Rishabh Rish Con P 4WUB 100-500V 1/5A 60-300U 20 D, Active Power/Reactive Power/Apparrent Power/Phase Angle/Power Factor Transducer 4 wire, 100-500V, 5Amp measurement,60-300VAC/DC Supply, 2 x 0-20mA/4-20mA/0-10V output, with display
Measures Active Power/Phase Angle/Power Factor
Measures Apparent/Reactive/Active Power
Digital output setting 0-20mA/4-20mA/0-10V
Dual output version available
300mS response time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 43.75 x 100.9 mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish P 4WUB 100-500V 1/5A 60-300U 20 D
Functions
Power/Phase Angle/Power Factor Transducer 4 wire
Measurement Output
4-20mA/0-20mA/0-10V User Selectable
Input
57 - 500VAC 50/60Hz
Overload (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-40 - 70°C
Supply Voltage
60 - 300VAC, or 24-60VAC/DC
Accuracy
0.2%
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Datasheet
Product Datasheet
Technical Support
Rish Con P setup procedure blog
VFD38AMS43ANSAA, 3 Phase, Variable Frequency Drive, 18.5kW, 29 Amp (Normal Duty)/31.6 Amp (Heavy Duty), 460VAC L-L, 300x175x192mm
Features
3 Phase VFD/VSD
4-20mA, 0-5V, 0-10V Proportional Input Control
7 x Digital Input
2 x STO Inputs
Fully enclosed IP20 (Optional IP40)
Small frame Size
Applications
Fan Motor Control
Production Lines
Transportation
Controlled Power Applications
Suitable for extreme environments such as mining
Specification
Delta Part Number
VFD38AMS43ANSAA
Rated Operation Temperature
50°C (With Derating)
Configuration
3 Phase AC Drive
Control Voltage
4-20mA, 0-20mA, 0-10V
Digital Inputs
7 x Mix / 2 x STO
Load Current
24.4 Amp(Normal Duty) / 27.4 Amp(Heavy Duty) Per Phase
Control Range
0.1-599 Hz
Dimensions
250x130x185mm
Mounting Style
Panel Mount
Supply Voltage Range
323-528VAC
Soft Start
0-6000s
Termination Style
Screw
Unit Weight
6.5kg
Factory Pack Qty
1
Datasheet
MS300 Brochure
User Manual
BLR-Q(U)12R DM (3ACM12R-BEL-O-DM), Power Factor Regulator & Power Quality Analyser, 12 Step, 1 Phase Measurement, Power Quality Alarms, WITH BATTERY BACKUP, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
BLR-Q(U)12R DM / 3ACM12R-BEL-O-DM
Function
Reactive Power Correction & Power Quality Analyser
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
Battery Backup
YES
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
FP080080P, 800/5 Amp Split Core CT, Class 0.5, 2.5VA Clip On AC Current Transformer, 50 x 80mm Aperture, Dimension 145 x 159 x 37mm
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FP080080P
Technology
Split Core AC Clip On Current Transformer
Ratio
800/5
Aperture Size
50 x 80mm
VA Rating
2.5VA
Accuracy Class
Class 1
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
800Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Datasheet
Product Datasheet
Installation Guide
VFD25AMS43ANSAA, 3 Phase Variable Frequency Drive, 460VAC, 11kW, 19.5 Amp (Normal Duty)/21.3 Amp (Heavy Duty), 460VAC L-L, 0.1-599 Hz, 250x130x185mm
Features
3 Phase VFD/VSD
4-20mA, 0-5V, 0-10V Proportional Input Control
7 x Digital Input
2 x STO Inputs
Fully enclosed IP20 (Optional IP40)
Small frame Size
Applications
Fan Motor Control
Production Lines
Transportation
Controlled Power Applications
Suitable for extreme environments such as mining
Specification
Delta Part Number
VFD25AMS43ANSAA
Rated Operation Temperature
50°C (With Derating)
Configuration
3 Phase AC Drive
Control Voltage
4-20mA, 0-20mA, 0-10V
Digital Inputs
7 x Mix / 2 x STO
Load Current
19.5 Amp(Normal Duty) / 21.3 Amp(Heavy Duty) Per Phase
Control Range
0.1-599 Hz
Dimensions
250x130x219mm
Mounting Style
Panel Mount
Supply Voltage Range
323-528VAC
Soft Start
0-6000s
Termination Style
Screw
Unit Weight
6.5kg
Factory Pack Qty
1
Datasheet
MS300 Brochure
User Manual
Fastron Electronics SCT-F36-400, 0.333V, 400Amp measurement Split Core CT's Class 1, 35mm Aperture
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F36-400
Technology
Split Core AC Current Transformer
Ratio
400/0.333V
Aperture Size
ø 35 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
400Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
400g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
RCS-1200-1000 0.333V, 3 Phase 1000Amp AC Measurement 4 Inch ⌀ Rogowski Coils with Integrator, Class 1 Flexible Current Sensor System:
The RCS-1200 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-1000
Specification
Magnelab Part Number
RCS-1200-1000
Function
AC Current Measurement
Nominal Measurement Current
1000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Fastron FCT-D16-5-420, AC Split Core Current Transducer, 16mm Aperture, 0-5 Amp Measurement, 4-20mA Average RMS output, 24VDC Loop Powered, Class 0.5, 50-400 Hz Operation
Features
Average RMS Output
Split Core
4-20mA Current Output
Cable Mounting
24VDC Loop Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Motor Control
Actuators
Lamp Failure
Specification
LEM Part Number
AT 5 B420L
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
24VDC Loop Powered (10mA)
Load Current (RMS)
5 Amp
Maximum Measurement Current (RMS)
6 Amp
Output
4-20mA (Average RMS)
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
50 - 400Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
0.5%
Aperture
16mm
Termination Style
Screw
Approvals
CE,UL,ROHS
Unit Weight
140g
Factory Pack Qty
6
Datasheet
Product Datasheet
Fastron Electronics SCT-F50-600-5A, 5 Amp, 600Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-600-5A
Technology
Split Core AC Current Transformer
Ratio
600/5 Amp
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
600Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
1000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
SDM630Modbus-MID-V2-CL1 (SDM630-M), DIN Rail Mount kWh Meter, 3 Phase, Class 1, 100 Amp Direct Connect input, w/ 2 x pulse outputs and RS485 Comms, MID Approved
3 x 100 amp Direct Connect
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
2 x Pulse Outputs (1 Configurable)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630Modbus-MID-V2-CL1 (SDM630-M)
Functions
Three Phase Energy Meter
Supply Voltage
NA
Nominal Measurement Range
415V L-L 230V L-N, 100 Amp
Maximum Measurement Range
480V L-L 230V L-N, 100 Amp
Nominal Current Input
Direct connect 3 x 100 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
BLR-Q(U)06R MB(3ACM06R-BEL-O-QMB), Power Factor Regulator & Power Quality Analyser, 6 Step, 1 Phase Measurement, Power Quality Alarms, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 6 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
RS485 Modbus RTU
Specification
Beluk Part Number
BLR-Q(U)06R MB/ 3ACM06R-BEL-O-QMB
Function
Reactive Power Correction & Power Quality Analyser
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
6
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Modbus RTU Included
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)