Fastron Electronics FESCT-055-400-5-IP65, 400Amp Measurement, 5 Amp Output Split Core CT's, Class 1, w/10M Flying leads, ø 55mm Aperture
Features
Quick Release Split Core System
10m Flying Leads
ø 55mm
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurement, 5 Amp Outputs
Specification
Fastron Electronics Part Number
FESCT-055-400-5-IP65
Technology
Split Core AC Current Transformer
Ratio
400/5A
Aperture Size
ø 55mm
VA Rating
2.5VA
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Dimensions
180x138x52mm
Mounting Style
Panel Mount
Operating Temperature Range
-35°C / 55°C
Continuous Current (max)
400Amp x 1.2
Termination Style
10M Twisted Pair 0.34mm^2
Unit Weight
2000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Advanced Energy Thyro-A-3A-400-16-H-RL3, Three Phase SCR Controller 16 Amp 400VAC +10/-57%, Phase(VAR), Burst(TAKT) Fire, SWITCH Operating Modes, Voltage Control, Current Feedback Option
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustments
Synchronisation Function for Multiple TAKT Sync
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (VAR Mode Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-3A-400-16-H-RL3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Three Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
Advanced Energy Thyro-A-3A-400-45-H-RLP3, Three Phase SCR Controller 45 Amp 400VAC +10/-57%, Phase(VAR), Burst(TAKT) Fire, SWITCH Operating Modes, Voltage Control, Current Feedback, Power Limit Options
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustments
Synchronisation Function for Multiple TAKT Sync
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (VAR Mode Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-3A-400-45-H-RLP3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Three Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
Fastron Electronics AM5H-A-D-V1-D-NAN, 96x48mm DC Ammeter DC Voltmeter 0-50mVDC with 4-20mA output, 22-60VAC/DC supply, Digital Panel Meter & Transmitter, 5 Digit
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 5 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 96 x 48mm Panel Space
90mm Depth
Specification
Fastron Electronics Part Number
AM5H-A-D-V1-D-NAN
Conditioner Output
4-20mA
Input
0 - 50mVDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Display Type
5 Digit RED LED
Termination Style
Screw
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
User Manual
Application Notes
Panel Meters Blog Articles
Rishabh Rish Con-V(500)-F-H-O1A1-O200-D-Z-Z, AC Voltage Transducer, Input Programmable True RMS 50Hz 57-500VAC Full Scale, 0-20mA, 60-300VAC Supply, with Display
Digital output setting 0-20mA/4-20mA/0-10V
Dual output version available
300mS response time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 43.75 x 100.9 mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish Con-V(500)-F-H-O1A1-O200-D-Z-Z
Measurement Output
4-20mA/0-20mA/0-10V User Selectable
Input
57 - 500VAC 50/60Hz
Overlaod (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-40 - 70°C
Supply Voltage
60 - 300VAC
Accuracy
0.2%
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Datasheet
Product Datasheet
Technical Support
Rish Con P setup procedure blog
Gigavac Sensata GV211BAX, Contactor SPST-NO, 150+ AMP, 12-900VDC, 12VDC Coil, 38cm Flying leads, IP67, IP69
Features
Hermetically Sealed
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 - Temporary water immersion (30 Min)
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
PWM option provides additional drive control flexibility
Built in Coils suppression for all DC Coils
Flexible package for installation
Specification
Gigavac Part Number
GV211BAX
Main Contact Type
SPST-NO
Auxiliary Contact Type
None
Coil Voltage
12VDC
Load Current
150+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.5kV rms
Control Input Terminals
38cm Flying Leads
Special Feature
N/A
Mounting Style
Panel Mount (M5)
Load Voltage Range
12 - 900VDC
Standards
CE, UL1604, IP67, SAEJ1171, UL508
Termination Style
M8
Unit Weight
250g
Factory Pack Qty
1
Datasheet
Product Datasheet
Vishay Estamat MH-12N Automatic Reactive Power Controller 12 Step, 3 Phase
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Programmable Primary CT Ratio
Luminous Display
Various Program Combinations
IP40
Up to 12 steps
Measurement System - Automatic/Manual
230VAC Aux Supply
Overvoltage and Under/Overcompensation Alarm
Specification
Vishay Part Number
Estamat MH-12N
Function
Reactive Power Correction
Nominal Voltage (Un)
415V Line to Line (4 Wire)
Supply Voltage
230VAC (L-N), 12VA 45-65Hz
Relay Rating
250VAC/3Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
N/A
Re-connection Delay Time
1s - 1200s User Adjustable
Desired Power Factor
0.85 IND - 1.00 CAP
Number of Output Relays
13
Smallest Capacitor Current
50mA
CT Input Range
0.05 - 5.5 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
N/A
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP40 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
Product Datasheet
User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Iskra Doo MT406-1254 Series Single Phase AC Voltage Transducer, Fixed zero and span
Class 0.5 (EN 60688)
0-20mA analogue output for Moving Coil Voltmeter
Average RMS values of voltage
Features :
Measurement of up to 125VAC
Self powered
Accuracy class 0.5
Input frequency 50/60Hz
Specification
Iskra Doo Part Number
MT406-1254
Functions
Single Phase AC Voltage Transducer
Supply Voltage
Self Powered
Nominal Measurement Range
110VAC (0-125V Scale)
Maximum Measurement Range
132VAC
Output
0-20mA
Tariff Input
N/A
Accuracy
Class 0.5
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
N/
Weight
340g
Enclosure Material
UL94
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
FP500160P, 5000/5 Amp Split Core CT, Class 1 15VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Electronics Part Number
FP500160P
Technology
Split Core AC Clip On Current Transformer
Ratio
5000/5
Aperture Size
80 x 160mm
VA Rating
15VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
4000Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Datasheet
Product Datasheet
Installation Guide
Iskra Doo KNL90-00-240VAC, AC Contactor 240/400/500/690V, 3 Pole 3 x NO, Nominal Current = 90 Amps, 240VAC Coil
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL90-00-240VAC
Functions
3 Pole Contactor (3 x NO)
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
90 Amp Continuous @ 55 Deg C
Auxiliary Contacts
Optional BFX10-40, 4 Pole Snap On Aux Contacts
Trip Delay Time
2-10ms
Electrical Life
1,200,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
15,000,000 Ops
Control Voltage
240VAC
Power Dissipation
9.4W per pole
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
1.25kg
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue
Iskra Contactor Catalogue
Fastron Electronics GA5-D-V7-D-N, 96x48mm 5 DIGIT Digital Ammeter 0-600VDC input, 100-240VAC/DC Supply
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 5 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 96 x 48mm Panel Space
60mm Depth
Specification
Fastron Electronics Part Number
GA5-D-V7-D-N
Conditioner Output
N/A
Input
0-600VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
96 x 48mm Panel Mount (60mm depth)
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
BH-50-2-24, Split Core Hall Effect DC Current Transducer, +/-50 Amp DC, 4-20mA Bipolar output, 31mm aperture, 24VDC supply
Compact and versatile Split Core DC current sensor, +/-50 Amp DC, 4-20mA Bipolar Output
Features
⌀31mm Aperture
Split Core
DC Bipolar Measurement
4-20mA analogue output
Busbar, or DIN Rail Mounting
Isolated plastic case recognised according to UL94-V0
Advantages
High isolation between primary and secondary circuits
Easy installation
DIN Rail Mount
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
Fastron Part Number
BH-50-2-24
Technology
DC Hall Effect Current Transducer with Process Output
ROHS
Yes
Supply Voltage
24VDC
Nominal Current (DC)
+/-50 Amp DC
Response Time
< 200mS
Output
Bipolar 4-20mA Analogue
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
DC
Mounting Style
DIN Rail Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Elevator Screw
Unit Weight
120g
Factory Pack Qty
6
Datasheet
Product Datasheet