FP050080P, 500/5 Amp Split Core CT, Class 0.5 2.5VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FP050080P
Technology
Split Core AC Clip On Current Transformer
Ratio
500/5
Aperture Size
50 x 80mm
VA Rating
2.5VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
500Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Datasheet
Product Datasheet
Installation Guide
LEM ART-B22-D175-SP3, AC Measurement Rogowski Coil (coil only). 17.5cm Diameter, Class 0.5, 3M Shielded Cable Connection
Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary circuit (measurement). The patented Perfect Loop Technology dramatically reduces both the error due to the position of the measured conductor within the aperture, and the error due to the proximity of external conductors.
The ART series single phase flexible rope CT from LEM. In conjunction with AI-PMUL combined integrator & signal conditioner LEM offer True RMS 0-5V, 0-10V, 0-20mA, 4-20mA outputs, or direct linear outputs 0.333V or 0.166V
Included is a 17.5cm diameter rope CT, and 1.5M of twisted pair (1000V) output leads for connection to an integrator, or meter/logger with integration function.
LEM coils come with 5 year warranty
Features
Rated insulation voltage 1000 V Cat III PD2
Accuracy Class 0.5 (IEC 61869-2)
Protection degree IP67
? 70, ? 125, ? 175, ? 300 mm sensing aperture
3 m output cable (other lengths available see page 8)
Ambient temperature ?40 °C … +80 °C
Very flexible and thin coil: 6.1 mm
Slot for attaching the loop on the primary with a cable tie
? 2 mm hole to pass a security seal tampering
An innovative patented clasp drastically reduces the positioning error near the closing
Internal shield for enhanced measurement accuracy at low primary currents.
Advantages
Thin, flexible, and light weight solution
Very low positioning error
Quick, non-intrusive and easy setup
A single sensor for a large current range without overload
Less influenced by external fields
Adaptable for a large range of cable diameters
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010; IEC 61010-2-32 ed.3: 2012
1) IEC 61869-1 ed1.0: 2007; IEC 61869-2: ed1.0: 2012
1) IEC 61869-6: draft 2016; IEC 61869-10: draft 2016
UL
Specification
LEM Part Number
ART-B22-D175-SP3
Function
AC Current Measurement
Measuring Range
0 - 5,000 Amp RMS (Contact Us for Possible Replacement for wider range)
Secondary Voltage (Sensitivity)
22.5mV
Frequency Measuring Range
50-300kHz
Operating Voltage
Self Powered
Accuracy
0.5% from 25 to 5000 Amp
Phase Angle
< 0.004
Coil Diameter (?)
17.5cm
Coil Circumference
55cm
Integrator to Coil Cable
3M Twisted Pair
Maximum Voltage
1000V Reinforced insulation according to EN 61010-1
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
7.4kV
Overload
350,000 Amp
Termination Style
2 Stripped Wires
Weight
138g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
Product Datasheet
Application Notes
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modeling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ? 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ? 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Techsem MTC570-18-416F3, Dual Thyristor Module, 570 Amp, 1800V
Features
Thyristor for line frequency
Pressure Contact Technology
Electrically insulated base plate
Industrial standard package
Long-term stability
3600V Isolation
60mm Base Width
Applications
Power Converter
Line rectifying 50/60 Hz
Deep Cycle Applications
Controlled Rectifiers
Softstart AC motor control
AC power control
Lighting and temperature control
Specification
Techsem Part Number
MTC570-18-416F3
Vrrm
1800V
Diode Configuration
Dual Thyristor Module
IF(av) @ 85 Deg C
500 Amp
Package Size
W:60mm L:144mm D:52mm
Itsm
17 kA
VF(to)
0.9V
Tj(max)
125°C
rF
0.27mΩ
I(gt) @ 25 Deg C
250mA
Terminals
M10 Screw
Hole Centres
80mm x 48mm(M6)
Gate Terminals
Spade (A 2.8 - 0.8 DIN 46244)
R th(j-c)
0.065°C/W
R th(c-h)
0.02°C/W
Weight
1500g
Mounting Torque
6 Nm (12 Nm Terminals)
Factory Pack Qty
2
Certification
UL Listed, ROHS
Techsem Headquarters
China
Datasheet
Product Datasheet
Alternatives
See MCC552-16io1
See TT570N16KOF
Gigavac GX16CEB, Contactor SPST-NO, 600+ AMP, 12-800VDC, 24VDC Coil, 8 Pin Deutch Connector, SPST-NO Auxiliary Contact, IP67, IP69K
Features
Hermetically Sealed (Patented) rated to 175 Deg C
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 & IP69K
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Flexible package for installation
Chassi level power terminals
Salt Fog MIL-STD-810
Specification
Gigavac Part Number
GX16CEB
Main Contact Type
SPST-NO
Auxiliary Contact Type
SPST-NO
Coil Voltage
24VDC
Load Current
600+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.2kV rms
Control Input Terminals
8 Pin Deutch Connector
Aux Contact Terminals
8 Pin Deutch Connector
Special Feature
Hermetically Seal rated to 175 Deg C
Mounting Style
Panel Mount (M5)
Load Voltage Range
12-800VDC
Standards
UL1604, IP67, IP69K, SAE J1171, ISO8846
Termination Style
M12
Unit Weight
900g
Factory Pack Qty
1
Datasheet
Product Datasheet
Gigavac GX16FEB, Contactor SPST-NO, 600+ AMP, 12-800VDC, 48VDC Coil, 8 Pin Deutsch Conector, SPST-NO Auxiliary Contact, IP67, IP69K
Features
Hermetically Sealed (Patented) rated to 175 Deg C
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 & IP69K
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Flexible package for installation
Chassi level power terminals
Salt Fog MIL-STD-810
Specification
Gigavac Part Number
GX16FEB
Main Contact Type
SPST-NO
Auxiliary Contact Type
SPST-NO
Coil Voltage
48VDC
Load Current
600+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.2kV rms
Control Input Terminals
8 Pin Deutsch Conector
Aux Contact Terminals
8 Pin Deutsch Conector
Special Feature
Hermetically Seal rated to 175 Deg C
Mounting Style
Panel Mount (M5)
Load Voltage Range
12-800VDC
Standards
UL1604, IP67, IP69K, SAE J1171, ISO8846
Termination Style
M8
Unit Weight
900g
Factory Pack Qty
1
Datasheet
Product Datasheet
Gigavac HXNC241CAB, Normally Closed Contactor SPST-NC 200 Amp 1500VDC, 24VDC Coil, 38cm Flying leads, with SPST-NO Auxiliary Contact Continuous Duty, IP67, IP69K
Features
Hermetically Sealed (Patented) rated to 175 Deg C
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 & IP69K
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
PWM option provides additional drive control flexibility
Built in Coils suppression for all DC Coils
Flexible package for installation
Chassi level power terminals
Salt Fog MIL-STD-810
Specification
Gigavac Part Number
HXNC241CAB
Main Contact Type
SPST-NC
Auxiliary Contact Type
SPST-NO
Coil Voltage
24VDC
Load Current
200 Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
5.375kV rms
Control Input Terminals
38cm Flying Leads
Aux Contact Terminals
38cm Flying Leads
Special Feature
Hermetically Seal rated to 175 Deg C
Mounting Style
Panel Mount (M5)
Load Voltage Range
1500VDC
Standards
UL1604, IP67, IP69K, SAE J1171, ISO8846, CE
Termination Style
M8
Unit Weight
440g
Factory Pack Qty
1
Datasheet
Product Datasheet
Crydom M505015F, Bridge, single phase, half controlled, 480VAC input, 50 Amp, with freewheeling diode
Features
Package with DCB ceramic base plate
Isolation voltage 2500 V∼
Planar glass passivated chips
Low forward voltage drop
UL registered, E 148688
Applications
Heat and temperature control for industrial furnaces and chemical processes
Lighting control
Motor control
Power converter
Advantages
Easy to mount with two screws
Space and weight savings
Improved temperature and power cycling capability
High power density
Spec
Crydom Part Number
M505015F
AC Line voltage
480V
Device Configuration
Single Phase Half Controlled Rectifier Bridge
DC Output @ 100 Deg C
100 Amp
Package Size
W:57.5mm L:44mm D:34.6mm
Itsm
600 A
VF(to)
1.7V
Tj(max)
125°C
rF
N/A
Terminals
M5 (1.5Nm)
Hole Centres
41.2mm (M5)
Gate Terminals
N/A
R th(j-c)
0.7°C/W
R th(c-h)
N/A
Weight
106g
Isolation
2.5kV
Factory Pack Qty
10
Certification
UL Listed
Crydom Headquarters
USA
Datasheet
Product Datasheet
Alternatives
M5010012F
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Secure Meters DPM48I150-2, 48mm x 96mm LCD Digital Ammeter, 0-6 Amp Input, 0.5% Accuracy, 40 to 300VAC/DC Supply, IP54 (Optional IP65)
Features
LCD Dual Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 48mm Panel Space
52mm Depth
CE Approved
ROHS and REACH
Specification
Secure Part Number
DPM48I150-2
Frequency Range
45-65 Hz
Accuracy
0.5%
Input
0-6 Amp
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
40-300VAC/DC
Termination Style
Screw
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Standards
IEC / EN 61010-1; IEC / EN 61010-2-030
Protection Degree
IP54 (IP65 Optional)
Weight
280g
Factory Pack Qty
1
Datasheet
Product Datasheet
Manual
DPM Series User Manual
Application Notes
Panel Meters Blog Articles
Iskra Doo WM3-6 230DB Three Phase Power Meter with RS485 & IR Comms
65 Amp direct connect, no CT's required
Ultra slim 3 DIN
IR Communication as standard
RS485 communication up to 19,200 bit/s
Optional Pulse Output
True RMS values of currents and voltages
Measurements of active, reactive power
Accuracy class 1
The meter is intended for measuring, and monitoring single-phase electrical power networks. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of Active and Reactive Power
Optional Pulse Output
RS485 Comms
IR Comms
Graphic LCD with illumination
Multilingual support
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
WM3-6 230DB
Functions
Energy Meter
Supply Voltage
230V L-N, 400V L-L 5 Amp -20% +15% < 5VA
Nominal Measurement Range
230V L-N, 5 Amp -20% +15%
Maximum Measurement Range
230V L-N, 5 Amp -20% +15%
Nominal Current Input
3 x 65 Amp AC Direct Connect
Infra Red Output
19200 bit/s
Tariff Input
N/A (Optional)
Accuracy
Class 1 (I,U,F,PF,) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Dimensions
53.6 x 84 x 69.4mm (3 DIN)
Pulse Output
N/A
Isolation
4kV
RS485
1200-19200 b/s
Weight
270g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
LEM ART-B22-D125-SP3, AC Measurement Rogowski Coils (coil only). 12.5cm Diameter, Class 0.5, 3M Shielded Cable Connection
Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary circuit (measurement). The patented Perfect Loop Technology dramatically reduces both the error due to the position of the measured conductor within the aperture, and the error due to the proximity of external conductors.
The ART series single phase flexible rope CT from LEM. In conjunction with AI-PMUL combined integrator & signal conditioner LEM offer True RMS 0-5V, 0-10V, 0-20mA, 4-20mA outputs, or direct linear outputs 0.333V or 0.166V
Included is a 12.5cm diameter rope CT, and 1.5M of twisted pair (1000V) output leads for connection to an integrator, or meter/logger with integration function.
LEM coils come with 5 year warranty
Features
Rated insulation voltage 1000 V Cat III PD2
Accuracy Class 0.5 (IEC 61869-2)
Protection degree IP67
? 70, ? 125, ? 175, ? 300 mm sensing aperture
3 m output cable (other lengths available see page 8)
Ambient temperature ?40 °C … +80 °C
Very flexible and thin coil: 6.1 mm
Slot for attaching the loop on the primary with a cable tie
? 2 mm hole to pass a security seal tampering
An innovative patented clasp drastically reduces the positioning error near the closing
Internal shield for enhanced measurement accuracy at low primary currents.
Advantages
Thin, flexible, and light weight solution
Very low positioning error
Quick, non-intrusive and easy setup
A single sensor for a large current range without overload
Less influenced by external fields
Adaptable for a large range of cable diameters
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010; IEC 61010-2-32 ed.3: 2012
1) IEC 61869-1 ed1.0: 2007; IEC 61869-2: ed1.0: 2012
1) IEC 61869-6: draft 2016; IEC 61869-10: draft 2016
UL
Specification
LEM Part Number
ART-B22-D125-SP3
Function
AC Current Measurement
Measuring Range
0 - 5,000 Amp RMS (Contact Us for Possible Replacement for wider range)
Secondary Voltage (Sensitivity)
22.5mV
Frequency Measuring Range
50-373kHz
Operating Voltage
Self Powered
Accuracy
0.5% from 25 to 5000 Amp
Phase Angle
< 0.004
Coil Diameter (?)
12.5cm
Coil Circumference
40cm
Integrator to Coil Cable
3M Twisted Pair
Maximum Voltage
1000V Reinforced insulation according to EN 61010-1
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
7.4kV
Overload
300,000 Amp
Termination Style
2 Stripped Wires
Weight
130g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
Product Datasheet
Application Notes
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modeling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ? 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ? 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Crydom A2450EG, Solid State Relay, Single Phase 18-36VAC Control, 50A, 24-280VAC Load w/status LED
Features
• Ratings from 25A to 125 Amp @ 24-280 VAC
• SCR output for heavy industrial loads
• Zero voltage or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• AC & DC control types
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
Spec
Crydom Part Number
A2450EG
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
24VAC (18 - 36VAC)
Load Current
50 Amp (rms)
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Panel Mount
Load Voltage Range
90 - 280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
SDM630Modbus-MID-V2-CL1 (SDM630-M), DIN Rail Mount kWh Meter, 3 Phase, Class 1, 100 Amp Direct Connect input, w/ 2 x pulse outputs and RS485 Comms, MID Approved
3 x 100 amp Direct Connect
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
2 x Pulse Outputs (1 Configurable)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630Modbus-MID-V2-CL1 (SDM630-M)
Functions
Three Phase Energy Meter
Supply Voltage
NA
Nominal Measurement Range
415V L-L 230V L-N, 100 Amp
Maximum Measurement Range
480V L-L 230V L-N, 100 Amp
Nominal Current Input
Direct connect 3 x 100 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility