Eastron SDM630MCT-2L-TCP, Dual 3 Phase DIN Rail Mount kWh Meter with Easyclick, 2 x 3 Phase or 6 x Single Phase, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 2 x 3 Phase Connect
100mA RJ12 6 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 2 x three phase or 6 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-2L-TCP
Functions
Dual Three Phase Energy Meter/ 6 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
600g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Risbabh EM94-Z-V3-L-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-L-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Eastron Europe SDM120Modbus, DIN Rail Mount kWh Meter, Single Phase, Class 1/Class B, 45Amp Direct Connect, w/ 2 x pulse outputs and RS485 Comms, MID Approved
45 amp Direct Connect
1 x Configurable Pule Output (via Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM120Modbus-MID
Functions
Single Phase Energy Meter
Supply Voltage
N/A
Nominal Measurement Range
230V L-L 230V L-N, 45 Amp
Maximum Measurement Range
276V L-L 230V L-N, 45 Amp
Nominal Current Input
Direct connect 45 Amp
Pulse Output
1 x 1000imp/kwh, 1 x Configurable via Modbus 60/100(default)/200ms
Accuracy
Class 1/Class B (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
24mm x 100mm x 66mm (1 module wide)
Isolation
4kV
RS485
2400-38400 b/s
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 6 Modules
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
Modbus Protocol
Setup Video
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
Risbabh EM94-Z-V2-L-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V2-L-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V3-L-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V3-L-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
201-1000VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Eastron Europe SDM120CTModbus-MID, DIN Rail Mount kWh Meter, Single Phase, 240VAC aux, Class 1/Class B, 5 Amp CT Connect, w/ 2 x pulse outputs and RS485 Comms, MID Approved
5 Amp CT Connect
1 x Configurable Pule Output (via Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy Class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM120CTModbus-MID
Functions
Single Phase Energy Meter
Supply Voltage
230V L-N, 5 Amp +/-15% < 5VA
Nominal Measurement Range
230V L-L 230V L-N, 45 Amp
Maximum Measurement Range
276V L-L 230V L-N, 45 Amp
Nominal Current Input
5 Amp CT
Pulse Output
1 x 1000imp/kwh, 1 x Configurable 60/100(default)/200ms
Primary CT Ratio
5,10,20,30,40,50,75,100,125,150,200,250,300,400,600 Amp only
Accuracy
Class 1/ Class B (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
24mm x 100mm x 66mm (1 module wide)
Isolation
4kV
RS485
2400-38400 b/s
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 6 Modules
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
Modbus Protocol
Setup Video
Modbus Utility
EEM Meter Setting Software Utility
Risbabh EM94-Z-V1-L-Z, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-L-Z
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V2-M-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V2-M-D
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Eastron Europe SDM630MCT-2L, Dual 3 Phase DIN Rail Mount kWh Meter with Easyclick, 2 x 3 Phase or 6 x Single Phase, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 2 x 3 Phase Connect
100mA RJ12 6 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 2 x three phase or 6 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-2L
Functions
Dual Three Phase Energy Meter/ 6 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
600g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Secure Elite E500C-5202, Panel Mount Network Recorder with Harmonics (15th) & PQ Parameters, Class 0.5S, 50..500VAC 50/60Hz, RS485 Modbus RTU, 35..300V DC/85..300VAC Aux, 16MB Dual Logger , TFT Touch Screen, 10 Years Warranty
Automatic range of nominal current up to 6 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-L, 300V L-N
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
Dual Loggers, configurable for Instant or accumulated energy
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
RS 485 communication up to 38400 bit/s as standard
Optional Protocol Modules Modbus TCP, BACNet IP, Profinet, SCADA EC61850
Optional Modules for Analogue outputs and Relay Alarms
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values and accumulated energy. Includes Harmonics to the 15th
Accuracy class 0.5S
Dual Internal Loggers
Measurement of 20 minimal and maximal values in different time periods
RS 232/RS 485 communication up to 38400 bit/s or Ethernet communication
MODBUS communication protocol
Optional Protocol Modules Modbus TCP, BACNet IP, Profinet, SCADA EC61850
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
Universal or AC/DC power supply
Graphic Colour TFT 320 x 240 pixels (53x70mm)
Automatic range of nominal current up to 6 A and nominal voltage up to 500 V
Multilingual support
User-friendly Free ECon Configuration software
Specification
Secure Part Number
E500C-5202
Functions
Power Quality Meter(15th Hamonic), Energy Meter, Network Recorder
Supply Voltage
Universal 35..300V DC, 85..300VAC
Nominal Measurement Range
240V L-N, 1/5 Amp, 415V L-L 1/5 Amp
Maximum Measurement Range
300V L-N, 1/5 Amp, 500V L-L 1/5 Amp
Alarm
Optional Module 2 Relay/Pulse Outputs
Tariff/Digital Inputs
TOU Tarriff Clock
Accuracy
Class 0.5S (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Analogue Output
Optional Module 2 x Programmable Analogue Outputs
Internal Memory
2 x 8MB
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS232/RS485
N/A Optional
CT Termination
Ring Terminals
Weight
600g
Certification
CE, CSA, ROHS
Warranty
10 Years from dispatch from Secure Warehouse
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Cross Reference
The Following meters are close equivalents to Elite 500 Series. For further details please contact Fastron Sales Team
Elite 500_400_300_100 series competition replacement for
Schneider
Siemens
Accuenergy (RS485 +DNP3 default)
Socomec
Selec
PM 5000 series
PAC 2000 series
ACCUVIM-CL + DNP3.0
DIRIS A-20
Selec MFM376
PM 5100
PAC 3200
ACCUVIM-CL + DNP3.0
DIRIS A-20
MFM384, CL-1, RS485
PM 5300
ACCUVIM-IIR
DIRIS A-20
MFM383A
PM 5500
PAC 4200
ACCUVIM-IIR(+ BACnet)
DIRIS A-20
MFM384. RS485
PM 6463
Siemens 7KMPAC4200
ACCUVIM-IIR (+ Profibus)
DIRIS A-30/ DIRIS - A60 (PQ Feature)
MFM384-C-CE-CL05, RS485
PM 5650
ACCUVIM-IIR (+ IEC 61850)
DIRIS A-30 + Profibus
MFM384-C-CE-CL05, RS485
PM 5760
ACCUVIM-EL
DIRIS A-30 +Ethernet
MFM384-C-CE-CL05, RS485
PM5330
ACCUVIM-EL (+ BACnet)
DIRIS A-30/ DIRIS A-60
PM 5560
ACCUVIM-EL (+ Profibus)
DIRIS A-30/ DIRIS A-60
DM6200H
ACCUVIM-EL (+ IEC 61850)
PM2220
ACCUVIM-II R +Ethernet
PM2230 / DM2120 (LED)
PM 5350
Eastron Europe DCM230 1-2-1-1 V2, DIN Rail Mount DC kWh Meter, 1000VDC, 85-265VAC aux, Class 1, 45/60/75mV Shunt Connect, w/ 1 x pulse outputs and RS485 Modbus RTU Comms, Single Tariff, MID Approved
45/60/75mV Shunt Connect
RS 485 communication up to 38,400 bit/s as standard
1 x Pulse Outputs (1 Configurable)
Bidirectional Measurement
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records DC Current and Voltage (DC Power) value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, energy, power) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
DCM230 1-2-1-1 V2
Functions
DC Energy Meter
Supply Voltage
9-60VDC
Nominal Measurement Range
5-300VDC,5-600VDC,5-1000VDC (See version 1
Maximum Measurement Range
5-1000VDC
Nominal Current Input
Shunt up to 2000Amp See our DC Current Shunt Section for Suitable Shunt
Pulse Output
1 x Configurable 60/100/200ms
Tariff Input
N/A
Accuracy
Class 1 (I,U,kW,kWh)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
36mm x 100mm x 66mm (2 modules wide)
Isolation
4kV
RS485
2400-38400 b/s
Weight
250g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Utility
EEM Meter Setting Software Utility
MC330 SEDMNAT 240/E230 2RO/RS485, Panel Mount Multifunction Meter, Class 1, 240VAC 61 Parameter (U, I, P, Q, S, PF, PA, f, ϴ, MD...), 4 Energy Counters,16Hz to 400Hz, 2 x Relay Outputs, RS485 Comms, 230V/240V Aux Supply, Internal Logger
Internal 8MB Logger
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Internal Logger
Measurement of instantaneous values of more than 60 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 1
Measurement of 20 minimal and maximal values in different time periods
Optional dual tariff inputs and pulse or relay outputs
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 600 V
Multilingual support
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MC330 H ARNG SUDMNAT
Functions
Power Quality Meter, Energy Meter
Supply Voltage
230V/240VAC
Nominal Measurement Range
500V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
2 x Relay Outputs
Tariff/Digital Input
N/A (Optional 4 x Tarrif/Digital Inputs)
Accuracy
Class 0.5 (I,U,F,PF,θ,) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Internal Logger
Yes (8MB)
RS232/RS485
2400-115200 b/s
Weight
500g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual