LEM HAZ 12000-SB Series Open Loop Hall Effect Current Transducer
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
Features
Instantaneous output version +/-10V, +/-20mA
True RMS output versions 4-20mA, 0-10V putput
Hall effect measuring principle
Galvanic isolation between primary and secondary circuit
Instantaneous voltage output
Isolation voltage 17kV Rms /50 Hz /1min
Low power consumption
Package in PBT meeting UL 94-V0
Instantaneous voltage output
Advantages
Easy installation
Small size and space savings
Only one design for wide Ratings range
High immunity against external interference
Applications
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Power supplies for welding and telecom applications
Application domain
Industrial
Traction
Specification
LEM Part Number
HAZ 12000-SB
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
+/- 15VDC
Load Current (RMS + DC)
12000 Amp
Overload Rating
30000 At
Output
+/-10 V Instantaneous
Isolation
17kV (AC, 50Hz, 1 min)
Bandwidth
DC-3kHz
Mounting Style
Busbar Mount
Operating Temperature Range
-25°C / 85°C
Accuracy
1%
Termination Style
F2023A (FUJICON)
Unit Weight
6kg
Factory Pack Qty
2
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM HO 100-S-0100 Series Open Loop AC/DC Hall Effect Sensor
Features
Open loop current transducer
Voltage output
Single power supply +5 V
Overcurrent detect 2.93 × IP N (peak value)
Galvanic separation between primary and secondary circuit
Low power consumption
Factory calibrated
Compact design for panel mounting
Aperture: 15 × 8 mm
Factory calibrated
Repositionabel mounting foot
Dedicated parameter settings available on request
Advantages
Low offset drift
Over-drivable Vref
Creepage / clearance > 8 mm
Fast response
Applications
AC variable speed and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Combiner box
Solar inverter on DC side of the inverter (MPPT).
Standards
IEC 61800-1: 1997
IEC 61800-2: 2015
IEC 61800-3: 2004
IEC 61800-5-1: 2007
IEC 62109-1: 2010
UL 508: 2013.
Application Domain
Industrial.
Specification
LEM Part Number
HO 100-S-0100
Technology
Open Loop Hall Effect
Aperture
15 x 8mm
ROHS
Yes
Supply Voltage
5 VDC
Load Current (RMS + DC)
100 Amp
Measurement Range
+/-250 Amp
Output
2.5 Vref
Isolation
4.3 kV
Bandwidth
DC-100 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 105°C
Accuracy
1%
Termination Style
JST B5B-PH type
Unit Weight
32g
Factory Pack Quantity
25
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM HOP 1000-SB O/L Split Core Hall Effect Current Sensor, 500 Amp, +/-4V Output, 40 x 104mm Aperture, +/-12..15V Supply, Panel Mount, X = 2% Open Loop AC/DC Hall Effect Sensor
Features
Bandwidth DC to 10kHz
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical or Busbar Mounting
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Wide dynamic range, nominal 500 to 2000 A in one package.
Up to 3000 A measurement range
Applications
Power supplies for TELECOM (monitoring and measurement)
Electrical chemistry
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Chopper
Battery supplied applications
Specification
LEM Part Number
HOP 1000-SB
Technology
Open Loop Hall Effect
Aperture
104 x 40mm Square
ROHS
Yes
Supply Voltage
+/-12..15 VDC Bipolar, Isolated
Load Current (RMS + DC)
1000 Amp
Measurement Range
+/-2000 Amp
Overload Rating
Contact Us for Possible Replacement
Output
+/-4 V
Isolation
3 kV
Bandwidth
DC-10 kHz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
2%
Termination Style
Molex 5045-04A
Unit Weight
590g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM HOP 1500-SB O/L Split Core Hall Effect Current Sensor, 1500 Amp, +/-4V Output, 40 x 104mm Aperture, +/-12..15V Supply, Panel Mount, X = 2% Open Loop AC/DC Hall Effect Sensor
Features
Bandwidth DC to 10kHz
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical or Busbar Mounting
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Wide dynamic range, nominal 500 to 2000 A in one package.
Up to 3000 A measurement range
Applications
Power supplies for TELECOM (monitoring and measurement)
Electrical chemistry
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Chopper
Battery supplied applications
Specification
LEM Part Number
HOP 1500-SB
Technology
Open Loop Hall Effect
Aperture
104 x 40mm Square
ROHS
Yes
Supply Voltage
+/-12..15 VDC Bipolar, Isolated
Load Current (RMS + DC)
1500 Amp
Measurement Range
+/-3000 Amp
Overload Rating
Contact Us for Possible Replacement
Output
+/-4 V
Isolation
3 kV
Bandwidth
DC-10 kHz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
2%
Termination Style
Molex 5045-04A
Unit Weight
590g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM HOP 500-SB O/L Split Core Hall Effect Current Sensor, 500 Amp, +/-4V Output, 12.5 x 41mm Aperture, +/-12..15V Supply, Panel Mount, X = 2% AC/DC Hall Effect Sensor
Features
Bandwidth DC to 8kHz
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical or Busbar Mounting
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Wide dynamic range, nominal 200 to 600 A in one package.
Up to 900 A measurement range
Applications
Power supplies for TELECOM (monitoring and measurement)
Electrical chemistry
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Chopper
Battery supplied applications
Specification
LEM Part Number
HOP 500-SB
Technology
Open Loop Hall Effect
Aperture
12.5 x 41mm Square
ROHS
Yes
Supply Voltage
+/-12..15 VDC Bipolar, Isolated
Load Current (RMS + DC)
500 Amp
Measurement Range
+/-1000 Amp
Overload Rating
Contact Us for Possible Replacement
Output
+/-4 V
Isolation
3 kV
Bandwidth
DC-10 kHz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
2%
Termination Style
Molex 5045-04A
Unit Weight
590g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM LES 25-NP, C/L Multi Range Hall Effect Current Sensor, 25 Amp, 2.5V ref in ref Out, PCB Mount, X = 2.25%, 4.3kV Isolation
Features
Closed loop current transducer
Voltage output
4.3kV Isolation
Frequency bandwidth 300kHz
Single supply + 5 V
Galvanic isolation between primary and secondary
Low power consumption
Compact design for PCB mounting
Vref IN Vref OUT
Multirange through PCB routing
Advantages
LTS footprint compatible
Zero insertion losses
Very good linearity
Very good dv/dt immunity
High immunity to external interference
Current overload capability
Optimised response time
Applications
AC variable speed and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Solar inverters
Standards
IEC 61800-1: 1997
IEC 61800-2: 2015
IEC 61800-3: 2004
IEC 61800-5-1: 2007
IEC 62109-1: 2010
IEC 62477-1: 2012
UL 508:2013.
Application Domain
Industrial
Specification
LEM Part Number
LES 25-NP
Technology
Closed Loop Multirange Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
5 VDC
Load Current (RMS + DC)
15 Amp
Measurement Range
+/-51 Amp
Output
2.5 Vref
Isolation
4.3 kV
Bandwidth
DC-300 kHz
Mounting Style
PCB Mount
Operating Temperature Range
-40°C / 105°C
Accuracy
2.25%
Termination Style
PCB
Unit Weight
10g
Factory Packaging
25
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Alternatives
LTS 15-NP
LH 100-P, C/L Hall Effect Current Sensor, 100 Amp, 50mA Output, PCB Mount, 5kV Isolation
Features
Bandwidth DC to 200kHz
Closed loop transducer using Hall effect
Compact and versatile
PCB Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Applications
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
LH 100-P
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-12..15 VDC Bipolar, Isolated
Load Current (RMS + DC)
100 Amp
Measurement Range
+/-175Amp
Output
50mA
Isolation
5 kV
Bandwidth
DC-200 kHz
Mounting Style
PCB Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
0.4%
Termination Style
Through Hole PCB
Unit Weight
20g
Factory Pack Quantity
25
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LH 25-NP, C/L Multi Range Hall Effect Current Sensor, 50 Amp, 25mA Output, PCB Mount, 5kV Isolation
Features
Bandwidth DC to 200kHz
Closed loop transducer using Hall effect
Compact and versatile
PCB Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Applications
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
LH 25-NP
Technology
Multi Range Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-12..15 VDC Bipolar, Isolated
Load Current (RMS + DC)
8,12,25 Amp via pinouts
Measurement Range
+/-55Amp
Output
25 mA
Isolation
5 kV
Bandwidth
DC-200 kHz
Mounting Style
PCB Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
0.4%
Termination Style
Through Hole PCB
Unit Weight
20g
Factory Pack Quantity
25
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM DVL 150 Digital Voltage Transducer, Vpn = 150V, 50mA output, +/-15...24VDC powered, 8.5kV Isolation
Features
Bandwidth DC to 14kHz
Digital Transducer (ASIC based)
Closed loop transducer using Hall effect
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVL 150
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-15..24 VDC Bipolar, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 150V
Measurement Range
+/- 225V
Output
50 mA @Vpn
Isolation
8.5 kV
Bandwidth
DC-14 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
270g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
RCS-1200 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1200 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-1200-3000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
3000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
RCS-1800-0500 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-0500
Specification
Magnelab Part Number
RCS-1800-0500
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
500 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 500 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
RCS-2400-1000 Three-Phase Flexible Current Sensor System(Rogowski Coils):
The RCS-2400 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-2400 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-2400-1000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
1000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
8 Inch
Coil Circumference
24 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide