Fastron Electronics FESCT-055-100-1-IP65, 100Amp Measurement, 1 Amp Output Split Core CT's, Class 1, w/10M Flying leads, ø 55mm Aperture
Features
Quick Release Split Core System
10m Flying Leads
ø 55mm
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurement, 1 Amp Outputs
Specification
Fastron Electronics Part Number
FESCT-055-100-1-IP65
Technology
Split Core AC Current Transformer
Ratio
100/5A
Aperture Size
ø 55mm
VA Rating
2.5VA
Accuracy Class
Class 1
Output
1 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Dimensions
180x138x52mm
Mounting Style
Panel Mount
Operating Temperature Range
-35°C / 55°C
Continuous Current (max)
100Amp x 1.2
Termination Style
10M Twisted Pair 0.34mm^2
Unit Weight
2000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Trent FGM6DC-2PL-500 350A, 2 Pole DC Moulded Case Circuit Breaker (MCCB) Fixed Type 20kA 350 Amp, 1000VDC
Miniature Circuit Breakers are used for over-current (overload and short-circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
2 Pole Disconnect
20kA Short Circuit Rating @1000VDC
Suitable for DC Power Systems Including Solar and Battery
Standards :
IEC/EN 60947-3
IP20 (IP40 Installed) IEC 61008
Specification
Trent Part Number
FGM6DC-2PL-400 350A
Functions
2 Pole DC MCCB
Nominal Voltage
1000VDC
Nominal Current Range
350 Amps
Trip Delay Time
< 50ms
Rated Impulse Voltage
12kV
Operating Temperature
-35 to 70 Deg C
Electrical Operations
5,000 Ops
Insulation Voltage
1500V
Short Circuit Current Ics=Icu (Ics/Icu)
20kA
Approvals
CE
Standards
GB/T14048.2, IEC/EN 60947-3, IP20 (IP40 Installed)
Weight
5.7kg
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
CE Declaration
A53TP50D + HS212DR, Solid State Relay, and Heatsink Assembly, 3 Phase 90-280VAC Control, 20 Amp per phase @ 40 Deg C, 48-530VAC Load, LED Status Indicator
Features
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
A53TP50D + HS212DR
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
90-280VAC
Load Current
3 x 20 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Din Rail Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Datasheet
D53TP Series
3 Phase SSR and Heatsink Mounted
HS212 Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
LEM DVL 150 Digital Voltage Transducer, Vpn = 150V, 50mA output, +/-15...24VDC powered, 8.5kV Isolation
Features
Bandwidth DC to 14kHz
Digital Transducer (ASIC based)
Closed loop transducer using Hall effect
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVL 150
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-15..24 VDC Bipolar, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 150V
Measurement Range
+/- 225V
Output
50 mA @Vpn
Isolation
8.5 kV
Bandwidth
DC-14 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
270g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
FPT-50 400/5A 5P20 2.5VA, Protection Class CT, 400/5A, Class 5P20 2.5VA, 52.3 x 32.2mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
Specification
Fastron Electronics Part Number
FPT-50 400/5A 5P20 2.5VA
Technology
Protection Class Current Transformer
Ratio
400/5
Aperture Size
52.3 x 32.2mm
VA Rating
2.5VA
Accuracy Class
Class 5P20
Output
5 Amp AC
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10 Deg C / 50 Deg C
Continuous Current (max)
400Amp x 20
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
1.2 kg
Factory Pack Qty
1
Datasheet
Product Installation Guide and Datasheet
Techsem MD1293-22-432F2A, Single Diode Module, 1293 Amp, 2200V
Features
Diode for line frequency
Pressure Contact Technology
Electrically insulated base plate
Industrial standard package
Long-term stability
3600V Isolation
70mm Base Width
Applications
Power Converter
Line rectifying 50/60 Hz
Deep Cycle Applications
High Powered Rectifiers
DC Blocking Diodes
Flywheel Diodes
Specification
Techsem Part Number
MD1293-22-432F2A
Vrrm
2200V
Diode Configuration
Single Diode Module
IF(av) @ 85 Deg C
1293 Amp
Package Size
W:70mm L:146mm D:90mm
Itsm
40 kA
VF(to)
0.7V
Tj(max)
125°C
rF
0.10mΩ
Terminals
M12 Screw
Hole Centres
80mm x 58mm(M6)
Gate Terminals
Spade (A 2.8 - 0.8 DIN 46244)
R th(j-c)
0.038°C/W
R th(c-h)
0.02°C/W
Weight
2.8kg
Mounting Torque
6 Nm (13 Nm Terminals)
Factory Pack Qty
2
Certification
ROHS
Techsem Headquarters
China
Datasheet
Product Datasheet
Alternatives
DZ1070N18K
Contact Us for Possible Replacement
LEM AHR 800 B10, Hall Effect Current Sensor, 800Amp, True RMS 0-10V output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
0-10V voltage output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 800 B10
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
800 Amp
Maximum Measurement Current (Peak)
2500 Amp
Output
0-10V
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
F923 Series AC Current Transducer with Process Outputs & High and Low Sold State Alarm
Features
Isolated measurement of AC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F923-X-XX-AC-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 2Amp @ 40VDC, 2Amp @ 60VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Wolfracoat C 1.2kg Lubricating Paste for CNC Machines, Gears, Motors, Modules, Capsules or Stud Mount Semiconductors
Features
Electricially and thermally and electrically conductive copper based lubricant.
Large Tubs available on request.
Datasheet
Datasheet
MSDS
Application Notes
Correct Application of Thermal Paste
Advanced Energy Thyro-A-2A-400-100-HRL3, Thyro-A-2A-Series 2 Leg 3 Phase SCR Controller 100Amp 400VAC +10/-57% Burst(TAKT) Fire Mode, Economical Firing Mode, Voltage Control, Current Limit Option
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, 2 Leg Economical Burst Controller Firing Mode
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustment
Synchronisation Function
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-2A-400-100-HRL3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Single Phase AC Switch
Control Modes
2 Leg Burst(TAKT) for low dissipation
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
Advanced Energy Thyro-A-3A-400-45-H-RLP3, Three Phase SCR Controller 45 Amp 400VAC +10/-57%, Phase(VAR), Burst(TAKT) Fire, SWITCH Operating Modes, Voltage Control, Current Feedback, Power Limit Options
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustments
Synchronisation Function for Multiple TAKT Sync
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (VAR Mode Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-3A-400-45-H-RLP3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Three Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
RCS-5A, 5 Amp Output, Class 0.5 INTEGRATOR ONLY Three Phase 500/1000/2500/5000/10000/25000/50000 Amp AC Selectable Measurement Ranges
RCS-5A Integator by Magnelab converts AC input current of up to 50000 amperes to an AC output of 5 Amp.
A 24VDC Power Supply is included to operate the coils.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-5A
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
500/1000/2500/5000/10000/25000/50000 Amp RMS Selectable
Measurement Range
10% - 130% if Ipn
Output Range
0-5 Amp
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
24VDC
Accuracy
1% from 25 to 5000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
12 Inch
Coil Circumference
36 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
3500g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS-VAR Series Installation Guide