H-10-2-24, Split Core Hall Effect DC Current Transducer, 0-10 Amp DC, 4-20mA unipolar output, 31mm aperture, 24VDC supply
Compact and versatile Split Core DC current sensor, 0-10 Amp DC, 4-20mA Unipolar Output
Features
⌀31mm Aperture
Split Core
DC Unipolar Measurement
4-20mA analogue output
Busbar, or DIN Rail Mounting
Isolated plastic case recognised according to UL94-V0
Advantages
High isolation between primary and secondary circuits
Easy installation
DIN Rail Mount
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
Fastron Part Number
H-10-2-24
Technology
DC Hall Effect Current Transducer with Process Output
ROHS
Yes
Supply Voltage
24VDC
Nominal Current (DC)
0-10 Amp
Response Time
< 200mS
Output
Unipolar 4-20mA Analogue
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
DC
Mounting Style
DIN Rail Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Elevator Screw
Unit Weight
120g
Factory Pack Qty
6
Â
Datasheet
Product Datasheet
SDM630MCT-LORAWAN-MID-AS923, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 1, 1/5 Amp CT Connect, w/ 2 x pulse outputs and LoRaWaN AS923 Wireless Comms
1/5 Amp CT Input
LoRaWaN AS923
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
Â
The meter is intended for measuring, and monitoring single-phase or three phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Â
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-LORAWAN-MID-AS923
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
1/5 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
Comms
LoRaWaN AS923
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Â
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Modbus Utility
EEM Meter Setting Software Utility
Fastron FCR-400-120R-5V, Three Phase Proportional Phase Control Module, 4-20mA,0-5V Control input 400VAC, 120 Amp Per Phase, Voltage Regulator
4-20mA, or 0-5V Control Input
Ratings from 25A to 120 Amp @ 180-280 VAC
SCR output for heavy industrial loads
Instantaneous turn-on output
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Specification
Trent part Number
FCR-400-120R-5
Switching Type
Phase Angle (Random Crossing)
Control Voltage
4-20mA, 0-5V Proportional Inputs
Load Current
120 Amp (rms) @ 40 Deg C
Surge Capability
1100Amp (peak)
Special Feature
3 Phase Proportional Controller + SSR/3 Phase Voltage Regulator
Mounting Style
Panel Mount
Load Voltage Range
180-400VAC +10%
Max Non Repetitive Peak Voltage
600 Vp
Termination Style
Barrier Strip Screw
Dimensions
105 x 80 x 55mm
Unit Weight
400g
Factory Pack Qty
20
Â
Datasheet
FCR-400-120R
Powersem PSD35T/20 Single Phase Half Controlled Rectifier Bridge, Replaces Semikron SKD30/20
Features
Package with DCB ceramic base plate
Isolation voltage 3000 V∼
Planar glass passivated chips
Low forward voltage drop
Leads suitable for PC board soldering
UL registered, E 148688
Applications
Heat and temperature control for industrial furnaces and chemical processes
Lighting control
Motor control
Power converter
Advantages
Easy to mount with two screws
Space and weight savings
Improved temperature and power cycling capability
High power density
Specification
Powersem Part Number
PSD35T/20
AC Line voltage
680V
Device Configuration
Three Phase Diode Rectifier Bridge
DC Output @ 85 Deg C
38 Amp
Package Size
W:55mm L:45mm D:24mm
Itsm
400 A
VF(to)
0.85V
Tj(max)
150°C
rF
12mΩ
Terminals
M4 (1.5Nm)
Hole Centres
45mm (M4)
Gate Terminals
N/A
R th(j-c)
2.8°C/W
R th(c-h)
0.6°C/W
Weight
110g
Isolation
3kV
Factory Pack Qty
10
Certification
UL Listed
Powersem Headquarters
Germany
Â
Datasheet
Product Datasheet
Â
LEM ART-B22-D300-SP4, AC Measurement Rogowski Coil (coil only). 30cm Diameter, Class 0.5, 4.5M Shielded Cable Connection
Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary circuit (measurement). The patented Perfect Loop Technology dramatically reduces both the error due to the position of the measured conductor within the aperture, and the error due to the proximity of external conductors.
