Fast ONE AHF 100A-400V-4W-R, Rack Mounted Active Harmonic Filter & Static Var Generator, 70Kvar/100 Amp, 3 Phase 4 Wire, 400V-4Wire +/-20%
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions. and for the filtering or control of Harmonic Distortion
Features
Automatic Power Factor Correction up to Cos φ = 0.99
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Modular Construction for Rack or Wall Mount Installations
Perfect for Residential Applications
Stack multiple modules for larger Power Factor Correction Requirements
Specification
Fastron Part Number
Fast ONE AHF 100A-400V-4W-R
Function
Reactive Power Correction & Rack Mounted Active Harmonic Filter
Current /Load Rating
100 Amp per Phase /70Kvar
Nominal Voltage (Un)
400V-4Wire Line to Line 50Hz
Switch Delay Time
Instant Correction/Inverter Based
Desired Harmonic
0.99 IND - 0.99 CAP
LCD Display Accuracy
IGBT Temp, Grid Current Grid THDi, Grid PF, Grid Imbalance
Current imbalance
< 5%
Comms
RS485 (Optional)
Mounting Style
Rack Mount
Termination Style
Screw
Dimensions
486x220x610mm
Weight
60kg
Certification
EN 61000-6-4:2007+A1:2011
EN 61000-6-2:2005
EN 61000-3-2:2014
EN 61000-3-3:2013+A1:2019
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Datasheet
User Manual
Fastron TC5-W-W-2-T/R-2 PID Controller, 100-240VAC with 2 3 Amp Relay Alarms, K,E,J Thermocouple, Pt100 or Cu20, Optional Linear Current/Voltage, 96x48mm,Relay + 12VDC Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Now available will full Multirange input (K,E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x48mm,4-20mA Output)
Specification
Fastron Part Number
TC5-W-W-2-T/R-2
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)/12VDC @ 20mA
Input
Multirange Type,K,E,J,Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
2 3 Amp Relay Alarms standard (Excludes 96x48mm with SSR/Relay output)
Mounting Style
96x48mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Safety
CE
Factory Pack Qty
10
Datasheet
TC5 Datasheet and User Manual
Fastron Electronics Fast ONE SVG 50kvar-400V-4W, 50kVar Static Var Generator(SVG)/Inverter for Reactive Power Correction, 3 Phase 4 Wire, Wall Mounted
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions.
Features
Automatic Power Factor Correction up to Cos φ = 0.99
Auto rotation of same capacitors for long life
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Modular Construction for Rack or Wall Mount Installtions
Perfect for Residential Applications
Stack multiple modules for larger Power Factor Correction Requirements
Specification
Fastron Part Number
Fast ONE SVG 50kvar-400V-4W
Mounting
Wall Mounted
Function
Reactive Power Correction
Configuration
4 Wire
Nominal Voltage (Un)
400VAC Line to Line 50Hz
Switch Delay Time
Instant Correction/Inverter Based
Desired Power Factor
0.99 IND - 0.99 CAP
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 (Optional)
Termination Style
Screw
Dimensions
540x278x540mm
Weight
34kg
Certification
EN 61000-6-4:2007+A1:2011
EN 61000-6-2:2005
EN 61000-3-2:2014
EN 61000-3-3:2013+A1:2019
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Datasheet
User Manual
Advanced Energy Thyro-A-3A-400-16-H-RL3, Three Phase SCR Controller 16 Amp 400VAC +10/-57%, Phase(VAR), Burst(TAKT) Fire, SWITCH Operating Modes, Voltage Control, Current Feedback Option
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustments
Synchronisation Function for Multiple TAKT Sync
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (VAR Mode Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro-A-3A-400-16-H-RL3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Three Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
TCD-L-2-PT COOLING Temp Controller, 96x96mm 230VAC, C/O Relay output, PT100 RTD Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-L-2-PT
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Pt100 RTD
Control Mode
Cooling ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
96x96mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
Fastron TC5-L-1A-2-T/R-2 PID Controller, 100-240VAC with 2 3 Amp Relay Alarms, K,E,J Thermocouple, Pt100 or Cu20, Optional Linear Current/Voltage, 96x96mm,4-20mA Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Now available will full Multirange input (K,E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x48mm,4-20mA Output)
Fastron Part Number
TC5-L-1A-2-T/R-2
Control Output
4-20mA
Input
Multirange Type,K,E,J, Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
2 3 Amp Relay Alarms standard (Excludes 96x96mm with SSR/Relay output)
Mounting Style
96x96mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Datasheet
TC5 Datasheet and User Manual
Fastron Electronics BTCD/A-M-A3-TA, PID Controller 96x96mm, 85-265VAC, 3 Alarms, Retransmission, Multirange TC/RTD/4-20mA Input
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP56 (front panel only)
CE Approved
Each unit needs just 80 mm depth panel space
Optional Pattern Control Feature
Specification
Fastron Part Number
BTCD/A-M-A2-DA-TA
Control Output
4-20mA
Input
Multirange 4-20mA/RTD/Thermocouple (other linear inputs to be specified at time of order)
Option 1
3rd Alarm
Option 2
4-20mA Retransmission
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
100-240VAC
Termination Style
Screw
Weight
600g
Factory Pack Qty
1
CE
Yes
Datasheet
BTC Series Brochure
BTC Series User Manual
BTC Series RS485 Comms Manual
Fine Tuning PID Adjustments
Crydom CWA4890P, Solid State Relay, Single Phase 90-280VAC Control, 90A, 48-660VAC Load w/ Overvoltage Varistor
Features
Ratings from 25A to 125 Amp @ 48-660VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
CWA4890P
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
24VAC (18-36VAC)
Load Current
90 Amp (rms)
Surge Capability
1350 Amp (peak)
Special Feature
LED Status Indicator, High Surge, MOV Overvoltage protection
Mounting Style
Panel Mount
Load Voltage Range
48-660VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Crouzet 88981136 Crouzet em4 Ethernet Nano PLC Starter Kit, 16 x Inputs, 2 (PWM), 8 (Relay) Outputs, 24 V ac/dc, Ethernet Comms, Includes Software UBS key, and Ethernet Cable
Includes software and Ethernet Cable
Up to 104 I/Os - 16 DI (4 High Speed / 8 AI)
10 x DO (2 x Solid State 0.5Amp PWM, 2 Relays 6 Amp, and 6 Relays 8 Amp)
Optional Wireless Programming & Control with native 3G and Crouzet Virtual Display
Optional Modbus RTU Network (Master/Slave)
Local datalog management
Up to 1000 programing blocks with intuitive Crouzet Soft to go from simple to complex applications
HMI Screens Available
Specification
Crouzet Part Number
88981136 (em4 Ethernet)
Analogue Inputs
12 x 0 - 10VDC, (4 High Speed)
Digital Inputs
24VAC/DC @ 2.1mA (8 Standard and 4 High Speed)
Digital Outputs
Relay, 12 or 24VAC/DC, 250VAC @ 100mA minimum (2 x 6 Amp, 6 x 8 Amp)
PWM SSR Output
2
Expandable
Yes
Comms
Ethernet (RS485, Bluetooth,3G,Standard) and Wifi versions available
LCD Display
Yes
Mounting Style
DIN Rail Mount (124.6mm)
Supply Voltage Range
24VAC/DC (21.6 - 28.8VAC)
Termination Style
Screw
Weight
350g
Environmental
Reach, RoHS, Halogen free 1272/2008/CE
Certification
CE, cULus Listed
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Software
Crouzet Touch Soft V6.00.02.173
Software M3-soft-AC9-V3.1.2.0_ML
Remote Control Software CVD_PC_V2_3_01_02
Crouzet Soft EVO EM4 1.12.01.14
TCD-M-3-PT HEATING Temp Controller, 72x72mm 230VAC, C/O Relay output, PT100 RTD Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-M-3-PT
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Pt100 RTD
Control Mode
Time Proportional Control
Control Range
0- 999 Deg C
Mounting Style
72x72mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
TCD-S-1-PT HEATING Temp Controller, 48x48mm 230VAC, C/O Relay output, PT100 RTD Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-S-1-PT
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Pt100 RTD
Control Mode
Heating ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
48x48mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual