Risbabh EM94-Z-V3-M-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-M-D
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V1-H-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display, 60-300VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-H-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
RCT-1800-Coil, Single Phase, 6 Inch Rogowski Coil. Requires Integrator or suitable Rogowski Coil mete
The RCS-1800 Single Phase flexible rope CT from Magnelab converts AC input current to mV/kA output.
Included is an 18 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads. Note 6 Inch Diameter when not flexed
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCT-1800-Coil
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
N/A
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
N/A
Accuracy
0.5%
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
500g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Risbabh EM94-Z-V1-L-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-L-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
VA1021B, Liquid PH Tester & Temperature Tester Portable with External BNC Connected Sensor. Range 0-14PH, 0-50 Deg C Accuracy 0.02PH/0.5 Deg C, WITH BLUETOOTH AND APP
Features
Portable /Battery Powered 3 x AAA (500 Hours)
External Sensor (BNC)
Range 0-14PH, 0-50 Deg C
Accuracy 0.02PH/0.5 Deg C
Bluetooth Comms
Free App
Specification
Datasheet
Datasheet
Risbabh EM94-Z-V3-L-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-L-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
TCD-H-1-K HEATING Temp Controller, 48x96mm 230VAC, C/O Relay output, Type K Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-H-1-K
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Type K Thermocouple
Control Mode
Heating ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
48x96mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
Hanyoung Nux LP3-5A3RN, 96x48mm Frequncy/RPM Counter 0.1-50kHz, 0-1VDC / 4.5-24VDC Pulse Input, 85-265VAC supply
Large 5 Digit 0.4 Inch LED Display
250mS Response Time
PC 94 UL V0
Input signals can be NPN, PNP, or 24VDC Pulses depending on the model used
Each unit needs just 48 x 24mm Panel Space
86.2mm Depth
Specification
Fastron Electronics Part Number
LP3-5A3RN
Input
Selectable H:4.5-24VDC / L: 0-1VDC
Measurement Range
0.1Hz - 50kHz
Operating Temperature
-20 - 70°C
Load Voltage
85-265VAC 50/60Hz
Termination Style
Screw
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Safety Approvals
CE
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet / User Manual
Application Notes
Panel Meters Blog Articles
Risbabh EM94-Z-V2-H-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display, 60-300V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V2-H-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V1-M-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input,10-60VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-M-D
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Fastron Electronics GBMC-5-N2-R2NN, 140x420mm, Pulse Input Counter/Totaliser NPN 12V input 4 Digit, Large Panel Meter, 100-240VAC/DC Supply
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMC-5-N2-R2NN
Conditioner Output
None (optional)
Relay Outputs
2
Input
0-3kHz NPN 12VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
N/A
Zero Adjustment Range
N/A
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Risbabh EM94-Z-V1-M-Z, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input,10-60VDC, Single Line LCD Display,10-60VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-M-Z
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.