The ART series single phase flexible rope CT from LEM. In conjunction with AI-PMUL combined integrator & signal conditioner LEM offer True RMS 0-5V, 0-10V, 0-20mA, 4-20mA outputs, or direct linear outputs 0.333V or 0.166V
Included is a 30cm diameter rope CT, and 1.5M of twisted pair (1000V) output leads for connection to an integrator, or meter/logger with integration function.
LEM coils come with 5 year warranty
Features
Rated insulation voltage 1000 V Cat III PD2
Accuracy Class 0.5 (IEC 61869-2)
Protection degree IP67
⌀ 70, ⌀ 125, ⌀ 175, ⌀ 300 mm sensing aperture
3 m output cable (other lengths available see page 8)
Ambient temperature −40 °C … +80 °C
Very flexible and thin coil: 6.1 mm
Slot for attaching the loop on the primary with a cable tie
⌀ 2 mm hole to pass a security seal tampering
An innovative patented clasp drastically reduces the positioning error near the closing
Internal shield for enhanced measurement accuracy at low primary currents.
Advantages
Thin, flexible, and light weight solution
Very low positioning error
Quick, non-intrusive and easy setup
A single sensor for a large current range without overload
Less influenced by external fields
Adaptable for a large range of cable diameters
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010; IEC 61010-2-32 ed.3: 2012
1) IEC 61869-1 ed1.0: 2007; IEC 61869-2: ed1.0: 2012
1) IEC 61869-6: draft 2016; IEC 61869-10: draft 2016
UL
Specification
LEM Part Number
ART-B22-D300-SP4
Function
AC Current Measurement
Measuring Range
0 - 5,000 Amp RMS (Contact Us for Possible Replacement for wider range)
Secondary Voltage (Sensitivity)
22.5mV
Frequency Measuring Range
50-300kHz
Operating Voltage
Self Powered
Accuracy
0.5% from 25 to 5000 Amp
Phase Angle
< 0.004
Coil Diameter (⌀)
30cm
Coil Circumference
95cm
Integrator to Coil Cable
4.5M Twisted Pair / Coax
Maximum Voltage
1000V Reinforced insulation according to EN 61010-1
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
7.4kV
Overload
300,000 Amp
Termination Style
2 Stripped Wires
Weight
155g
Factory Pack Qty
1
Certifications
Â
UL, ROHS
Datasheet
Product Datasheet
Application Notes
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modeling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Â
Fastron Electronics FEFC203-100-T, 2 Stage EMI (RFI) Input [Inverter] Output [NON Inverter] Sine Wave Filter for 3-phase systems, 100 Amp, 400VAC
Features
Suitable alternative to Schaffner FN3258(Input) or FN5020(Output) Series
3 phase Input [Inverter] Output [NON Inverter] Sine Wave Filter with high attenuation
400VAC +10%
Applications
Input of VSD Drives or Controlled Rectifiers
Diesel Generator Output
CNC Machinese
Elevators
Power Supplies
For Industrial Applications
Suitable for use in equipment according to IEC/UL 60950
Medical Version Available
Specification
Fastron Part Number
FEFC203-100-T
Rated Voltage
400V
Rated Current
100A
Filter Stages
2 Stage (3 Phase 3 wire)
Operating Temperature
-25°C to 85°C
Filter Type
Excellent Attenuation for Sine Wave Output, Moderate Attenuation for input Line Filtering
Leakage Current
N/A
Mounting
Panel Mount
Material
Metal
Termination Style
Screw
Weight
4kg
Factory Pack Qty
1
Protection Class
From front side IP 40 acc. to IEC 60529
Isolation
2.2kV
CE
Yes
Â
Datasheet
Product Datasheet
Â
A53TP50D + HS212DR-F, Solid State Relay, and Heatsink Assembly, 3 Phase 90-280VAC Control, 36 Amp per phase @ 40 Deg C, 48-530VAC Load, LED Status Indicator
Features
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
D53TP50D + HS212DR-F
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
90-280VAC
Load Current
3 x 36 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Din Rail Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Â
Datasheet
D53TP Series
3 Phase SSR and Heatsink Mounted
HS212 Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies