Trent I^2t (aR) Blade Style Semiconductor Fuse 900Amp, 690VAC, Square Body, Size_Body Size 3, DIN 43 653, 200kA (78mm Hole Centers) F170M6013
Features
Square Body, Size_Body Size 3, DIN 43 653
Wide Range of I^2t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I^2t
Short Circuit Protection
DC or AC Motor I^2t Protection
Battery Fuse
Specification
Trent Part Number
F170M6013
Fuse Type
I^2t AR Class
Nominal Voltage
690VAC @ 50Hz
I^2t Rating (660V)
670000A^2/s
Nominal Current (RMS DC)
700 Amp
Tested Breaking Capacity
200kA (78mm Hole Centers) @ 690VAC
Dimensions
76 x 104 x 76mm
Hole Centers
78mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40DegC / 125DegC
Watts Dissipation
110W
Termination Style
M10
Unit Weight
700g
Factory Pack Qty
10
Datasheet
Product Datasheet
KW62-TT570N16KOF 1100 Amp RMS 130mm long Isolated Water Cooled SCR Module
Replacement to Semikron SKIW900/16
Nominal 1000 Amp RMS Output using TT500N16KOF
Nominal 1100 Amp RMS Output using MCC552-16
Comes with Brass inlet and outlet for hose, along with plug.
Pressure tested to 300 mbar
110 Deg C Normally Closed Thermal switch included
Specification
Thermal Rating based on 25 Deg C max inlet water temperature, and 50 Deg C max Ambient
Type No
Litres/min
Device
Rcw deg C/W
mbar
kg
Continous Current (rms)
KW62-TT570N16KOF
2
50 x 92
0.055
50
2.7kg
1050 Amp
4
50 x 92
0.042
190
1150 Amp
Datasheet
KW62 Datasheet
TT570N16KOF
Fastron Electronics GT-D-C-SP02, 0-150VDC Voltage Transducer, 22-60VAC/DC aux, 4-20mA output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-D-C-SP02
Control Output
4-20mA
Input
0 - 150VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22 - 60VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
RCS-1200-1000 0.333V, 3 Phase 1000Amp AC Measurement 4 Inch ⌀ Rogowski Coils with Integrator, Class 1 Flexible Current Sensor System:
The RCS-1200 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-1000
Specification
Magnelab Part Number
RCS-1200-1000
Function
AC Current Measurement
Nominal Measurement Current
1000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Varsi V130K14, 130VAC, 170VDC, K14 Axial Package, Lugged Series Metal Oxide Varistor (MOV)
High Energy Absorption Rating
Industry Standard Package
Wide Operating Range 35 - 1100VAC
High Peak Current Capability (70kA)
UL/CSA/ROHS/ISO9001:2015 Approved
Panel Mount
Screw Terminals
APPLICATION AREAS:
1. Railways and trams: For the protection of electrical equipment, power electronics (IGBT, thyristors...) in systems with alternating, direct or combined AC + DC power supply, especially in power supply of AC/DC, DC/AC, DC/DC converters. They may be used in systems with main and auxiliary power supply for example: automatic control and regulation systems, cooling systems, warming systems, ventilation systems, and combination systems (electromechanical, electropneumatic and other systems).
2. Wind powerplants For protection of automatic control and regulation in power electronics (IGTB, tyristors...), as well as the protection of sensitive electronic systems (e. g. AC/DC, DC/AC, DC/DC converters, drive systems) from direct or indirect lightning strikes.
3. Photovoltaic systems For protection of photopanels, automatic control electronics with sensitive electronic components, and DC/AC converters (inverters) from direct or indirect lightning strikes. Depending on the application, both serial and parallel connections are possible. With serial connection the required voltage is achieved. With parallel connection higher current absorption is achieved in the modules.
Specification
Varsi Part Number
V150K14
Operating Voltage AC (50-60Hz)
150V
Operating Voltage DC
200V
Average Power Dissipation
0.6W
Permissable Peak Current
5.5kA
Energy Absorption(2ms)
50W(max)
Tolerance(Vn)
+/- 10%
Termination Style
Ring Lug
Weight
7g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CSA
Yes
Datasheet
Product Datasheet
Application Notes
Technical Blog MOV Article
Trent MYG20-241 Series Metal Oxide Varistor (MOV), Varistor, 200VAC, 240VDC, K20 Axial Package 60W, Lugged
High Energy Absorption Rating
Industry Standard Package
Wide Operating Range 35 - 1100VAC
High Peak Current Capability (70kA)
UL/CSA/ROHS/ISO9001:2015 Approved
Panel Mount
Screw Terminals
APPLICATION AREAS:
1. Railways and trams: For the protection of electrical equipment, power electronics (IGBT, thyristors...) in systems with alternating, direct or combined AC + DC power supply, especially in power supply of AC/DC, DC/AC, DC/DC converters. They may be used in systems with main and auxiliary power supply for example: automatic control and regulation systems, cooling systems, warming systems, ventilation systems, and combination systems (electromechanical, electropneumatic and other systems).
2. Wind powerplants For protection of automatic control and regulation in power electronics (IGTB, tyristors...), as well as the protection of sensitive electronic systems (e. g. AC/DC, DC/AC, DC/DC converters, drive systems) from direct or indirect lightning strikes.
3. Photovoltaic systems For protection of photopanels, automatic control electronics with sensitive electronic components, and DC/AC converters (inverters) from direct or indirect lightning strikes. Depending on the application, both serial and parallel connections are possible. With serial connection the required voltage is achieved. With parallel connection higher current absorption is achieved in the modules.
Specification
Trent Part Number
MYG20-241
Operating Voltage AC (50-60Hz)
200V
Operating Voltage DC
240V
Average Power Dissipation
1W
Permissable Peak Current
10kA
Energy Absorption(2ms)
127W(max)
Tolerance(Vn)
+/- 10%
Termination Style
Axial Lead
Weight
3g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CSA
Yes
Datasheet
Product Datasheet
Application Notes
Technical Blog MOV Article
D5251255TER0000 Power Factor Correction Capacitor, 3 Phase, Dry Type DWCAP 12.5 KVAR, 525V, 50HZ, 100 x 230mm
Characteristics and utility
12.5 kVar @ 525V @ 50 Hz 12.5.0kvar 12.5kvar
Three phase capacitor DUAL WINDING internally delta connected
Discharge resistors Incorporated
Reactive power factor correction
Dry type
Connector type - single sided terminal
Indoor mounting
True triple safety
Overpressure disconnection system
Protection by internal fuses
DWCAP system (patented) internal windings Displacement
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Polyurethane self-extinguishing resin V0, developed under standard UL 94 by RTR Energía
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
RTR Energia Part Number
D5251255TER0000
Technology
Dry Type, Low Loss, Self Healing
Dimensions
100 x 230mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
525V @ 50Hz
Kvar
12.5 Kvar
Capacitance
3 x 48.12uF
Tolerance On Capacitance
-5% + 10%
Current (In)
13.75 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
DWCAP system (Patented) internal windings Displacement
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Unit Weight
1.5kg
Factory Pack Quantity
25
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Voltage Derating Tables
D5252505TER0000 Power Factor Correction Capacitor, 3 Phase, Dry Type DWCAP 25.0 KVAR, 525V, 50HZ, 120 x 230mm
Characteristics and utility
25 kVar @ 525V @ 50 Hz 25.0kvar 25kvar
Three phase capacitor DUAL WINDING internally delta connected
Discharge resistors Incorporated
Reactive power factor correction
Dry type
Connector type - single sided terminal
Indoor mounting
True triple safety
Overpressure disconnection system
Protection by internal fuses
DWCAP system (patented) internal windings Displacement
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Polyurethane self-extinguishing resin V0, developed under standard UL 94 by RTR Energía
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
RTR Energia Part Number
D5252505TER0000
Technology
Dry Type, Low Loss, Self Healing
Dimensions
120 x 230mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
525V @ 50Hz
Kvar
25.0 Kvar
Capacitance
3 x 96.24uF
Tolerance On Capacitance
-5% + 10%
Current (In)
27.49 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
DWCAP system (Patented) internal windings Displacement
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Unit Weight
3.1kg
Factory Pack Quantity
25
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Voltage Derating Tables
D5254005TER0000 Power Factor Correction Capacitor, 3 Phase, Dry Type DWCAP 40.0 KVAR, 525V, 50HZ, 136 x 230mm
Characteristics and utility
40kVar @ 525V @ 50 Hz / 25kVar @ 400VAC
Three phase capacitor DUAL WINDING internally delta connected
Discharge resistors Incorporated
Reactive power factor correction
Dry type
Connector type - single sided terminal
Indoor mounting
True Triple safety
Overpressure disconnection system
Protection by internal fuses
DWCAP system (patented) internal windings Displacement
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Polyurethane self-extinguishing resin V0, developed under standard UL 94 by RTR Energía
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
RTR Energia Part Number
D5254005TER0000
Technology
Dry Type, Low Loss, Self Healing
Dimensions
136 x 230mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
525V @ 50Hz
Kvar
40.0 Kvar
Capacitance
Tolerance On Capacitance
-5% + 10%
Current
44 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
DWCAP system (Patented) internal windings Displacement
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Unit Weight
4.9kg
Factory Pack Quantity
25
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Voltage Derating Tables
LEM AHR 1500 B420, AHR 1500 B420, Hall Effect Current Sensor, 1500Amp, True RMS 4-20mA output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 1500 B420
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
1500 Amp
Maximum Measurement Current (Peak)
2500 Amp
Output
4-20mA
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AHR 800 B10, Hall Effect Current Sensor, 800Amp, True RMS 0-10V output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
0-10V voltage output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 800 B10
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
800 Amp
Maximum Measurement Current (Peak)
2500 Amp
Output
0-10V
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition