Risbabh EM94-Z-V2-L-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V2-L-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Northern Design Multicube Modular Single and 3 Phase Measurement Module
Up to 20 Meters in 1 with additional modules. Requires multicube modular master unit
Minimum 2 x 3 phase or 1 x single phase circuits with measurement module
Alternative master with logger
Optional pulse output modules
Requires Multicube Modular Master or Multicube Master with Logger
Optional 12 way pulse/alarm digital output modules
Nominal current up to 0.383V (For 0.333V CT Input) and nominal voltage up to 240V L-N 415V L-L
Graphic Display
Optional RS485 or Ethernet communication up to 19,200 bit/s
True RMS measurement of currents and voltages
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, reactive power, power factor, harmonics, etc.) from the measured signals.
Features :
Dual 3 phase Measurement Module
2 x 3 Phase or 6x Single Phase Circuits
Accuracy class 1
Simple Menu
Optional MODBUS RTU RS485 communication up to 19,200 bit/s or Ethernet communication
5 Year Warranty
240V AC power supply
Specification
Northern Design Part Number
Multicube Modular Master
Functions
kWh Meter, Energy Meter, Power Quality
Supply Voltage
240VAC < 15VA
Nominal Measurement Range
415V L-L 240V L-N, 0.333V
Maximum Measurement Range
480V L-L 280V L-N, 0.383V
Display
Graphic LCD
Pulse Output
12
Accuracy
Class 1 (kW,kWh) Class 1(Active), Class 2 Reactive
Ethernet
Optional
Real Time Clock
1min/month (30ppm)
Isolation
2.11kV
RS232/RS485
N/A (Optional 2400-19200 b/s)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
ABS with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
164 x 96mm x 29mm
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product brochure
User manual
Wiring Diagram
Suitable 0.333V CT's
Split Core CT's
Northern Design Cube 400-M2 Series 3 Phase Power Meter
Optional 2 Pulse Input or Outputs
Nominal current up to 6 A (For 5A CT Input) and nominal voltage up to 240V L-N
Three Line Display
Optional RS 232/RS 485 communication up to 19,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Optional THD up to 15th Harmonic
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 1
Simple Menu
Optional RS 232/RS 485 communication up to 19,200 bit/s or Ethernet communication
MODBUS and Ethernet communication protocol
240V AC power supply
Specification
Northern Design Part Number
Cube 400-M2
Functions
kWh Meter, Energy Meter
Supply Voltage
240VAC < 5VA
Nominal Measurement Range
415V L-L 240V L-N, 5 Amp
Maximum Measurement Range
415V L-L 280V L-N, 6 Amp
Display
Three Line LCD
Pulse Output
2 (input or output)
Accuracy
Class 1 (kW,kWh) Class 1(Active) Class 2(kVar,PF)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS232/RS485
N/A (Optional 2400-19200 b/s)
Weight
350g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Product Manual
Product Comms Manual
Application Notes
Dual Tariff Guide
CT Cable Losses
Meter Accuracy at Low Current
Current Input Isolation
SDM630MCT-LORAWAN-MID-AS923, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 1, 1/5 Amp CT Connect, w/ 2 x pulse outputs and LoRaWaN AS923 Wireless Comms
1/5 Amp CT Input
LoRaWaN AS923
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
The meter is intended for measuring, and monitoring single-phase or three phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-LORAWAN-MID-AS923
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
1/5 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
Comms
LoRaWaN AS923
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Modbus Utility
EEM Meter Setting Software Utility
Risbabh EM94-Z-V1-L-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-L-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Northern Design Power Rail 350-M2 Three Phase Power Meter
5 Amp CT Input
Optional RS 232/RS 485 communication up to 19,200 bit/s
True RMS values of currents and voltages
Power Quality Measurements
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, Hours Run, Peak Demand etc to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Optional MODBUSRS 232/RS 485 communication up to 19,200 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Northern Design Part Number
Power Rail 350-M2
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N, 5 Amp +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 5 Amp +/-15%
Nominal Current Input
5 Amp AC
Pulse Output
3 x NO Voltage Free Contacts 100mA @ 100VAC/DC
Accuracy
Class 1 (I,U,F,PF,) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
106mm x 90mm x 58mm (6 modules wide)
Isolation
3.5kV
RS232/RS485
(Optional 1200-19200 b/s)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 6 Modules
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Product Manual
Product Comms Manual
Option Links
Application Notes
CT Cable Losses
Meter Accuracy at Low Current
Current Input Isolation
Eastron SDM630MCT-RC, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 0.5, 85mV/kA Rogowski Coil Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms. COILS NOT INCLUDED
85mV/kA Rogowski Coil Connect
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 0.5
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-RC
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
85mV/kA Rogowski Coil Connect
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 0.5 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
Northern Design Power Rail IP 350-M2 Three Phase Power Meter
5 Amp CT Input
Modbus TCP communication
True RMS values of currents and voltages
Power Quality Measurements
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, Hours Run, Peak Demand etc to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus TCP communication
Pulse output as standard
Graphic LCD with illumination
Specification
Northern Design Part Number
Power RailIP 350-M2
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N, 5 Amp +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 5 Amp +/-15%
Nominal Current Input
5 Amp AC
Pulse Output
3 x NO Voltage Free Contacts 100mA @ 100VAC/DC
Accuracy
Class 1 (I,U,F,PF,) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
106mm x 90mm x 58mm (6 modules wide)
Isolation
3.5kV
Comms
Modbus TCP Ethernet
Weight
250g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 6 Modules
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Product Manual
Product Comms Manual
Option Links
Application Notes
CT Cable Losses
Meter Accuracy at Low Current
Current Input Isolation
Northern Design Cube 350-M2-C-H Series 3 Phase Power Meter
2 Pulse Input or Outputs
Nominal current up to 6 A (For 5A CT Input) and nominal voltage up to 240V L-N
Single Line Display
Optional RS 232/RS 485 communication up to 19,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
THD up to 15th Harmonic
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 1
Simple Menu
Optional RS 232/RS 485 communication up to 19,200 bit/s or Ethernet communication
MODBUS and Ethernet communication protocol
240V AC power supply
Specification
Northern Design Part Number
Cube 350-M2-C
Functions
kWh Meter, Energy Meter
Supply Voltage
240VAC < 5VA
Nominal Measurement Range
415V L-L 240V L-N, 5 Amp
Maximum Measurement Range
415V L-L 280V L-N, 6 Amp
Display
Single Line LCD
Pulse Output
2 (input or output)
Accuracy
Class 1 (kW,kWh) Class 1(Active) Class 2(kVar,PF)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS232/RS485
2400-19200 b/s
Weight
250g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Product Manual
Product Comms Manual
Application Notes
Dual Tariff Guide
Eastron SDM630MCT-3L, Tri 3 Phase DIN Rail Mount kWh Meter with Easyclick, 3 x 3 Phase or 9 x Single Phase, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 3 x 3 Phase Connect
100mA RJ12 9 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 2 x three phase or 6 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-3L
Functions
Tri Three Phase Energy Meter/ 9 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
System Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
600g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility