Fastron Electronics SCT-F24-100-40mA, 40mA, 100Amp measurement Split Core CT's, Class 1 Series Current Transformer
Features
Quick Release Split Core System
Cable Mount
40mA Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-100-40mA
Technology
Split Core AC Current Transformer
Ratio
100/.40 Amp
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
40mAmp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F24-200-0.2V, 200mV, 200Amp Measurement Class 1 Split Core CT's for Power Quality Analysers 1mV/Amp
Features
Quick Release Split Core System
Cable Mount
200mV Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-200-0.2V
Technology
Split Core AC Current Transformer
Ratio
200/200mV
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
200mV (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
200Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F50-600, 0.333V, 600Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-600
Technology
Split Core AC Current Transformer
Ratio
600/0.333V
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
600Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
600g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
FP063080P, 630/5 Amp Split Core CT, Class 1 3VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FP063080P
Technology
Split Core AC Clip On Current Transformer
Ratio
630/5
Aperture Size
50 x 80mm
VA Rating
3VA
Accuracy Class
Class 1
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
630Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Datasheet
Product Datasheet
Installation Guide
Fastron Electronics FESCTHY-3000-2500, 2500Amp 100mV Class 1 Measurement Split Core CT's, 1M Flying Leads, 76x127mm Aperture
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Electronics Part Number
FESCTHY-3000-2500
Technology
Split Core AC Current Transformer
Ratio
2500/100mV
Aperture Size
76x127mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mVAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
2500Amp x 1.2
Termination Style
Terminals
Unit Weight
3000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Installation Guide
FESCTHY Install Guide
Fastron Electronics FESCTHY-3000-3000, 3000Amp 100mV Class 1 Measurement Split Core CT's, 1M Flying Leads, 76x127mm Aperture
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Electronics Part Number
FESCTHY-3000-3000
Technology
Split Core AC Current Transformer
Ratio
3000/100mV
Aperture Size
76x127mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mVAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
3000Amp x 1.2
Termination Style
Terminals
Unit Weight
3000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Installation Guide
FESCTHY Install Guide
FWLS-T1190N1600-SP02 Semiconductor Assembly, Water Cooled, Standard Water Cooler, 1600VAC, 2000Amp RMS Continuous, 12mm x 13.7mm Nipples
1000 Amp RMS Output using T430N16KOF
1600 Amp RMS Output using T720N16KOF
2000 Amp RMS Output using T1190N16KOF
Brass inlets and outlets for hose, along with plug.
Pressure Tested to 300 mbar
Specification
Thermal Rating based on 40°C max inlet water temperature.
Type No
Litres/min
Device
Rck deg C/W
mbar
kg
FWLS-1190N1600 (Replaces FWLS-T1050N1600)
4
T430N16KOF
0.10
190
3.5kg
4
T720N16KOF
0.08
190
4
T1190N16KOF
0.08
190
Type No
Maximum Junction Temp
Itsm
RMS Current
Vvrm
Dimensions
FWLS-1190N1600 (Replaces FWLS-T1050N1600)
125 Deg C
25500 A²/s
2000 Amp
1700V
196x227x110mm
Datasheet
Product Datasheet
Drawing
Magnelab SCT-0400-050, 50 Amp, 0.333v Class 1 Series Current Transformer, 10mm Aperture, UL approved
Features
Quick Release Split Core System
Cable Mount
0.333v Output
Self Powered
Rated System Voltage 0.60/3kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Magnelab Part Number
SCT-0400-050
Technology
Split Core AC Current Transformer
Ratio
50/0.333v
Aperture Size
ø 10 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333v (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
50Amp x 1.2
Termination Style
0.5M Flying Leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
RCS-2405-VAR, 5 Amp Output, Class 1 Three Phase 500/1000/2500/5000\10000\25000\50000 Amp AC Measurement 8 Inch Diameter Rogowski Coils with Integrator Flexible Current Sensor System (Rogowski Coils):
The RCS-2405 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 5 Amp.
A 24VDC Power Supply is included to operate these coils. The RCS-2405 comes with 5 Amp integrator..
Included is an 24 inch circumference rope CT with Integrator, and power supply.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-2405-VAR
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
500/1000/2500/5000\10000\25000\50000 Amp RMS Selectable
Measurement Range
10% - 130% if Ipn
Output Range
0-5 Amp
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
24VDC
Accuracy
1% from 25 to 5000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
8 Inch
Coil Circumference
24 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
2500g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS-VAR Series Installation Guide
RCS-3600-2000 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-3600 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-3600 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-3600-2000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
2000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 2000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
12 Inch
Coil Circumference
36 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Rishabh CT 400/5 Class 1 20VA 86/40 (45), Current Transformer 400/5Amp CT 20VA, Class 1 HIGH BURDEN
Features
DIN Rail Mounting Clip Included
Built In Sealable Terminal Covers
Mounting Feet Supplied
Narrow Width (45mm)
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Rishabh Part Number
CT 400/5 Class 1 20VA 86/40 (45)
Technology
AC Current Transformer
Ratio
400/5
Aperture Size
36mm or 11x41mm Busbar
VA Rating
20VA
Accuracy Class
Class 1
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Din Rail Moun
Operating Temperature Range
-30°C / 85°C
Continuous Current (max)
400Amp x 1.2
Termination Style
Screw
Unit Weight
300g
Factory Pack Qty
9
Datasheet
Product Datasheet
Rishabh 3PH105-21(40) 125, Class 1, 1.5VA 125 Amp, 5 Amp Output, 3 Phase Current Transformer, Panel Mount, Busbar Mount
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Rishabh Part Number
3PH105-21(40) 125
Technology
AC Current Transformer
Ratio
125/5
Aperture Size
20 x 24mm
VA Rating
1.5VA
Accuracy Class
Class 1
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-30°C / 85°C
Continuous Current (max)
125Amp x 1.2
Termination Style
Screw
Unit Weight
1000g
Factory Pack Qty
9
Datasheet
Product Datasheet