Fastron Electronics SCT-F36-630-5A, 5 Amp, 630Amp Measurement, Class 1 Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F36-630-5A
Technology
Split Core AC Current Transformer
Ratio
630/5 Amp
Aperture Size
ø 35 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
630Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
400g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
AFP0RE16RS, Expansion for FP0R Series Progammable Logic Controller (PLC) 8 x On/Off inputs, 8 x Relay Outputs, 24VDC
Allow the expansion of outrouts for AFP0 Series , Expansion for Progammable Logic Controller (PLC) 8 x On/Off inputs, 8 x Relay Outputs, 24VDC.Â
Datasheet
Datasheet
Westcode-IXYS-Littlefuse B1815NC160, Thyristor(SCR) PUK, 1225Amp, 1600V, 74/26, Replaces N1802NC160
Features
Very low forward voltage drop
Very low leakage current
International standard package
74/26 Package
Press Mounted
Double or Single Sided Cooling
Applications
Power Supplies
Rectifier for drives applications
Uncontrolled Rectifiers
Rectifiers for UPS
Battery Chargers
Field Supply for DC Motors
Water Cooled Rectifiers
DC Substation Blocking Diode
Large Generators
Specification
Westcode-IXYS Part Number
B1815NC160
Vrrm
1600V
Diode Configuration
Thyristor Capsule (PUK)
IF(av) @ 60 Deg C
1225 Amp
Package Size
ø74 x 26mm
Itsm
29.6 kA
Tj(max)
125°C
Gate Terminals
Faston
Weight
510g
Factory Pack Qty
6
Certification
ROHS
IXYSÂ Headquarters
USA
Datasheet
Product Datasheet
Alternatives
T1190N16TOF VT
SKT1200/18E
N1718NC200
Contact Us for Possible Replacement
Heatsink
Heatsink Profiles
Â
Crydom DR24D06, Solid State Relay, 4-32VDC control, 6 Amp 24-280VAC Output, Slimline, Din Rail Mount, LED status Indicator
Features
Ratings from 3 Amp, 6 Amp, 12 Amp 1-100VDC, 1-60VDC, 24-280VAC, 48-600VAC
DIN Rail Mount
SCR output for reliable AC switching, or Mosfet for DC Switching
Ultra slim package
UL/CSA/VDE Approved, CE Compliant to EN60950-1
EMC compliant to Level 3
Epoxy free design
Spec
Crydom Part Number
DR24D06
Switching Type
DC
ROHS
Yes (Details)
Control Voltage
4-32VDC
Load Current
6 Amp (rms)
Surge Capability (10ms)
285 Amp (rms)
Special Feature
LED Status Indicator
Mounting Style
DIN Rail Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
50g
Factory Pack Qty
20
Â
Datasheet
Product Datasheet
Equivalent
Similar part
ks32-60-24z2-f41f-1z-c2-4Â
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
RCS-1800-3000 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-3000
Specification
Magnelab Part Number
RCS-1800-3000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
3000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Crydom DR24A06, Solid State Relay, 208-265VAC control, 6 Amp 24-280VAC Output, Slimline, Din Rail Mount, LED status Indicator
Features
Ratings from 3 Amp, 6 Amp, 12 Amp 1-100VDC, 1-60VDC, 24-280VAC, 48-600VAC
DIN Rail Mount
SCR output for reliable AC switching, or Mosfet for DC Switching
Ultra slim package
UL/CSA/VDE Approved, CE Compliant to EN60950-1
EMC compliant to Level 3
Epoxy free design
Spec
Crydom Part Number
DR24A06
Switching Type
AC
ROHS
Yes (Details)
Control Voltage
208-265VAC
Load Current
6 Amp (rms)
Surge Capability (10ms)
285Â Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
DIN Rail Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
50g
Factory Pack Qty
20
Â
Datasheet
Product Datasheet
Equivalent
Similar part
ks32-60-24z2-f41f-1z-c2-4Â
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics SCT-F36-400-5A, 5 Amp, 400Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F36-400-5A
Technology
Split Core AC Current Transformer
Ratio
400/5 Amp
Aperture Size
ø 35 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
400Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
400g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's