Fastron FRI8-01/2, Current Monitoring Relay AC 0.2 - 2A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choise of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 8 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI 8-01/2
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
-15 %; ? %
Current Range
0.1 - 2 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.
Fastron FC5-M-1U-2-G-4 PID Controller, 24VDC with 2 x Relay Alarms, K,E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 72x72mm,0-10V Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
FC5-M-1U-2-G-4
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Multirange K,E,J,N,T,S,R,B Thermocouple, PT100/Cu20 RTD Input/Linear Current 4(0)-20mA/Linear Voltage 0-10(5)V
Option 1
2 x Relay Alarms standard (Excludes 72x72mm with SSR/Relay output)
Mounting Style
72x72mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Datasheet & User Manual
Datasheet
User Manual
FC5 Communication Protocol
LEM DVL 1500, Digital Voltage Transducer, 1500V, +/-15...24VDC, 50mA output, 8.5kV Isolation
Features
Bandwidth DC to 14kHz
Digital Transducer (ASIC based)
Closed loop transducer using Hall effect
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVL 1500
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-15..24 VDC Bipolar, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 1500V
Measurement Range
+/- 2250V
Output
50 mA @Vpn
Isolation
8.5 kV
Bandwidth
DC-14 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
270g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Risbabh EM94-Z-V3-M-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-M-D
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Fastron FC5-L-1U-2-G-4 PID Controller, 24VDC with 2 x Relay Alarms, K,E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x96mm,0-10V Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
FC5-L-1U-2-G-4
Control Output
0-10V
Input
Multirange Type K, J, E,S,T,R, Pt100, Cu50/Linear Current 4(0)-20mA/Linear Voltage 0-10(5)V
Option 1
2 x Relay Alarms standard (Excludes 96x96mm with SSR/Relay output)
Mounting Style
96x96mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Datasheet & User Manual
Datasheet
User Manual
FC5 Communication Protocol
VX4-USNA-A2, Temp Controller, 48x48mm, 100-240VAC, Multirange Input, SSR Output, 2 Alarms
Multirange Input (Programmable)
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
UL/CE Approved
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant
Specification
Hanyoung Nux Part Number
VX4-USNA-A2
Control Output 1 (Heat)
SSR 12-15VDC @30mA
Control Output 2 (Cool)
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Multirange Type K/J/E/T/R/B/S/L/N/U/W/PLII/PT100/JPT100/4-20mA/0-20mA/1-5V/0-5V/0-10V/0-50mV/0-100mV. Note for Direct Current Input please use 250 Ohm Resistor in Parallel to the input terminals.
Alarm
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 1
2nd Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 2
N/A
Mounting Style
48 x 48mm Panel Mount
Supply Voltage
85 - 265VAC
Termination Style
Screw
Weight
250g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
VX Series Brochure
VX Series Instruction Manual
Free Software
Hanyoung Nux TCS Software
Hanyoung Nux TCS Software User Manual
VX Series SB Driver (Windows 7) Not required for Windows 10 or 11
Fastron FRW8-01, Temperature Control Relay, Heat/Cool, 24 - 240VAC/DC, Din Rail Mount, 1 x SPST 16 Amp Relay, Includes PTC Probe for -15 to 45 Deg C Range
Features :
Range -15°C to 45°C
Multi-voltage 24 →240 V AC/DC
LED status indicator
Heating or Cooling ON/OFF Control With Hysteresis
Specification
Fastron Part Number
FRW8-01
Function
Temperature Control Relay
Nominal Voltage
24 → 240 V AC/DC
Digital Output
1 x SPST, 250VAC/DC @ 16 Amp
Sensor Type
PTS-N-3.0M PTC Sensor
Min Breaking Current
10mA/12VDC
Temp Control Ranges
-15°C to 45°C
Repeatability
0.5%
Isolation
4kV
Repetition Accuracy
0.5%
Termination Style
Screw
Weight
80g
Factory Pack Qty
1
Certification
CE
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
Hanyoung Nux UP18RD-8NA-C, Inductive Proximity Sensor M18 Cylindrical Unshielded, 8mm Sensing Distance (0-6.4mm Set), 12-24VDC NPN Output, Normally Open NO, Connector TypeUP18RD-8NA-C, Inductive Proximity Sensor M18 Cylindrical Unshielded, 8mm Sensing Distance (0-6.4mm Set), 12-24VDC NPN Output, Normally Open NO, Connector Type
200HZ Response
12-24VDC Operating voltage
200mA Maximum Output
Built in reverse power, surge, overcurrent protection
50 Meg Ohm Insulation residtance
Specification
Hanyoung Nux Part NumberFastron NArt Number
UP18RD-8NA-C
Sensor Type
Inductive Proximity Sensor M18 Cylindrical Unshielded
No of Wires
3
Material
Stainless Steel Body / Face PBT / Cable Holder Polyester Elastomer
Shielded
NO
Sensing Distance
4mm (0-3.2mm Set)
Frequency Response
200Hz
Output Type
12-24VDC NPN Normally Open
Sensor Thread Size
M18
Standard Target
Ferrous Metal 8 x 8 x 1mm
Approvals
CE
Residual Voltage
1.5V
Current Consumption
6mA
Ambient Operating Temperature
-25 to 70 Deg C
Insulation Resistance
50 Meg Ohm (500V dc in Megohms) between all terminals and case
Dielectric Strength
1500Vac 1 min at 50/60Hz Between all terminals and case
Shock Resistance
500m/s^2, 3 times in each direction
Vibration Resistance
10-55Hz Double amplitude: 1.5mm, 2 hours in each direction X,Y,Z)
Termination
Cable Type (stdnard 2M cabel length), connector cable type, connector type
Colour
NPN:Green, NPN:Navy
Protection Class
IP67
Approvals
CE
Weight
130g
Factory NAck Qty
1
Datasheet
Product Datasheet
Product Datasheet
Fastron FC5-L-1A-2-G-4 PID Controller, 24VDC with 2 x Relay Alarms, E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x96mm,4-20mA Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Fastron Part Number
FC5-L-1A-2-G-4
Control Output
4-20mA
Input
Multirange Type,K,E,J, Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
2 x Relay Alarms standard (Excludes 96x96mm with SSR/Relay output)
Mounting Style
96x96mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Datasheet & User Manual
Datasheet
User Manual
FC5 Communication Protocol
Fastron FRI 8-03/8, Under/Over Current Monitoring Relay AC 0.8 - 8 A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8-03/8 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choise of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 10 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI 8-03/5
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
-15 %; ? %
Current Range
0.8 - 8 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multi voltage supply is an advantage.
Fastron FRI 8-03/0.5, Under/Over Current Monitoring Relay AC 0.05 - 0.5 A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choise of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 8 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI 8-03/0.5
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
-15 %; ? %
Current Range
0.05 - 0.5 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.