Fastron Electronics GT-DVO(0-30V)D-1, Signal Isolator/DC Voltage Transducer, 0-30VDC input, 22-60VAC/DC aux, 4-20mA output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GT-DVO(0-30V)D-1
Control Output
4-20mA
Input
0-30V
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Eastron Smart X96-5-MID, Panel Mount Multifuction Meter, Class 1, 173-480VAC, 1A/5A CT input, 30 Parameter, 2 x Digital Pulse/Alarm Outputs, Modbus RTU RS485 Comms, Self Powered, MID Approved
Metering and Numerical Display
Adjustable tariff clock (Optional 4 Tarriffs), display of electric energy consumption in optional currency
Modbus RTU as standard
True RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 30 quantities (U, I, P, THD, IHD, S, PF, PA, f, f, MD, etc.).
Accuracy class 1
Optional 2 or 4 tariff inputs,
Digital Output and Input
Ethernet communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD with Dual Metering and PF Displays
Specification
Eastron Part Number
Smart X96-5-MID
Functions
Power Quality Meter, Energy Meter
Aux Supply
Through Measurement Inputs
Nominal Measurement Range
173-480V L-N, 1/5 Amp
Maximum Measurement Range
280V L-N, 1/5 Amp
Pulse Outputs
2 x Digital Outputs (shared with Alarm function)
Alarm
2 x Digital Outputs (shared with Pulse function)
Tariff Input
1 (Optional 4 x )
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
2.5kV (1 Min)
RS485
2400-38400 b/s
Weight
500g
Certification
MID, UL
Factory Pack Qty
1
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Operating Temperature
-25 →+55 °C
Datasheet
Product Datasheet
User Manual
Modbus Registers
FPT-135 750/1A 5P35 5VA Protection Class CT, 750/1A, Class 5P35 5VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 750/1A 5P35 5VA
Technology
Protection Class Current Transformer
Ratio
750/5
Aperture Size
81 x 135mm
VA Rating
5VA
Accuracy Class
Class 5P35
Output
5 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
750Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
Fastron Electronics Fast ONE Complete AHF 300A-400V, Active Harmonic Filter & Static Var Generator, 300 Amp @ 45 Deg C, 3 Phase 3 Wire, 400VAC +/-20%, L:950 x W:950 x H:2200mm
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions. and for the filtering or control of Harmonic Distortion
Features
Automatic Power Factor Correction up to Cos φ = 0.99
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Modular Construction for Rack or Wall Mount Installations
Perfect for Residential Applications
Stack multiple modules for larger Power Factor Correction Requirements
Specification
Fastron Part Number
Fast ONE Complete AHF 300A-400V,
Function
Reactive Power Correction & Active Harmonic Filter
Configuration
3 x 100 Amp / 70kvar Modules
Current /Load Rating
300 Amp per Phase (270 Amp @ 55 Deg C) /210Kvar
Nominal Voltage (Un)
400VAC Line to Line 50Hz +/-20%
Switch Delay Time
Instant Correction/Inverter Based
Desired Harmonic
0.99 IND - 0.99 CAP
LCD Display
IGBT Temp, Grid Current Grid THDi, Grid PF, Grid Imbalance
Current imbalance
< 5%
Comms
RS485 (Optional)
Termination Style
Screw
Dimensions
L:950 x W:950 x H:2200mm
Weight
460kg
Certification
EN 61000-6-4:2007+A1:2011
EN 61000-6-2:2005
EN 61000-3-2:2014
EN 61000-3-3:2013+A1:2019
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
AHF Module Datasheet
Complete with Enclosure Datasheet
User Manual
Secure Elite E500C-5202, Panel Mount Network Recorder with Harmonics (15th) & PQ Parameters, Class 0.5S, 50..500VAC 50/60Hz, RS485 Modbus RTU, 35..300V DC/85..300VAC Aux, 16MB Dual Logger , TFT Touch Screen, 10 Years Warranty
Automatic range of nominal current up to 6 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-L, 300V L-N
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
Dual Loggers, configurable for Instant or accumulated energy
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
RS 485 communication up to 38400 bit/s as standard
Optional Protocol Modules Modbus TCP, BACNet IP, Profinet, SCADA EC61850
Optional Modules for Analogue outputs and Relay Alarms
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values and accumulated energy. Includes Harmonics to the 15th
Accuracy class 0.5S
Dual Internal Loggers
Measurement of 20 minimal and maximal values in different time periods
RS 232/RS 485 communication up to 38400 bit/s or Ethernet communication
MODBUS communication protocol
Optional Protocol Modules Modbus TCP, BACNet IP, Profinet, SCADA EC61850
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
Universal or AC/DC power supply
Graphic Colour TFT 320 x 240 pixels (53x70mm)
Automatic range of nominal current up to 6 A and nominal voltage up to 500 V
Multilingual support
User-friendly Free ECon Configuration software
Specification
Secure Part Number
E500C-5202
Functions
Power Quality Meter(15th Hamonic), Energy Meter, Network Recorder
Supply Voltage
Universal 35..300V DC, 85..300VAC
Nominal Measurement Range
240V L-N, 1/5 Amp, 415V L-L 1/5 Amp
Maximum Measurement Range
300V L-N, 1/5 Amp, 500V L-L 1/5 Amp
Alarm
Optional Module 2 Relay/Pulse Outputs
Tariff/Digital Inputs
TOU Tarriff Clock
Accuracy
Class 0.5S (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Analogue Output
Optional Module 2 x Programmable Analogue Outputs
Internal Memory
2 x 8MB
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS232/RS485
N/A Optional
CT Termination
Ring Terminals
Weight
600g
Certification
CE, CSA, ROHS
Warranty
10 Years from dispatch from Secure Warehouse
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Cross Reference
The Following meters are close equivalents to Elite 500 Series. For further details please contact Fastron Sales Team
Elite 500_400_300_100 series competition replacement for
Schneider
Siemens
Accuenergy (RS485 +DNP3 default)
Socomec
Selec
PM 5000 series
PAC 2000 series
ACCUVIM-CL + DNP3.0
DIRIS A-20
Selec MFM376
PM 5100
PAC 3200
ACCUVIM-CL + DNP3.0
DIRIS A-20
MFM384, CL-1, RS485
PM 5300
ACCUVIM-IIR
DIRIS A-20
MFM383A
PM 5500
PAC 4200
ACCUVIM-IIR(+ BACnet)
DIRIS A-20
MFM384. RS485
PM 6463
Siemens 7KMPAC4200
ACCUVIM-IIR (+ Profibus)
DIRIS A-30/ DIRIS - A60 (PQ Feature)
MFM384-C-CE-CL05, RS485
PM 5650
ACCUVIM-IIR (+ IEC 61850)
DIRIS A-30 + Profibus
MFM384-C-CE-CL05, RS485
PM 5760
ACCUVIM-EL
DIRIS A-30 +Ethernet
MFM384-C-CE-CL05, RS485
PM5330
ACCUVIM-EL (+ BACnet)
DIRIS A-30/ DIRIS A-60
PM 5560
ACCUVIM-EL (+ Profibus)
DIRIS A-30/ DIRIS A-60
DM6200H
ACCUVIM-EL (+ IEC 61850)
PM2220
ACCUVIM-II R +Ethernet
PM2230 / DM2120 (LED)
PM 5350
RODNV624010, Steel Teclom Enclosure IP55, AIR COOLED 578M3/h, RAL 7035 Gray, 2.0mm Galvanised Steel, Thermostat and Fan Pre-installed
Features
Thermostat Controlled Dual Fans for 578m3/h maximum flow rate
Lockable Door via Key
Stack multiple modules for larger Power Factor Correction Requirements
Optional HMI IP55 Door with Window RODNV624010
Specification
Fastron Part Number
RODNV624010
Function
Steel Water Proof Enclosure AIR COOLED
Configuration
Enclosure with Hinged Door, Key Lock and Fan and Thermostat
Air Flow Rate
578m3/h
Termination Style
Screw
Dimensions
L:950 x W:950 x H:1200mm
Weight
70kg
Certification
AS 3000
AS 3100
Factory Pack Qty
1
Material of housing
2.0mm Galvanised Steel Painted RAL 7035
Enclosure protection
IP55
Operating Temperature
-20...55 °C
Datasheet
Datasheet
Shinko PCA1R10010 Series Digital Indicating Controllers
Program control, Fixed Point Control function are standard features
5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Time Signal Output
Drip-proof / Dust-proof IP66 (front panel only)
16-step, 16 Patterns with Interlinking pattern is a standard feature
UL/CSA Approved
Each unit needs just 60 mm depth panel space
EC Compliant (Details)
Applications
Kiln Controller
Timed Heatsink Process
Food Industry
Oven Controller
Furnace Controller
Specification
Shinko Part Number
PCA1R10010
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Number of Steps
16
Number of Patterns
16
Interlinkable
Yes
Input
Multirange (refer to datasheet)
Option 1
4-20mA Retransmission Output
Option 2
None
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
24VAC/DC
Termination Style
Screw
Weight
270g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
PCA Series Brochure
PCA Series User Manual
Shinko Product Guide
Fine Tuning Adjustments
Eastron SDM630MCT-4L, Quad 3 Phase DIN Rail Mount kWh Meter with Easyclick, 4 x 3 Phase or 12 x Single Phase, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 4 x 3 Phase Connect
100mA RJ12 12 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 2 x three phase or 6 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-4L
Functions
Quad Three Phase Energy Meter/ 12 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
System Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
700g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Premium Quality TC Cable 500M Teflon - Type R Thermocouple Cable 500 Meter Twisted and Screened 7/0.2mm, ANSI Standard
Features
CE, ANSI, ROHS Approved
Colour Codes
Datasheet
Thermocouple Cable Brochure
Fastron H31/110M + FTH2553ZD3, 3 Phase Solid State Relay, with Heatsink, IP20 Cover, Panel Mount, 25 Amps Per Phase @ 50 Deg C, 530VAC Load, with IP20 Cover
Ratings from 25 to 120 Amp @ 70-480 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
IP20 Cover Included
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Includes IP20 Cover
Specification
Fastron Part Number
H31/110M + FTH2553ZD3
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
3-32VDC
Load Current
3 x 25 Amp (rms) @ 50 Deg C
Surge Capability
350 Amp (peak)
Special Feature
LED Status Indicator, with IP20 Cover
Mounting Style
Panel Mount
Load Voltage Range
70-530VAC
Dimensions
L:110 x W:125 x D:180mm
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
2kg
Factory Pack Qty
10
Datasheet
Product Datasheet
H31 Datasheet
Equivalent Parts
Contact Us for Possible Replacement
Fastron Electronics FESCT-055-500-1-IP65, 500Amp Measurement, 1 Amp Output Split Core CT's, Class 1, w/10M Flying leads, ø 55mm Aperture
Features
Quick Release Split Core System
10m Flying Leads
ø 55mm
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurement, 1 Amp Outputs
Specification
Fastron Electronics Part Number
FESCT-055-500-1-IP65
Technology
Split Core AC Current Transformer
Ratio
500/5A
Aperture Size
ø 55mm
VA Rating
2.5VA
Accuracy Class
Class 1
Output
1 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Dimensions
180x138x52mm
Mounting Style
Panel Mount
Operating Temperature Range
-35°C / 55°C
Continuous Current (max)
500Amp x 1.2
Termination Style
10M Twisted Pair 0.34mm^2
Unit Weight
2000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide