F920-A-XX-XX-XX - Signal Conditioner and +/-15VDC Bipolar Power Supply with Adjustable High and Low C/O Relay Alarm. +/- 4V Bipolar Input, For External LEM Hall Effect Sensor
Features
Isolated measurement of AC or DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC Average RMS or DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty, Otherwise 4-6 weeks
Datasheet
Datasheet
Risbabh EM94-Z-V1-H-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display, 60-300VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-H-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
LEM ART-B22-D70-SP3 + AI-PMUL Single Phase Rogowski Coil Set, Class 1, User Selectable 0.333v, 0.166v, True RMS 4-20mA, 0-20mA, 0-10V, 0-5V Outputs, Sensitivity, and Measurement Range, 7cm Diameter
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Included Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D70-SP3 + AI-PMUL
Function
Single Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 7cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Applicaton Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Risbabh EMDC 6002-60-LA-C-2R, 4 Channel DC kWh Meter, Class 0.5, 150-150mV Shunt input, 10-60VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, 4 Line LCD Display, 12-70VDC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 10-60VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EMDC 6002-60-LA-C-2R
Functions
4 Channel DC kWh Meter, Energy Meter
Supply Voltage
12-70VDC
Nominal Measurement Range
10-60VDC
Maximum Measurement Range
10-60VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
LEM HAZ 12000-SB Series Open Loop Hall Effect Current Transducer
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
Features
Instantaneous output version +/-10V, +/-20mA
True RMS output versions 4-20mA, 0-10V putput
Hall effect measuring principle
Galvanic isolation between primary and secondary circuit
Instantaneous voltage output
Isolation voltage 17kV Rms /50 Hz /1min
Low power consumption
Package in PBT meeting UL 94-V0
Instantaneous voltage output
Advantages
Easy installation
Small size and space savings
Only one design for wide Ratings range
High immunity against external interference
Applications
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Power supplies for welding and telecom applications
Application domain
Industrial
Traction
Specification
LEM Part Number
HAZ 12000-SB
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
+/- 15VDC
Load Current (RMS + DC)
12000 Amp
Overload Rating
30000 At
Output
+/-10 V Instantaneous
Isolation
17kV (AC, 50Hz, 1 min)
Bandwidth
DC-3kHz
Mounting Style
Busbar Mount
Operating Temperature Range
-25°C / 85°C
Accuracy
1%
Termination Style
F2023A (FUJICON)
Unit Weight
6kg
Factory Pack Qty
2
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
2026 Application Guide
Risbabh EM94-Z-V1-M-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input,10-60VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-M-M
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V1-L-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-L-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V1-L-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-L-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Eastron Smart X72-5G, Panel Mount Multifuction Meter, Class 0.5S, 50-480VAC, 1A/5A CT input, 30 Parameter, 2 x Digital Pulse/Alarm Outputs, 4 Digital/Tariff Inputs, Modbus RTU RS485 Comms, Self Powered
Metering and Numerical Display
Adjustable tariff clock (Optional 4 Tariffs), display of electric energy consumption in optional currency
Modbus RTU as standard
True RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 30 quantities (U, I, P, THD, IHD, S, PF, PA, f, f, MD, etc.).
Accuracy class 1
Optional 2 or 4 tariff inputs,
Digital Output and Input
Ethernet communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD with Dual Metering and PF Displays
Specification
Eastron Part Number
Smart X72-5G
Functions
Power Quality Meter, Energy Meter
Aux Supply
65-276VAC/90-380VDC
Nominal Measurement Range
50-480V L-L, 1/5 Amp
Maximum Measurement Range
480V L-L, 1/5 Amp
Pulse Outputs
2 x Shared with Digital outputs
Alarm
2 x Digital Outputs (shared with Pulse function)
Tariff Input
4 Digital Inputs
Accuracy
Class 0.5S (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
2.5kV (1 Min)
RS485
2400-38400 b/s
Weight
500g
Certification
MID, UL
Factory Pack Qty
1
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Operating Temperature
-25 →+55 °C
Datasheet
User Manual
LEM HAX 1500-S/SP18, O/L Current Transducer, 1500 Amp, +/-15V Supply, 64 x 21 Square Aperture, +/-4V Output, SP18 = Electrolube, UR5604 A+B Potting
Features
Bandwidth DC to 25kHz
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Wide dynamic range, nominal 100 to 2500 A in one package.
Up to 5500 A measurement range
Applications
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
LEM Part Number
HAX 1500-S/SP18
Technology
Open Loop Hall Effect
Aperture
64 x 21mm Square
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
1500 Amp
Measurement Range
+/-4500 Amp
Overload Rating
+/-30000 At
Output
+/-4 V
Isolation
4.4 kV
Bandwidth
DC-25 kHz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-25°C / 85°C
Accuracy
1%
Termination Style
Molex 5045-04A
Unit Weight
450g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM Application Guide 2026
Risbabh EM94-Z-V1-M-Z, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input,10-60VDC, Single Line LCD Display,10-60VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-M-Z
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.