Fastron FRI 8-03/16, Under/Over Current Monitoring Relay AC 1.6 - 16 A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8-03/16 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choise of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 10 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI 8-03/16
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
-15 %; ? %
Current Range
1.6 - 16 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1 x changeover/ SPDT (AgNi / Silver Alloy)
Rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current fl ow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.
Fastron Electronics FESCT-3000-1000, 1000Amp 0.333V Class 1 Measurement Split Core CT's, 1M Flying Leads, 76x127mm Aperture
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Electronics Part Number
FESCT-3000-1000
Technology
Split Core AC Current Transformer
Ratio
1000/0.333V
Aperture Size
76x127mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333VAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
1000Amp x 1.2
Termination Style
Terminals
Unit Weight
3000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
A53TP50D + HS212, Solid State Relay, and Heatsink Assembly, 3 Phase 90-280VAC Control, 20 Amp per phase @ 40 Deg C, 48-530VAC Load, LED Status Indicator
Features
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
A53TP50D + HS212
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
4-32VDC
Load Current
3 x 20 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Panel Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Datasheet
HS103DR
D53TP Series
3 Phase SSR and Heatsink Mounted
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
VX2-UCNA-A2D2, Temp Controller, 48x96mm, 100-240VAC, Multirange Input, 4-20mA Output, 2 Alarms, 2 x SV
Multirange Input (Programmable)
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP65 (front panel only)
UL/CE Approved
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant
Specification
Hanyoung Nux Part Number
VX2-UCNA-A2D2
Control Output 1 (Heat)
4-20mA
Control Output 2 (Cool)
N/A
Input
Multirange Type K/J/E/T/R/B/S/L/N/U/W/PLII/PT100/JPT100/4-20mA/0-20mA/1-5V/0-5V/0-10V/0-50mV/0-100mV. Note for Direct Current Input please use 250 Ohm Resistor in Parallel to the input terminals.
Alarm
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 1
2nd Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 2
2 x SV Input (2 Setpoint Selection/External Setting Input)
Mounting Style
48 x 96mm Panel Mount
Supply Voltage
85 - 265VAC
Termination Style
Screw
Weight
350g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
VX Series Brochure
VX Series Instruction Manual
Free Software
Hanyoung Nux TCS Software
Hanyoung Nux TCS Software User Manual
VX Series SB Driver (Windows 7) Not required for Windows 10 or 11
Crouzet 87622162, Totalizer/Counter with orange Backlit Display CTR24 10-264VAC/DC, Lithium Battery Powered 8 year battery Life
Hour Meter with two PNP Inputs
IP65
4-30VDC PNP Inputs
6 Digit Display (8mm)
10-264VAC/DC Aux Supply
48 x 24mm Cutout
Rest On Panel or External Inhibit
Datasheet
Product Datasheet
Fastron GPH8048ZA3, Solid State Contactor SSR, Single Phase 90-280VAC Control, 80A, 70-480VAC Load, Din Rail Mount
Ratings from 10A to 100 Amp @ 70-480 VAC
Contactor Style for retrofit
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
CE Compliant to EN60950-1
IP20
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Spec
Fastron Part Number
GPH8048ZA3
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
90-280VAC
Load Current (single unit)
67 Amp (rms) @ 20 Deg C Ambient, 57 Amp (rms) @ 40 Deg C Ambient
Surge Capability
1400 Amp (peak)
Special Feature
Contactor Style IP20 Terminals
Mounting Style
DIN Rail Mount
Load Voltage Range
70 - 480VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
500g
Factory Pack Qty
20
Datasheet
Product Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Crydom D2425D, Dual Solid State Relay, Two Pole 4-15VDC Control, 2 x 25A, 24-280VAC Load
Features
Ratings from 2 x 25A to 2 x 40 Amp @ 24-530 VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
D2425D
Switching Type
Zero Crossing (Dual)
ROHS
Yes (Details)
Control Voltage
4-15VDC
Load Current
25 Amp (rms)
Surge Capability
250 Amp (peak)
Special Feature
Dual SSR
Mounting Style
Panel Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
D53TP50D + HS212DR, Solid State Relay, and Heatsink Assembly, 3 Phase 4-32VDC Control, 20 Amp per phase @ 40 Deg C, 48-530VAC Load, LED Status Indicator
Features
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
D53TP50D + HS212DR
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
4-32VDC
Load Current
3 x 20 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Din Rail Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Datasheet
D53TP Series
3 Phase SSR and Heatsink Mounted
HS212 Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
D53TP50D + HS212, Solid State Relay, and Heatsink Assembly, 3 Phase 4-32VDC Control, 20 Amp per phase @ 40 Deg C, 48-530VAC Load, LED Status Indicator
Features
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
D53TP50D + HS212DR
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
4-32VDC
Load Current
3 x 20 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Panel Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Datasheet
D53TP Series
3 Phase SSR and Heatsink Mounted
HS212 Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Shinko WCS13ARR/MM Series Dual Loop Digital Indicating Controllers
Differential control, Tank level control, converter function are standard features
5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
9-step pattern (for SV and time) is a standard feature
UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant (Details)
Specification
Shinko Part Number
WCS13ARR/MM
Control Output 1
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Control Output 2
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Multirange (refer to datasheet)
Option
None
Mounting Style
48 x 48mm Panel Mount
Supply Voltage
100 - 240VAC
Termination Style
Screw
Weight
180g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
WCS Series Brochure
WCS Series User Manual
, Obsolete. Contact Us for Possible Replacement for replacement model
Xmer CT Split 125/50SC 800/5 Class 1 10VA, 55 x 85mm Aperture
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Rishabh Part Number
Xmer CT Split 125/50SC 800/5 Class 1 10VA
Technology
Split Core AC Current Transformer
Ratio
800/5
Aperture Size
55 x 85mm
VA Rating
10VA
Accuracy Class
Class 1
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-30°C / 85°C
Continuous Current (max)
600Amp x 1.2
Termination Style
Screw
Unit Weight
1.25kg
Factory Pack Qty
9
Datasheet
Product Datasheet
Fastron FDV-50-420-24, DC Voltage Transducer, Din Rail Mount, 0-100VDC, 4-20mA output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-50-420-24
Analogue Output
4-20mA
Input
0 - 50VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet