seconds
Soft Start
Programmable from 0 to 10 seconds
Termination Style
Screw
Unit Weight
4kg (6kg Packed)
Factory Pack Qty
1
Technical Docs
User Manual
Modbus Register Map
Calibration Procedure
Wiring Detail
FPT-135 800/5A 5P20 15VA Protection Class CT, 800/5A, Class 5P20 15VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 800/5A 5P20 15VA
Technology
Protection Class Current Transformer
Ratio
800/5
Aperture Size
81 x 135mm
VA Rating
15VA
Accuracy Class
Class 5P20
Output
5 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
800Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
3kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
FPT-135 1000/5A 5P35 5VA Protection Class CT, 1000/5A, Class 5P35 5VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 1000/5A 5P35 5VA
Technology
Protection Class Current Transformer
Ratio
1000/5
Aperture Size
81 x 135mm
VA Rating
5VA
Accuracy Class
Class 5P35
Output
5 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
1000Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
FPT-135 1000/1A 5P20 15VA Protection Class CT, 1000/1A, Class 5P20 15VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 1000/1A 5P20 15VA
Technology
Protection Class Current Transformer
Ratio
1000/5
Aperture Size
81 x 135mm
VA Rating
15VA
Accuracy Class
Class 5P20
Output
1 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
1000Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
FPT-135 800/1A 5P20 10VA Protection Class CT, 800/1A, Class 5P20 10VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
Specification
Fastron Electronics Part Number
FPT-135 800/1A 5P20 15VA
Technology
Protection Class Current Transformer
Ratio
800/5
Aperture Size
81 x 135mm
VA Rating
10VA
Accuracy Class
Class 5P20
Output
1 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10DegC / 50DegC
Continuous Current (max)
800Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
Fastron Electronics FESCT-055-250-1-IP65, 250Amp Measurement, 1 Amp Output Split Core CT's, Class 1, w/10M Flying leads, ø 55mm Aperture
Features
Quick Release Split Core System
10m Flying Leads
ø 55mm
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurement, 1 Amp Outputs
Specification
Fastron Electronics Part Number
FESCT-055-250-1-IP65
Technology
Split Core AC Current Transformer
Ratio
250/5A
Aperture Size
ø 55mm
VA Rating
2.5VA
Accuracy Class
Class 1
Output
1 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Dimensions
180x138x52mm
Mounting Style
Panel Mount
Operating Temperature Range
-35°C / 55°C
Continuous Current (max)
250Amp x 1.2
Termination Style
10M Twisted Pair 0.34mm^2
Unit Weight
2000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics FESCT-055-300-1-IP65, 300Amp Measurement, 1 Amp Output Split Core CT's, Class 1, w/10M Flying leads, ø 55mm Aperture
Features
Quick Release Split Core System
10m Flying Leads
ø 55mm
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurement, 1 Amp Outputs
Specification
Fastron Electronics Part Number
FESCT-055-300-1-IP65
Technology
Split Core AC Current Transformer
Ratio
300/5A
Aperture Size
ø 55mm
VA Rating
2.5VA
Accuracy Class
Class 1
Output
1 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Dimensions
180x138x52mm
Mounting Style
Panel Mount
Operating Temperature Range
-35°C / 55°C
Continuous Current (max)
300Amp x 1.2
Termination Style
10M Twisted Pair 0.34mm^2
Unit Weight
2000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics FESCT-075-800-5-IP65, 800Amp Measurement, 5 Amp Output Split Core CT's, Class 1, w/10M Flying leads, ø 75mm Aperture
Features
Quick Release Split Core System
10m Flying Leads
ø 75mm
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurement, 5 Amp Outputs
Specification
Fastron Electronics Part Number
FESCT-075-800-5-IP65
Technology
Split Core AC Current Transformer
Ratio
800/5A
Aperture Size
ø 75mm
VA Rating
7.5VA
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Dimensions
180x138x52mm
Mounting Style
Panel Mount
Operating Temperature Range
-35°C / 55°C
Continuous Current (max)
800Amp x 1.2
Termination Style
10M Twisted Pair 0.34mm^2
Unit Weight
2000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Advanced Energy Thyro-A-1A-500-60-H-RL3, Thyro-A-1A-Series Single Phase SCR Controller 60Amp 500VAC Phase(VAR), Burst(TAKT), Quick TAKT(QTM), VT(on Request), SWITCH Operating Modes
Features
Optional Profinet,Profibus,Ethernet,Modbus Comms
500VAC +10/-57% Voltage, Current or Power Control
Built in Fuse
Smallest footprint on the market
Single Phase Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
Quick TAKT Mode (QTM), VT Mode (on request)
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
Potentiometer Adjustment
USB Configuration/Bias Setting
Synchronisation Function (dASM Module Recommended)
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
AC Soft Starter (Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-1A-500-60-H-RL3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Single Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
500VAC +10/-15% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 30kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide