Fast ONE AHF 75A-400V, Active Harmonic Filter & Static Var Generator, 50Kvar/75 Amp, 3 Phase + N, 400VAC +/-20%, WALL MOUNT
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions. and for the filtering or control of Harmonic Distortion
Features
Automatic Power Factor Correction up to Cos φ = 0.99
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Modular Construction for Rack or Wall Mount Installations
Perfect for Residential Applications
Stack multiple modules for larger Power Factor Correction Requirements
Specification
Fastron Part Number
Fast ONE AHF 75A-400V-4W
Function
Reactive Power Correction & Active Harmonic Filter
Current /Load Rating
75 Amp per Phase /50Kvar
Nominal Voltage (Un)
400VAC Line to Line 50Hz
Switch Delay Time
Instant Correction/Inverter Based
Desired Harmonic
0.99 IND - 0.99 CAP
LCD Display Accuracy
IGBT Temp, Grid Current Grid THDi, Grid PF, Grid Imbalance
Current imbalance
< 5%
Comms
RS485 (Optional)
Mounting Style
Wall Mount
Termination Style
Screw
Dimensions
486x183x550mm
Weight
50kg
Certification
EN 61000-6-4:2007+A1:2011
EN 61000-6-2:2005
EN 61000-3-2:2014
EN 61000-3-3:2013+A1:2019
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Datasheet
User Manual
Northern Design Multicube Modular Master Single and 3 Phase Power Meter with Logger and Modbus TCP/IP Comms, NEW WEB PAGE VERSION
Up to 20 Meters in 1 with additional modules
Minimum 2 x 3 Phase Circuits with measurement module
Master Unit of Modular Multicube System
Optional 12 way pulse/alarm digital output modules
Nominal current up to 0.383V (For 0.333V CT Input) and nominal voltage up to 240V L-N 415V L-L
Graphic Display
Optional RS485 or Ethernet communication up to 19,200 bit/s
True RMS measurement of currents and voltages
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, reactive power, power factor, harmonics, etc.) from the measured signals.
Features :
20 Meters in same space as 4 traditional meters
Expandable to 20 x 3 Phase or 60 x Single Phase Circuits
Accuracy class 1
In Built Logger
Simple Menu
Optional MODBUS TCP/IP/Ethernet communication
5 Year Warranty
240V AC power supply
Specification
Northern Design Part Number
Multicube Modular Master with Logger and TCP/IP
Functions
kWh Meter, Energy Meter, Power Quality, Network Recorder
Supply Voltage
240VAC < 15VA
Nominal Measurement Range
415V L-L 240V L-N, 0.333V
Maximum Measurement Range
480V L-L 280V L-N, 0.383V
Display
Graphic LCD
Pulse Output
12 (Optional)
Accuracy
Class 1 (kW,kWh) Class 1(Active), Class 2 Reactive
Ethernet
Yes
Logger
Yes
Isolation
2.11kV
RS232/RS485
Modbus TCP/IP
Weight
900g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
ABS with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
164 x 96mm x 100mm
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product brochure
User manual
Wiring Diagram
Suitable 0.333V CT's
Split Core CT's
Gigavac PNC113BDA, Contactor SPST-NC, 50 AMP, 1200VDC, 12VDC Coil, M3 Coil Screw Terminals, M4 Power Terminals
Features
Perfect for Capacitor Discharge or Dump Switch Applications
Hermetically Sealed (Patented) rated to 175 Deg C
High Efficiency Dual DC Coils - 12,24,48VDC options
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Small and lightweight
Flexible package for installation
CE Approved
Specification
Gigavac Part Number
PNC113BDA
Main Contact Type
SPST-NC
Auxiliary Contact Type
N/A
Coil Voltage
12VDC
Load Current
50 Amp
Mechanical Life @ 0 Amp
50,000 Operations
Impulse Withstand
6kV rms
Control Input Terminals
M3 Screw
Special Feature
N/A
Mounting Style
Panel Mount (M4)
Load Voltage Range
1500VDC
Standards
CE Approved
Termination Style
M4 Screw
Unit Weight
135g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics FTD-420-420-24, Signal Isolator/Conditioner, 4-20mA Input, 4-20mA Output, 24VDC
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted from 4 to 20 mA DC Loop Supply (Sensor Input) to insulated 4-20mA Standard Process Output
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
FTD-420-420-24
Control Output
4-20mA
Input
4-20mA
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
24VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
LEM HAZ 10000-SB, O/L Current Transducer, 10000 Amp, +/-15VDC supply, +/-10V Output
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
Features
Instantaneous output version +/-10V, +/-20mA
True RMS output versions 4-20mA, 0-10V putput
Hall effect measuring principle
Galvanic isolation between primary and secondary circuit
Instantaneous voltage output
Isolation voltage 17kV Rms /50 Hz /1min
Low power consumption
Package in PBT meeting UL 94-V0
Instantaneous voltage output
Advantages
Easy installation
Small size and space savings
Only one design for wide Ratings range
High immunity against external interference
Applications
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Power supplies for welding and telecom applications
Application domain
Industrial
Traction
Specification
LEM Part Number
HAZ 12000-SB
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
+/- 15VDC
Load Current (RMS + DC)
10000 Amp
Overload Rating
30000 At
Output
+/-10 V Instantaneous
Isolation
17kV (AC, 50Hz, 1 min)
Bandwidth
DC-3kHz
Mounting Style
Busbar Mount
Operating Temperature Range
-25°C / 85°C
Accuracy
1%
Termination Style
F2023A (FUJICON)
Unit Weight
6kg
Factory Pack Qty
2
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Fastron Electronics GT-LL2-D-4, Signal Transmitter/Conditioner, Load Cell, 2mV/V EX.5V input, 0-10V output, 22-60VAC/DC supply
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GT-LL2-D-4
Control Output
0-10V
Input
2mV/V EX.5V
Over Range
N/A
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
ART-B22-D70-SP3 + AI-P1A- 3 Pcs, 3 Phase Rogowski Coils & Universal Multi Range Integrator with Signal Conditioner
The universal Rogowski coil integrator AI-P1A complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-P1A is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
1 Amp instantaneous output.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Included Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D70-SP3 + AI-P1A- 3 Pcs
Function
3 Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
1 Amp output
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 7cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-P1A Datasheet
ART Series Datasheet
Applicaton Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Fastron Electronics GTD-T/TO(0-150)/A1 PT100 to 4-20mA Signal Conditioner or Transmitter
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-T/TO(0-150)/A1(0-20mA)
Control Output
4-20mA
Input
RTD (Pt100)
Over Range
N/A
Operating Temperature
0 - 60°C
Load Voltage
100 - 240VAC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
LEM DVL 500 Digital Voltage Transducer, Vpn = 500V, 50mA output, +/-15...24VDC powered, 8.5kV Isolation
Features
Bandwidth DC to 14kHz
Digital Transducer (ASIC based)
Closed loop transducer using Hall effect
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVL 500
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-15..24 VDC Bipolar, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 500V
Measurement Range
+/- 750V
Output
50 mA @Vpn
Isolation
8.5 kV
Bandwidth
DC-14 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
270g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Techsem MDC182-25-216F3, 182 Amp, 2500V, Dual Diode Module
Features
Pressure Contact Technology
Electrically insulated base plate
Improved temperature and power cycling
Planar passivated chips
Very low forward voltage drop
Very low leakage current
3600V Isolation
Industrial standard package
20mm Base Width
Applications
Power Supplies
Rectifier for drives applications
Uncontrolled Rectifiers
Rectifiers for UPS
Battery Chargers
For single and three phase bridge configurations
Field supply for DC motors
Input rectifiers for PWM inverter
Specification
Techsem Part Number
MDC182-25-216F3
Vrrm
2500V
Diode Configuration
Single Diode Module
IF(av) @ 85 Deg C
181 Amp
Package Size
TO-240AA W:20mm L:93mm D:30mm
Itsm
6.4 kA
VF(to)
0.85V
Tj(max)
150°C
rF
1.05mΩ
Terminals
M5 Screw
Hole Centres
80mm (M6)
Gate Trigger Current
N/A
R th(j-c)
0.20°C/W
R th(c-h)
0.08°C/W
Weight
320g
Mounting Torque
2.5 Nm (5 Nm Terminals)
Factory Pack Qty
10
Certification
UL Listed, ROHS
Techsem Headquarters
China
Datasheet
Product Datasheet
Fastron Electronics GTD-V4-A-44, Signal Conditioner/Voltage Transducer, 0-10VDC input, 100-240VAC/DC aux, Dual 0-10VDC outputs
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-V4-A-44
Conditioned Output
2 x 0-10V
Input
0-10V
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Gigavac P195FDA, MiniTactor Contactor SPST-NO, 80 AMP, 1200VDC, 48VDC Coil, M3 Coil Screw Terminals, M4 Power Terminals
Features
Perfect for Photovoltaic/Battery Systems
Hermetically Sealed (Patented) rated to 175 Deg C
High Efficiency Dual DC Coils - 12,24,48VDC options
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Small and lightweight
Flexible package for installation
Chassi level power terminals
Specification
Gigavac Part Number
P195FDA
Main Contact Type
SPST-NO
Auxiliary Contact Type
N/A
Coil Voltage
48VDC
Load Current
80 Amp
Mechanical Life @ 0 Amp
100,000 Operations
Dielectric at Sea Level
4.3kV rms
Control Input Terminals
M3 Screw
Special Feature
N/A
Mounting Style
Panel Mount (M4)
Load Voltage Range
1200VDC
Standards
UL508, NEC 690.11 and 690.12 DC
Termination Style
M4 Screw
Unit Weight
135g
Factory Pack Qty
1
Datasheet
Product Datasheet